Replacing a Beckhoff EL4032: Wiring and Output Checks
A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.
Manufacturer: BECKHOFF
Product No.: EL3122
Country of origin:Germany
Product Type: EtherCAT Terminals
Payment: T/T, Western Union
Weight: 55g
Dimensions: 12 mm x 100 mm x 68 mm
Shipping port: Xiamen
Warranty: 12 months
The BECKHOFF EL3122 is a 2-channel analog input EtherCAT Terminal designed for highly precise measurement of current signals in the 4 to 20 mA range. Both channels operate as differential inputs, providing a high-resolution 16-bit digital representation of the measured physical values. This terminal is integrated into the EtherCAT system via the standard E-bus connection, enabling fast communication and high-speed data acquisition.
To ensure optimal signal processing, the BECKHOFF EL3122 supports Distributed Clocks (DC) for highly synchronized sampling across the network. It features flexible configuration options, including activatable digital filters (FIR/IIR) to smooth input signals and eliminate high-frequency interference. Additionally, the terminal supports limit value monitoring and offers both standard and compact process images to optimize network bandwidth utilization.
| Manufacturer | BECKHOFF |
| Model | EL3122 |
| Product Type | EtherCAT Terminal |
| Number of Inputs | 2 differential inputs |
| Technology | Differential input |
| Bit Width in Process Image | Inputs: 8 bytes |
| Special Features | Standard and compact process image, activatable FIR/IIR filters, limit value monitoring |
| Signal Current | 4 to 20 mA |
| Resolution | 16 bit (including sign) |
| Measuring Error | < ±0.3% (relative to full scale value) |
| Internal Resistance | Typically 85 ohms + diode voltage |
| Input Filter Limit Frequency | 5 kHz |
| Common-Mode Voltage (Ucm) | Max. 10 V |
| Surge Voltage Resistance | Max. 35 V |
| Conversion Time | ~ 50 microseconds (fast mode ~ 35 microseconds) |
| Electrical Isolation | 500 V (E-bus / signal voltage) |
| Power Supply | Via the E-bus |
| Current Consumption E-bus | Typically 170 mA |
| Current Consumption Power Contacts | None |
| Current Load Power Contacts | Imax: 10 A |
| Distributed Clocks (DC) | Yes |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
| Weight | Approx. 55 g |
| Housing Material | Polycarbonate |
| Mounting | 35 mm DIN rail conforming to EN 60715 with lock |
| Wiring Technology | Spring actuation by screwdriver |
| Solid Conductor Connection Cross-section | 0.08 to 2.5 mm² (AWG 28 to 14) |
| Flexible Conductor Connection Cross-section | 0.08 to 2.5 mm² (AWG 28 to 14) |
| Ferrule Connection Cross-section | 0.14 to 1.5 mm² (AWG 26 to 16) |
| Stripping Length | 8 to 9 mm |
| Operating Temperature | -25 to +60 degC |
| Storage Temperature | -40 to +85 degC |
| Relative Humidity | 95%, no condensation |
| Protection Class | IP20 |
| Vibration/Shock Resistance | Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission | Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Approvals and Markings | CE, UL, ATEX |
| Ex Marking | II 3 G Ex nA IIC T4 Gc |
Global Express Shipping
Returns & Warranty

Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Country of origin |
Germany
|