Replacing a Beckhoff EL4032: Wiring and Output Checks
A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.
Manufacturer: BECKHOFF
Product No.: EL3174-0002
Country of origin:Germany
Product Type: EtherCAT Terminals
Payment: T/T, Western Union
Weight: 65g
Dimensions: 12 mm x 100 mm x 68 mm
Shipping port: Xiamen
Warranty: 12 months
The BECKHOFF EL3174-0002 is a high-performance, 4-channel analog input EtherCAT Terminal designed for flexible voltage and current measurement. This multi-function terminal features electrically isolated differential inputs, allowing each channel to be individually parameterised through the control system to process either current or voltage signals. The exceptional 2500 V functional isolation between channels and to the fieldbus makes it an ideal choice for preventing ground loop problems and ensuring high signal integrity in complex electrical environments.
As part of the modular BECKHOFF EtherCAT I/O system, the EL3174-0002 integrates directly into standard terminal segments. It operates with 16-bit resolution and supports Distributed Clocks (DC) for precise synchronization of measurements across the entire control network. The combination of flexible parameterization, electrical isolation, and high-speed EtherCAT communication provides reliable data acquisition for demanding test, measurement, and control systems.
| Parameter | Specification |
|---|---|
| Manufacturer | BECKHOFF |
| Exact Model | EL3174-0002 |
| Product Type | EtherCAT Terminal |
| Number of Inputs | 4 differential inputs |
| Housing Width | 12 mm |
| Parameter | Specification |
|---|---|
| Power Supply | Via the E-bus |
| Current Consumption E-bus | Typical 150 mA |
| Current Consumption Power Contacts | No contact to power contacts |
| Electrical Isolation | 2500 V functional isolation (channel/channel and channel/fieldbus) |
| Parameter | Specification |
|---|---|
| Measuring Range (Nominal) | -10 to +10 V or -20 to +20 mA (including 0...10 V and 0/4...20 mA) |
| Measuring Range (Technical) | -10.73 to +10.73 V or -21.47 to +21.47 mA |
| Resolution | 16 bit (including sign) |
| Internal Resistance | Greater than 200 kOhm (voltage) | Typical 85 Ohm (current) |
| Input Filter Limit Frequency | 5 kHz |
| Conversion Time | Minimum 150 microseconds |
| Measuring Error | Less than +/-0.2% (at 25 degC +/-5 degC, relative to full scale) |
| Parameter | Specification |
|---|---|
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
| Weight | Approximately 65 g |
| Mounting | On 35 mm DIN rail (EN 60715) with lock |
| Connection Type | CAGE CLAMP spring connection |
| Operating Temperature | -25 degC to +60 degC |
| Storage Temperature | -40 degC to +85 degC |
| Relative Humidity | 95%, non-condensing |
| Protection Class | IP20 |
| Approvals | CE, UL, ATEX, IECEx, cFMus |
The EL3174-0002 does not require hardware switches or physical address settings. All settings, including signal type configuration (voltage or current) and filter adjustments, are performed through the EtherCAT master configuration tool or the TwinCAT System Manager using the standard XML-based EtherCAT System Information (ESI) file.
Global Express Shipping
Returns & Warranty

Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Country of origin |
Germany
|