Description
To integrate modern control environments with existing network standards, the EL6752-0010 functions as a high-performance DeviceNet slave gateway designed for the EtherCAT Terminal system. This 1-channel communication interface enables high-speed data transfer and process image synchronization between an EtherCAT master and a primary DeviceNet master. Configured specifically as a DeviceNet slave, it allows seamless data exchange while keeping the networks galvanically isolated to prevent industrial noise and electrical interference from damaging sensitive controller electronics.
Housed in a compact 24 mm housing with standard signal LEDs for real-time status diagnostics, this module provides a reliable physical interface via a 5-pin open style connector. Integrating natively within the TwinCAT engineering environment, the terminal is engineered for rugged deployment in automated process environments requiring mixed-protocol network layouts.
Features
- 1-channel fieldbus interface acting as a DeviceNet slave
- Supported transmission rates of 125, 250, and 500 kbaud
- Galvanically decoupled 5-pin open style physical connection
- Status diagnostics through integrated hardware LEDs
- Compact terminal design optimized for DIN rail mounting space
- Direct integration with Beckhoff EtherCAT network architectures
Applications
- Integration of legacy DeviceNet field devices into EtherCAT networks
- Automotive manufacturing and assembly production lines
- Material handling systems and distribution facilities
- Process control systems and water treatment plants
Technical Specifications
| Manufacturer |
BECKHOFF |
| Part Number / Model |
EL6752-0010 |
| Technology |
DeviceNet slave terminal |
| Fieldbus |
DeviceNet |
| Number of Channels |
1 |
| Data Transfer Rates |
125, 250, 500 kbaud |
| Interface |
5-pin open style connector (galvanically decoupled) |
| Current Consumption E-bus |
typ. 260 mA |
| Operating Temperature |
-25 to +60 degC |
| Storage Temperature |
-40 to +85 degC |
| Relative Humidity |
95 %, no condensation |
| Vibration / Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity / Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Protection Rating |
IP20 |
| Installation Position |
Variable |
| Housing Material |
Polycarbonate |
| Dimensions (W x H x D) |
24 mm x 100 mm x 52 mm |
| Weight |
approx. 70 g |
| Wiring Connection |
Push-in connection |
Connections and Interfaces
| Connector Pin |
Function |
| Pin 1 |
V- (Power supply ground) |
| Pin 2 |
CAN_L (CAN low signal) |
| Pin 3 |
Shield (Drain/Shield wire) |
| Pin 4 |
CAN_H (CAN high signal) |
| Pin 5 |
V+ (DeviceNet network power) |
Installation Guidelines
- Mount the terminal onto a 35 mm DIN rail conforming to EN 60715, ensuring the integrated lock is fully engaged.
- Utilize the built-in double slot and key connection system when mounting side-by-side with other EtherCAT terminals to secure E-bus power and data contacts.
- Ensure fieldbus cabling is routed away from high-voltage motor lines to reduce risk of electromagnetic interference.
- Maintain sufficient panel ventilation space to keep ambient temperatures within the designated operating limit of -25 degC to +60 degC.
Compliance and Certifications
- CE
- UL
- ATEX: II 3 G Ex nA IIC T4 Gc