BECKHOFF

BECKHOFF ELM3142-0000 2-Channel Analog Input Multi-Function Measurement Terminal

SKU ELM3142-0000

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF
  • Product No.: ELM3142-0000
  • Origin Germany
  • Product Type: EtherCAT Terminals
  • Payment: T/T, Western Union
  • Weight: 0.35 kg
  • Dimensions: 30 mm x 100 mm x 95 mm
  • Shipping port: Xiamen
  • Warranty: 12 months

Tags

Quantity

Product Description

Description

The BECKHOFF ELM3142-0000 is a high-precision, 2-channel multi-function analog input measurement terminal from the ELM series, designed for industrial data acquisition and process monitoring within EtherCAT networks. This terminal offers versatile measurement options, allowing users to configure each channel individually for either high-accuracy voltage or current measurements. Housed in a durable zinc die-cast metal enclosure, it integrates into industrial control systems requiring highly stable, high-resolution measurements.

Featuring a 24-bit resolution and support for sampling rates up to 1 ksps (kilosamples per second) per channel in a multiplexed arrangement, the ELM3142-0000 provides excellent signal fidelity. It supports multiple voltage measurement ranges from ±1.25 V to ±10 V and current measurement of ±20 mA. Functional and connection diagnostics, such as broken wire and short circuit detection, ensure long-term operational reliability, while distributed clocks functionality offers synchronized timing accuracy under 1 microsecond.

Features

  • Two high-resolution analog input channels supporting differential measurement.
  • Individually configurable channels for voltage (±10 V to ±1.25 V) or current (±20 mA) measurements.
  • High-precision 24-bit resolution (including sign) for detailed signal acquisition.
  • Sampling rates up to 1 ksps per channel with oversampling factors ranging from 1 to 20.
  • Rugged zinc die-cast metal housing designed for optimal thermal performance and signal shielding.
  • Integrated functional diagnostics and connection diagnostics including wire break and short circuit detection.
  • E-bus interface with integrated Distributed Clocks for precise synchronization under 1 microsecond.
  • Push-in connection technology with a removable 4-pin service plug for ease of maintenance.

Applications

  • High-precision industrial test stands and measurement systems.
  • Multi-channel analog signal acquisition in automated assembly lines.
  • Process monitoring requiring synchronized voltage and current readings.
  • Control loops requiring high thermal stability and low measurement error.

Technical Specifications

General Specifications

Parameter Specification
Manufacturer BECKHOFF
Model ELM3142-0000
Product Family ELM Measurement Terminals
Number of Channels 2
Signal Type Differential
Resolution 24 bit (including sign)
Measurement Technology Voltage or current measurement, configurable per channel
Housing Material Zinc die-cast

Signal and Electrical Specifications

Parameter Specification
Voltage Input Ranges ±10 V, ±5 V, ±2.5 V, ±1.25 V
Current Input Range ±20 mA
Sampling Rate Max. 1 ksps per channel (multiplex)
Oversampling Factor n = 1 to 20 selectable
Internal Resistance > 4 MOhm (voltage), typ. 200 Ohm (current)
Measuring Error Typ. < ±100 ppm / ±0.01 % in select ranges (0 to 50 Celsius)
E-bus Current Consumption Typ. 250 mA
Power Contacts Current Load-dependent
Thermal Dissipation Typ. 2 W
Electrical Isolation (Channel/Bus) 707 V DC (type test)
Electrical Isolation (Channel/SGND) 707 V DC (type test)
Electrical Isolation (Channel/Channel) No

Mechanical and Environmental

Parameter Specification
Connection Technology Push-in, service plug 4-pin
Supported Conductor Types Solid, fine-stranded, ferrule
Connection Cross-section (Solid/Stranded) 0.2 to 1.5 mm² (AWG 24 to 14)
Connection Cross-section (Ferrule) 0.25 to 0.75 mm²
Stripping Length 8 to 9 mm
Dimensions (W x H x D) 30 mm x 100 mm x 95 mm
Weight Approx. 350 g
Mounting 35 mm DIN rail (EN 60715) with double slot/key connection
Operating Temperature -25 to +60 Celsius
Storage Temperature -40 to +85 Celsius

Certifications and Approvals

Parameter Specification
Approvals CE, UL

Installation Guidelines

  1. De-energize the System: Ensure all electrical power supplies (both E-bus and field power contacts) are completely switched off before mounting, removing, or wiring the module.
  2. DIN Rail Mounting: Mount the ELM3142-0000 on a standard 35 mm DIN rail (EN 60715). Utilize the double slot and key connection on the side for secure adjacent terminal locking.
  3. Wiring Connections: Connect conductors to the push-in terminals. Solid conductors can be plugged in directly. Fine-stranded wires or ferrules require spring actuation using a small screwdriver. Ensure wire strip length is between 8 and 9 mm.
  4. Service Plug Handling: Use the integrated 4-pin service plug for channel connections. Verify all signal lines are correctly mapped according to your electrical diagrams before energizing.
  5. E-Bus Verification: Power on the system and verify the functional LEDs. Confirm diagnostic indicators are green and the terminal is recognized in the TwinCAT system manager via the EtherCAT network.
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
FAQ
What measurement signal types are supported by the ELM3142-0000?
The BECKHOFF ELM3142-0000 supports configurable analog inputs on each channel, allowing differential measurement of voltages from ±1.25 V up to ±10 V and currents up to ±20 mA.
What is the resolution and maximum sampling rate of this terminal?
The BECKHOFF ELM3142-0000 features 24-bit resolution (including sign) and provides a maximum sampling rate of up to 1 ksps (1 ms) per channel using a multiplexed architecture.
Is there electrical isolation between the input channels?
No, the BECKHOFF ELM3142-0000 does not provide electrical isolation between individual channels, though it does feature 707 V DC electrical isolation between the channels and the E-bus/SGND.
What connection system does the terminal use for wiring?
The BECKHOFF ELM3142-0000 uses a 4-pin push-in service plug connection technology, accommodating solid conductors from 0.2 to 1.5 mm² (AWG 24 to 14) and fine-stranded or ferruled lines.
Reviews

ELM3142-0000

Stock &amp; lead time on request

Call
1 of 1

BECKHOFF ELM3142-0000 2-Channel Analog Input Multi-Function Measurement Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: ELM3142-0000

  • Country of origin:Germany

  • Product Type: EtherCAT Terminals

  • Payment: T/T, Western Union

  • Weight: 350g

  • Dimensions: 30 mm x 100 mm x 95 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The BECKHOFF ELM3142-0000 is a high-precision, 2-channel multi-function analog input measurement terminal from the ELM series, designed for industrial data acquisition and process monitoring within EtherCAT networks. This terminal offers versatile measurement options, allowing users to configure each channel individually for either high-accuracy voltage or current measurements. Housed in a durable zinc die-cast metal enclosure, it integrates into industrial control systems requiring highly stable, high-resolution measurements.

Featuring a 24-bit resolution and support for sampling rates up to 1 ksps (kilosamples per second) per channel in a multiplexed arrangement, the ELM3142-0000 provides excellent signal fidelity. It supports multiple voltage measurement ranges from ±1.25 V to ±10 V and current measurement of ±20 mA. Functional and connection diagnostics, such as broken wire and short circuit detection, ensure long-term operational reliability, while distributed clocks functionality offers synchronized timing accuracy under 1 microsecond.

Features

  • Two high-resolution analog input channels supporting differential measurement.
  • Individually configurable channels for voltage (±10 V to ±1.25 V) or current (±20 mA) measurements.
  • High-precision 24-bit resolution (including sign) for detailed signal acquisition.
  • Sampling rates up to 1 ksps per channel with oversampling factors ranging from 1 to 20.
  • Rugged zinc die-cast metal housing designed for optimal thermal performance and signal shielding.
  • Integrated functional diagnostics and connection diagnostics including wire break and short circuit detection.
  • E-bus interface with integrated Distributed Clocks for precise synchronization under 1 microsecond.
  • Push-in connection technology with a removable 4-pin service plug for ease of maintenance.

Applications

  • High-precision industrial test stands and measurement systems.
  • Multi-channel analog signal acquisition in automated assembly lines.
  • Process monitoring requiring synchronized voltage and current readings.
  • Control loops requiring high thermal stability and low measurement error.

Technical Specifications

General Specifications

Parameter Specification
Manufacturer BECKHOFF
Model ELM3142-0000
Product Family ELM Measurement Terminals
Number of Channels 2
Signal Type Differential
Resolution 24 bit (including sign)
Measurement Technology Voltage or current measurement, configurable per channel
Housing Material Zinc die-cast

Signal and Electrical Specifications

Parameter Specification
Voltage Input Ranges ±10 V, ±5 V, ±2.5 V, ±1.25 V
Current Input Range ±20 mA
Sampling Rate Max. 1 ksps per channel (multiplex)
Oversampling Factor n = 1 to 20 selectable
Internal Resistance > 4 MOhm (voltage), typ. 200 Ohm (current)
Measuring Error Typ. < ±100 ppm / ±0.01 % in select ranges (0 to 50 Celsius)
E-bus Current Consumption Typ. 250 mA
Power Contacts Current Load-dependent
Thermal Dissipation Typ. 2 W
Electrical Isolation (Channel/Bus) 707 V DC (type test)
Electrical Isolation (Channel/SGND) 707 V DC (type test)
Electrical Isolation (Channel/Channel) No

Mechanical and Environmental

Parameter Specification
Connection Technology Push-in, service plug 4-pin
Supported Conductor Types Solid, fine-stranded, ferrule
Connection Cross-section (Solid/Stranded) 0.2 to 1.5 mm² (AWG 24 to 14)
Connection Cross-section (Ferrule) 0.25 to 0.75 mm²
Stripping Length 8 to 9 mm
Dimensions (W x H x D) 30 mm x 100 mm x 95 mm
Weight Approx. 350 g
Mounting 35 mm DIN rail (EN 60715) with double slot/key connection
Operating Temperature -25 to +60 Celsius
Storage Temperature -40 to +85 Celsius

Certifications and Approvals

Parameter Specification
Approvals CE, UL

Installation Guidelines

  1. De-energize the System: Ensure all electrical power supplies (both E-bus and field power contacts) are completely switched off before mounting, removing, or wiring the module.
  2. DIN Rail Mounting: Mount the ELM3142-0000 on a standard 35 mm DIN rail (EN 60715). Utilize the double slot and key connection on the side for secure adjacent terminal locking.
  3. Wiring Connections: Connect conductors to the push-in terminals. Solid conductors can be plugged in directly. Fine-stranded wires or ferrules require spring actuation using a small screwdriver. Ensure wire strip length is between 8 and 9 mm.
  4. Service Plug Handling: Use the integrated 4-pin service plug for channel connections. Verify all signal lines are correctly mapped according to your electrical diagrams before energizing.
  5. E-Bus Verification: Power on the system and verify the functional LEDs. Confirm diagnostic indicators are green and the terminal is recognized in the TwinCAT system manager via the EtherCAT network.
Loading product navigation…

What measurement signal types are supported by the ELM3142-0000?

The BECKHOFF ELM3142-0000 supports configurable analog inputs on each channel, allowing differential measurement of voltages from ±1.25 V up to ±10 V and currents up to ±20 mA.

What is the resolution and maximum sampling rate of this terminal?

The BECKHOFF ELM3142-0000 features 24-bit resolution (including sign) and provides a maximum sampling rate of up to 1 ksps (1 ms) per channel using a multiplexed architecture.

Is there electrical isolation between the input channels?

No, the BECKHOFF ELM3142-0000 does not provide electrical isolation between individual channels, though it does feature 707 V DC electrical isolation between the channels and the E-bus/SGND.

What connection system does the terminal use for wiring?

The BECKHOFF ELM3142-0000 uses a 4-pin push-in service plug connection technology, accommodating solid conductors from 0.2 to 1.5 mm² (AWG 24 to 14) and fine-stranded or ferruled lines.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Implementing 3-Switch XOR Ladder Logic with Internal Bit

Implement a 3-SPST switch XOR light circuit in LogixPro or RSLogix 500 using an internal relay bit. Includes truth tables, boolean equations, and verified.

Building a Modbus RTU Network with CompactLogix and DeltaV

Integrate Allen-Bradley CompactLogix, Caterpillar ATS, and generators into DeltaV DCS over Modbus RTU. Covers ProSoft MVI69-MCM, Miille DIN266 gateways.

ONS Instruction Not Energizing OTE in Studio 5000 Ladder Logic

ONS instruction fires but the OTE coil never latches in Studio 5000 because the one-shot is only true for one scan. Use OTL/OTU or seal-in logic instead.

Kinetix 5500 EtherNet/IP Network Switch Requirements and Topology

Configure Allen-Bradley Kinetix 5500 servo drives on EtherNet/IP. Covers CIP Sync, IEEE 1588 V2 timing, Stratix selection, DLR topology, and HMI.

Moving Average Filtering in DCS and PLC Analog Control

A moving-average filter is the sliding-window smoother most instrument engineers drop into DCS and PLC analog paths. Here is how the window works, how N and sample time set lag, and when a...

GE Mark VI Function Blocks for Gas Turbine Control Logic

On Frame 5–9 gas turbines, GE Mark VI and Mark VIe run control as function-block application software. This article maps process, protection, and sequencing functions—and what Toolbox ST access...