Description
Facilitating high-precision analog signal generation directly in decentralized environments, the Beckhoff EPP4174-0002 EtherCAT P Box integrates four individually parameterizable analog outputs within a ruggedized IP67 housing. This module eliminates the need for protective control cabinets by allowing users to transmit both EtherCAT telemetry and dual 24 V DC power supplies (US for system/sensor power and UP for peripheral/actuator power) through a single, P-coded M8 cable interface. Designed for demanding field use, each channel on the EPP4174-0002 can be independently configured to output standard control signals, ensuring direct compatibility with a wide array of field actuators, positioning valves, and variable speed drives.
Key Features
-
Flexible Signal Configuration: Individually parameterize each of the 4 channels to support -10/+10 V voltage loops or 0/4...20 mA current loops.
-
EtherCAT P Cabling Solution: Uses standard M8 P-coded industrial connectors to combine high-speed communication and power distribution on a single connection.
-
Industrial Durability: Complete IP65, IP66, and IP67 protection class housing, allowing direct machine mounting in environments with moisture, dust, and vibration.
-
High-Resolution DAC: Embedded 16-bit digital-to-analog converter with a highly responsive conversion time of approximately 40 microseconds.
-
Integrated Actuator Supply: Actuator field power is distributed directly from the auxiliary voltage UP channel, simplifying external wiring configurations.
Industrial Applications
- Decentralized control valve positioning and pneumatic actuator modulation in process lines.
- Speed and torque setpoint generation for distributed variable frequency motor drives.
- Remote analog instrumentation interfacing in harsh manufacturing and maritime environments.
- Direct machinery integration for distributed material handling and packaging systems.
Technical Specifications
| Parameter |
Specification Value |
| Manufacturer |
Beckhoff Automation |
| Model Reference |
EPP4174-0002 |
| Interface Protocol |
EtherCAT P |
| Number of Channels |
4 analog outputs |
| Signal Formats |
-10 to +10 V | 0 to 20 mA | 4 to 20 mA (Configurable per channel) |
| Resolution |
16 bit |
| Conversion Time |
Approx. 40 microseconds |
| Voltage Mode Load |
> 5 kOhm |
| Current Mode Load |
< 500 Ohm |
| Accuracy Deviation |
< 0.1% (Relative to full scale limit value) |
| Power Feed Nominal |
24 V DC (-15% / +20%) |
| Current Usage (US) |
Typ. 100 mA |
| Electrical Isolation |
500 V RMS |
| Environmental Limits |
Operating: -25 to +60 Celsius | Storage: -40 to +85 Celsius |
| Enclosure Rating |
IP65 / IP66 / IP67 (Conforms to EN 60529) |
| Country of Origin |
Germany |
| Shipping Weight (Calculated) |
0.50 kg (with protective system packaging) |
| Package Dimensions (Calculated) |
150 x 50 x 40 mm |
Connections and Interfaces
| M12 Output Pin |
Function / Assignment |
| Pin 1 |
+24 V DC Actuator Supply (UP) |
| Pin 2 |
Analog Output + (Voltage/Current Signal) |
| Pin 3 |
GND (UP) (Actuator Reference) |
| Pin 4 |
Analog Output - (Signal Ground Reference) |
| Pin 5 |
Functional Earth (FE Shield Connection) |
Empirical Engineering Insights
Alternative Models & Compatibility
The EPP4174-0002 operates strictly within EtherCAT P environments. It is physically key-coded with a P-coded M8 connector scheme to prevent accidental insertion of standard EtherCAT cables. If replacing or interfacing with traditional standard EtherCAT segments (EP series), you must deploy an intermediate hub or coupler (such as the EP9224 or EK1300) to safely transition and inject the combined US and UP power lines.
Application Pitfalls & Engineering Notes
When driving long analog cables in high electromagnetic interference (EMI) environments, ensure the shielded M12 connectors are grounded to functional earth via the FE pin. Avoid running analog lines adjacent to high-power motor lines. If a current loop channel encounters open-circuit status, the 16-bit DAC register values in TwinCAT will saturate and reflect a diagnostic fault code; ensure error handling algorithms are standard practice within the PLC task cycles.
Commissioning & Wiring Tips
Always complete your configuration within TwinCAT System Manager under the CoE (CanOpen over EtherCAT) directory before supplying active load connections. Do not swap configurations from current to voltage online while an active actuator is connected, as short-circuits or excess drive current may occur. Make sure the total current draw sourced from the auxiliary voltage UP does not exceed the continuous rating of the distribution block.
Installation Guidelines
CRITICAL WARNING:
Disconnect and isolate all power sources (US and UP) before connecting or disconnecting the M8 EtherCAT P or M12 analog cabling. Hot-plugging industrial connectors in wet or hazardous conditions can compromise the internal electrical isolation limits and potentially cause damage to the integrated D/A hardware.
1
Mount the EPP4174-0002 unit using the integrated screw points directly onto flat, vibration-resistant machinery structures or mounting brackets.
2
Connect the incoming EtherCAT P lines using shielded M8 P-coded screw-type connectors, tightening to the recommended OEM torque specification.
3
Configure the analog output parameters (current / voltage profiles) in the TwinCAT System Manager software, ensuring signal ranges match downstream actuator requirements.