1 of 1

Beckhoff EPP4174-0002 EtherCAT P Box 4-Channel Analog Output Module

Beckhoff EPP4174-0002 EtherCAT P Box 4-Channel Analog Output Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EPP4174-0002

  • Country of origin:Germany

  • Product Type: EtherCAT P Box Modules

  • Payment: T/T, Western Union

  • Weight: 500g

  • Dimensions: 150 x 50 x 40 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Facilitating high-precision analog signal generation directly in decentralized environments, the Beckhoff EPP4174-0002 EtherCAT P Box integrates four individually parameterizable analog outputs within a ruggedized IP67 housing. This module eliminates the need for protective control cabinets by allowing users to transmit both EtherCAT telemetry and dual 24 V DC power supplies (US for system/sensor power and UP for peripheral/actuator power) through a single, P-coded M8 cable interface. Designed for demanding field use, each channel on the EPP4174-0002 can be independently configured to output standard control signals, ensuring direct compatibility with a wide array of field actuators, positioning valves, and variable speed drives.

Key Features

  • Flexible Signal Configuration: Individually parameterize each of the 4 channels to support -10/+10 V voltage loops or 0/4...20 mA current loops.
  • EtherCAT P Cabling Solution: Uses standard M8 P-coded industrial connectors to combine high-speed communication and power distribution on a single connection.
  • Industrial Durability: Complete IP65, IP66, and IP67 protection class housing, allowing direct machine mounting in environments with moisture, dust, and vibration.
  • High-Resolution DAC: Embedded 16-bit digital-to-analog converter with a highly responsive conversion time of approximately 40 microseconds.
  • Integrated Actuator Supply: Actuator field power is distributed directly from the auxiliary voltage UP channel, simplifying external wiring configurations.

Industrial Applications

  • Decentralized control valve positioning and pneumatic actuator modulation in process lines.
  • Speed and torque setpoint generation for distributed variable frequency motor drives.
  • Remote analog instrumentation interfacing in harsh manufacturing and maritime environments.
  • Direct machinery integration for distributed material handling and packaging systems.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Reference EPP4174-0002
Interface Protocol EtherCAT P
Number of Channels 4 analog outputs
Signal Formats -10 to +10 V | 0 to 20 mA | 4 to 20 mA (Configurable per channel)
Resolution 16 bit
Conversion Time Approx. 40 microseconds
Voltage Mode Load > 5 kOhm
Current Mode Load < 500 Ohm
Accuracy Deviation < 0.1% (Relative to full scale limit value)
Power Feed Nominal 24 V DC (-15% / +20%)
Current Usage (US) Typ. 100 mA
Electrical Isolation 500 V RMS
Environmental Limits Operating: -25 to +60 Celsius | Storage: -40 to +85 Celsius
Enclosure Rating IP65 / IP66 / IP67 (Conforms to EN 60529)
Country of Origin Germany
Shipping Weight (Calculated) 0.50 kg (with protective system packaging)
Package Dimensions (Calculated) 150 x 50 x 40 mm

Connections and Interfaces

M12 Output Pin Function / Assignment
Pin 1 +24 V DC Actuator Supply (UP)
Pin 2 Analog Output + (Voltage/Current Signal)
Pin 3 GND (UP) (Actuator Reference)
Pin 4 Analog Output - (Signal Ground Reference)
Pin 5 Functional Earth (FE Shield Connection)

Empirical Engineering Insights

Alternative Models & Compatibility

The EPP4174-0002 operates strictly within EtherCAT P environments. It is physically key-coded with a P-coded M8 connector scheme to prevent accidental insertion of standard EtherCAT cables. If replacing or interfacing with traditional standard EtherCAT segments (EP series), you must deploy an intermediate hub or coupler (such as the EP9224 or EK1300) to safely transition and inject the combined US and UP power lines.

Application Pitfalls & Engineering Notes

When driving long analog cables in high electromagnetic interference (EMI) environments, ensure the shielded M12 connectors are grounded to functional earth via the FE pin. Avoid running analog lines adjacent to high-power motor lines. If a current loop channel encounters open-circuit status, the 16-bit DAC register values in TwinCAT will saturate and reflect a diagnostic fault code; ensure error handling algorithms are standard practice within the PLC task cycles.

Commissioning & Wiring Tips

Always complete your configuration within TwinCAT System Manager under the CoE (CanOpen over EtherCAT) directory before supplying active load connections. Do not swap configurations from current to voltage online while an active actuator is connected, as short-circuits or excess drive current may occur. Make sure the total current draw sourced from the auxiliary voltage UP does not exceed the continuous rating of the distribution block.

Installation Guidelines

CRITICAL WARNING:

Disconnect and isolate all power sources (US and UP) before connecting or disconnecting the M8 EtherCAT P or M12 analog cabling. Hot-plugging industrial connectors in wet or hazardous conditions can compromise the internal electrical isolation limits and potentially cause damage to the integrated D/A hardware.

1

Mount the EPP4174-0002 unit using the integrated screw points directly onto flat, vibration-resistant machinery structures or mounting brackets.

2

Connect the incoming EtherCAT P lines using shielded M8 P-coded screw-type connectors, tightening to the recommended OEM torque specification.

3

Configure the analog output parameters (current / voltage profiles) in the TwinCAT System Manager software, ensuring signal ranges match downstream actuator requirements.

Loading product navigation…

Can the EPP4174-0002 module be connected to a standard EtherCAT network?

No. The module features P-coded M8 interfaces designed for unified EtherCAT P lines containing integrated system and peripheral power loops. It requires an EtherCAT P junction or master interface to link into traditional EtherCAT systems.

How is the signal output range configured for each individual channel?

Each analog output channel is parameterized independently. Signal settings (-10/+10 V, 0-20 mA, or 4-20 mA) must be set via the CANopen over EtherCAT (CoE) online directory inside TwinCAT software.

What is the maximum allowable load for current output mode on this module?

The output load for channels configured for current signals must remain below 500 Ohms. Exceeding this boundary causes DAC signal clipping and registers a saturation error in the process image.

How are connected field actuators powered by this module?

Actuators receive direct supply current from the distributed UP auxiliary power line. This is routed through the M12 connector's Pin 1, avoiding additional power drops.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...