Engineered for decentralized automation environments, the Beckhoff IP2312-B800 is a ruggedized digital I/O fieldbus box that facilitates direct signal interfacing in the field without the need for a protective control cabinet. This module integrates a balanced combination of four digital inputs and four digital outputs, communicating via a reliable RS485 physical interface.

The unit features robust M12 connections, allowing for secure and quick cabling of field devices and network communication. Designed to withstand harsh industrial conditions, the IP2312-B800 is ideal for localized control structures where fast signal acquisition (0.2 ms input filter) and reliable actuator switching (0.5 A per output channel) are required.

Features

  • Four digital inputs with a fast 0.2 ms signal filter to ensure accurate pulse detection.
  • Four digital outputs sourcing up to 0.5 A per channel at 24 V DC.
  • RS485 interface optimized for serial industrial fieldbus protocols.
  • Industrial-grade M12 screw connectors for secure signal, power, and bus routing.
  • Highly durable IP67-rated enclosure resistant to dust, moisture, and mechanical vibrations.

Applications

  • Decentralized conveyor systems and material handling routing.
  • Machine-mount sensor/actuator hubs in automotive and manufacturing assembly lines.
  • Food processing and packaging facilities requiring washdown protection.
  • Distributed remote I/O processing over long-distance RS485 links.

Technical Specifications

Manufacturer BECKHOFF
Model/Part Number IP2312-B800
Module Type Fieldbus Box I/O Module
Communication Interface RS485
Digital Inputs 4 channels (24 V DC)
Input Filter Time 0.2 ms
Digital Outputs 4 channels (24 V DC)
Max. Output Current 0.5 A per channel
Connection Technology M12 round connectors
Protection Class IP67
Shipping Weight 2.0 kg

Connections and Interfaces

Connection Type Connector Style Function
Fieldbus M12 RS485 Incoming and Outgoing lines
Digital Inputs M12 Channels 0 to 3 for 24 V DC sensors
Digital Outputs M12 Channels 0 to 3 for 24 V DC / 0.5 A actuators
Power Supply M8 / M12 24 V DC control voltage input and downstream feed

Installation Guidelines

  • Mounting: Secure the module directly to the machine frame or flat surfaces using the integrated mounting holes. Ensure the mounting surface is clean and level.
  • Grounding: Connect the functional ground (FE) directly to the machine potential via low-resistance grounding straps.
  • Torque Spec: Hand-tighten all M12 and M8 connections, then apply the specified torque of 0.6 Nm using an industrial torque wrench to maintain the IP67 protective seal.
  • Cabling: Keep signal and communication cables separate from high-voltage AC lines to prevent electromagnetic interference.

Compliance and Certifications

  • CE
  • UL

What is the primary function of the Beckhoff IP2312-B800?

The IP2312-B800 is a decentralized fieldbus box that connects 4 digital inputs and 4 digital outputs directly to an RS485 network in harsh IP67-rated environments.

What is the current rating for the digital outputs on this module?

Each digital output channel can source up to 0.5 A at 24 V DC.

What is the response or filter time for the digital inputs?

The module has a built-in input filter time of 0.2 ms for fast and accurate signal processing.

Does this module require an additional control enclosure?

No, because the IP2312-B800 is IP67 rated, it can be mounted directly on machinery without an external control cabinet.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Micro Drive Specialist EMS Bets on Custom Engineering to Broaden Market Appeal

UK micro-drive specialist EMS is pairing Faulhaber high-torque gearheads and compact motion controllers with in-house custom engineering—aiming beyond catalog sales into tailored mechatronics.

Bringing Object-Oriented Thinking to PLC Programming

Copy-paste ladder does not scale. Object-oriented PLC techniques—user-defined structures and instructions—cut duplication, propagate fixes once, and keep large multi-device programs readable.

Why Process Safety Management Programs Fail Even When OSHA Boxes Are Checked

OSHA boxes checked is not the same as a living PSM system. Refinery history shows programs fail when procedures, training, contractors, and investigations drift from how the plant actually runs.

What Is SCADA? Supervisory Control Without Replacing the PLC

SCADA sits above PLCs and RTUs: it acquires field data, alarms operators, and issues supervisory commands across plants and remote assets—without replacing local deterministic control.

What Is a VFD? Variable Frequency Drives That Actually Move the Needle

A VFD turns fixed-frequency mains into controlled voltage and frequency so AC motors match real load—cutting pump and fan energy while tightening torque, soft-start, and braking behavior.

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.