Troubleshooting Beckhoff EPP2008-0001 Output Faults
A field checklist for EPP2008-0001 current limits, supply voltage, channel LEDs, connector coding and load-related output faults.
Manufacturer: BECKHOFF
Product No.: IP2332-B518
Country of origin:Germany
Product Type: Fieldbus Modules
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
The BECKHOFF IP2332-B518 is a compact decentralized Fieldbus Box designed for industrial automation environments requiring distributed signal acquisition and control. Engineered for direct machine-level mounting without the need for control cabinets, this IP65, IP66, and IP67 protected module integrates into CANopen network architectures. It facilitates reliable data communication, process data exchange, and sensor or actuator connection across harsh industrial machinery and plant floors.
Equipped with an integrated CANopen interface, the unit supports extensive process data object (PDO) configurations and diagnostic functions. Power distribution, fieldbus connections, and peripheral signal integration are handled via robust industrial circular connectors, supporting decentralized system topologies where space efficiency and environmental resistance are critical.
| Parameter | Specification |
|---|---|
| Manufacturer | BECKHOFF |
| Exact Model | IP2332-B518 |
| Product Type | Fieldbus Box |
| Extension modules | - |
| Country of Origin | Germany |
| Parameter | Specification |
|---|---|
| Bus Interface | 1 x M12 plug, 5-pin; 1 x M12 socket, 5-pin (tee-connector integrated) |
| Data Transfer Rates | Automatic detection of 10 kbaud up to 1 Mbaud |
| Data Transfer Medium | Shielded copper cable, 2 x signal, 1 x CAN ground (recommended) |
| Number of PDOs (CANopen) | 16 send and 16 receive process data objects |
| Additional CANopen Features | Life, node guarding, emergency object, variable mapping, store/restore |
| I/O Communication Types | Event driven, cyclic, synchron, polling |
| Configuration Possibility | Through KS2000 or the controller (service data objects) |
| Parameter | Specification |
|---|---|
| Power Supply Control Voltage | 24 V DC (-15 %/+20 %) |
| Power Supply Load Voltage | According to I/O type |
| Power Supply Connection | Feed: 1 x M8 male socket, 4-pin; Downstream connection: 1 x M8 female socket, 4-pin |
| Box Supply Current | 45 mA + current consumption of sensors, max. 0.5 A |
| Auxiliary Power Current | According to I/O type |
| Electrical Isolation | Control voltage/fieldbus: 500 V; Control voltage/inputs or outputs: according to I/O type |
| Parameter | Specification |
|---|---|
| Operating Temperature Range | 0 to +55 degC |
| Storage Temperature Range | -25 to +85 degC |
| Vibration Resistance | Conforms to EN 60068-2-6 |
| Shock Resistance | Conforms to EN 60068-2-27 |
| EMC Immunity | Conforms to EN 61000-6-2 |
| EMC Emission | Conforms to EN 61000-6-4 |
| Protection Rating | IP65, IP66, IP67 (conforms to EN 60529) |
| Installation Position | Variable |
| Approvals and Markings | CE, UL |
| Interface | Function |
|---|---|
| M12 Plug (5-pin) / M12 Socket (5-pin) | CANopen bus interface (integrated tee-connector) |
| M8 Male Socket (4-pin) | Control voltage power supply feed |
| M8 Female Socket (4-pin) | Downstream control voltage power supply connection |