Description
Designed to facilitate seamless integration of utility metering devices, the Beckhoff KL6781 operates as a single-channel M-Bus master terminal within the standard Beckhoff Bus Terminal system. This module enables direct, bidirectional communication with up to 40 standard M-Bus loads, such as heat, water, electricity, or gas meters, over a single bus segment without requiring external level converters. Operating in master-slave mode via polling, the KL6781 transmits data standard M-Bus physics, enabling consolidated energy management and resource tracking directly from the TwinCAT control environment.
The terminal features a 24-byte process image for inputs and outputs, allowing robust data transfer rates ranging from 300 to 9600 baud. Integration is streamlined through the TwinCAT PLC M-Bus library, which provides specialized function blocks for rapid field configuration. With built-in short-circuit protection and 500 V electrical isolation between the K-bus and the M-Bus physics, the module ensures robust operation and system-wide protection against electrical faults in harsh industrial or commercial environments.
Features
-
Single-Channel Architecture: Dedicated M-Bus interface supporting up to 40 standard M-Bus loads (1.5 mA current consumption per load).
-
Flexible Baud Rates: Configurable data transfer rates from 300 to 9600 baud (default transmission set to 2400 baud).
-
Electrical Isolation: Complete 500 V isolation barrier safeguarding the internal K-bus from the M-Bus network.
-
Integrated Protection: Full short-circuit proof design to prevent module failure during field wiring faults.
-
Software Compatibility: Programmed and configured directly through TwinCAT using official M-Bus PLC function blocks.
Applications
- Commercial and industrial building automation systems (BAS).
- Sub-metering networks for monitoring water, gas, steam, and electricity consumption.
- Energy management systems (EMS) compliant with ISO 5001 standards.
- District heating stations and utility billing infrastructure.
Technical Specifications
Category
Parameter
Value
| Administrative |
Manufacturer |
Beckhoff Automation |
| Part Number/Model |
KL6781 |
| Product Series |
Bus Terminal System (KL Series) |
| Communication & Bus |
Technology |
M-Bus |
| Data Transfer Standard |
M-Bus physics |
| Number of Channels |
1 |
| Maximum Connected Loads |
40 standard loads (1.5 mA each) |
| Data Transfer Rates |
300 to 9600 baud (default: 2400 baud) |
| Bus Access |
Master-slave mode (polling) |
| Electrical Data |
Nominal Voltage |
24 V DC (-10% / +8%) |
| Current Consumption (K-bus) |
Typically 65 mA |
| Current Consumption (Power Contacts) |
Maximum 250 mA |
| Protection & Safety |
Short-Circuit Protection |
Yes |
| Electrical Isolation |
500 V (K-bus / M-Bus) |
| Process Image Bit Width |
24 bytes input / 24 bytes output |
| Environmental & Mechanical |
Weight |
Approx. 60 g |
Operating Temperature |
0 to 55 degC |
| Storage Temperature |
-25 to 85 degC |
| Relative Humidity |
95%, non-condensing |
| Standards & Approvals |
Vibration/Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Certifications & Marks |
CE, UL |
Connections and Interfaces
| Terminal Point |
Signal/Function |
Description |
| 1 |
M+ |
M-Bus Connection (+) |
| 2 |
Shield |
Shielding / Functional Ground |
| 3 |
+24 V DC |
External Power Supply (+) |
| 5 |
M- |
M-Bus Connection (-) |
| 7 |
0 V DC |
External Power Supply (0 V) |
Installation Guidelines
-
Mounting: Mount the terminal vertically on standard 35 mm DIN rails (EN 60715) within an IP20-rated enclosure or control cabinet.
-
Wiring: Keep maximum cable lengths on the M-Bus segment below 300 meters. Use shielded twisted-pair (STP) cabling for optimal noise immunity.
-
Grounding: Connect the shield connection point directly to a low-impedance functional ground or DIN rail clamp.
-
Ventilation: Ensure a clearance of at least 30 mm above and below the terminal block to maintain normal operating temperatures between 0 and 55 degC.