Description

For space-critical control architectures requiring high-density digital outputs, the Beckhoff KM2008-0001 compact terminal module delivers 64 digital outputs with a pluggable 1-wire connection design. This module enables efficient transmission of binary control signals from the K-bus system to actuators at the process level with complete electrical isolation. Integrating seamlessly into standard I/O environments, the high-density design groups outputs into eight channels per pluggable connector block, significantly reducing control cabinet space requirements while maintaining robust diagnostic and wiring flexibility.

Features

  • 64 digital output channels organized in an 8 x 8 distribution pattern.
  • Pluggable wiring interface with 1-wire connection design for fast, error-free field installation.
  • Robust protection mechanisms including short-circuit proof outputs and integrated reverse voltage protection.
  • High-efficiency backplane communication with negligible K-bus current consumption of typically 5 mA.
  • Galvanic isolation of 500 V between the K-bus and the field potential to prevent noise propagation.
  • Compact, DIN-rail mountable housing featuring a dual slot-and-key connection system for secure side-by-side assembly.

Applications

  • High-density control cabinet engineering and automation assembly.
  • Specialized machinery manufacturing requiring multiple low-power actuator controls.
  • Process automation and packaging systems utilizing decentralized I/O layouts.
  • Factory automation systems integrated via K-bus communication networks.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model KM2008-0001
Number of Outputs 64 (8 x 8)
Connection Technology Pluggable 1-wire connector
Nominal Voltage 24 V DC
Max. Output Current 0.5 A per channel (short-circuit proof)
Load Types Ohmic, inductive, lamp load
Short-Circuit Current Less than 2 A
Breaking Energy Less than 150 mJ per channel
Reverse Voltage Protection Yes
Electrical Isolation 500 V (K-bus/field potential)
K-Bus Current Consumption Typ. 5 mA
Power Contacts Current Consumption None (no power contacts)
Process Image Bit Width 64 outputs
Connection Cross-Section 0.08 to 1.5 mm (stranded or solid wire)
Stripping Length 8 mm
Dimensions (W x H x D) 123 mm x 100 mm x 55 mm
Weight Approx. 310 g (with 1-pin connector)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95%, non-condensing
Protection Class IP20
Installation Position Variable
Mounting 35 mm DIN rail (EN 60715) with lock

Installation Guidelines

  • Mounting: Securely snap the module onto a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking mechanism engages properly.
  • Side-by-Side Installation: Connect adjacent modules utilizing the integrated double slot-and-key side mechanics to maintain terminal stability.
  • Wiring: Strip conductor ends to exactly 8 mm before inserting into the pluggable terminal block. Suitable for solid and stranded conductors ranging from 0.08 to 1.5 mm.
  • Environmental Considerations: Ensure ventilation space allows the ambient operating temperature to remain within the 0 to +55 degC limit. Avoid installation in environments with condensing humidity.

Compliance and Certifications

  • CE
  • EMC Immunity conforming to EN 61000-6-2
  • EMC Emission conforming to EN 61000-6-4
  • Vibration Resistance conforming to EN 60068-2-6
  • Shock Resistance conforming to EN 60068-2-27

FAQ

What is the connection type of the Beckhoff KM2008-0001?

The KM2008-0001 features a pluggable 1-wire connector interface, which simplifies high-density field wiring for 64 digital output channels.

What is the maximum output current supported per channel?

Each of the 64 output channels supports a maximum load current of 0.5 A. The outputs are fully short-circuit proof.

Does the KM2008-0001 require power contacts for backplane communication?

No, this terminal module does not utilize power contacts. It communicates and draws power via the K-bus, with a typical current consumption of 5 mA.

What load types can the KM2008-0001 control?

The KM2008-0001 is designed to switch ohmic, inductive, and lamp loads up to its specified electrical limit of 0.5 A per channel.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Commissioning OPC UA in KEPServerEX: A Field Checklist

A practical commissioning sequence for KEPServerEX OPC UA connections: define data ownership, test tags locally, configure endpoint and certificate trust, limit access, then verify failure recovery...

Set a PLC Commissioning Laptop IP Without Losing Access

Commissioning an Ethernet-connected PLC often starts with the laptop, not the controller. Learn how to record existing settings, choose a temporary address, test connectivity, and restore the plant...

Designing Automation for Combustible Dust Hazards

Combustible dust controls require more than alarms. Learn how to map dust generation, select instrumentation, design interlocks, handle failed feedback, test safe states, and maintain the full...

Hairpin Stators: Benefits, Limits, and Inspection

Hairpin windings raise slot fill and support compact traction motors, but conductor geometry, AC losses, insulation damage, weld quality, and cooling determine whether the design meets its targets.

Using Ansible for Controlled SCADA Server Changes

Use Ansible to standardize SCADA server changes without expanding OT risk. This guide covers inventories, idempotent playbooks, staged testing, credentials, logging, and practical rollback controls.

Securing Remote PLC Access Beyond the VPN

A VPN encrypts the path to an industrial network, but secure remote PLC work also needs identity controls, segmented access, change approval, logging, safe operating boundaries, and tested recovery...