BECKHOFF

BECKHOFF KS3044 Bus Terminal

SKU KS3044

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: KS3044

  • Country of origin:Germany

  • Product Type: Bus Terminals

  • Payment: T/T, Western Union

  • Weight: 70g

  • Dimensions: 6.8 cm x 1.2 cm x 10.0 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The BECKHOFF KS3044 is a 4-channel analog input Bus Terminal designed for processing 0 to 20 mA process signals in industrial automation architectures. Operating as part of the established BECKHOFF Bus Terminal system, this unit features pluggable wiring technology to facilitate efficient installation and maintenance without disrupting field cabling. It interfaces directly with compatible bus couplers via the internal K-bus, transmitting digitized process values to the higher-level control system.

Engineered for single-ended signal acquisition, the KS3044 delivers 12-bit resolution across its four independent channels. The terminal is housed in a compact polycarbonate enclosure designed for standard 35 mm DIN rail mounting, incorporating electrical isolation between the field-side signals and the K-bus logic. It is suited for process measurement tasks requiring standard current loop monitoring within machine control cabinets.

Features

  • Four analog input channels supporting 0 to 20 mA signal current ranges
  • Single-ended measurement technology with internal resistance and series diode drop
  • 12-bit analog-to-digital resolution for precise process data representation
  • Pluggable wiring level for simplified installation and pre-wired connector replacement
  • K-bus interface for communication and power distribution within the Bus Terminal segment
  • DIN rail mounting design utilizing standard 35 mm mounting rails conforming to EN 60715

Applications

  • Acquisition of analog sensor signals in industrial machinery and factory automation systems
  • Process monitoring of 0 to 20 mA current loops in control cabinet installations
  • Distributed data acquisition across modular machine architectures using BECKHOFF Bus Terminals

Technical Specifications

General

Parameter Specification
Manufacturer BECKHOFF
Exact Model KS3044
Product Type Bus Terminal
Design form Terminal housing with pluggable wiring level
Material Polycarbonate
Dimensions (L x W x H) 6.8 cm x 1.2 cm x 10.0 cm
Weight 0.07 kg

Signal and I/O

Parameter Specification
Number of inputs 4
Signal current 0 to 20 mA
Technology Single-ended
Internal resistance 80 ohms + diode voltage 0.7 V
Resolution 12 bit
Measuring error < ±0.3 % (relative to full scale value)
Conversion time ~ 4 ms
Surge voltage resistance Max. 35 V
Bit width in the process image Input: 4 x 16 bit data (4 x 8 bit control/status optional)

Electrical

Parameter Specification
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption K-bus Typ. 65 mA
Current consumption power contacts No power contacts
Current load power contacts Imax: 10 A
Configuration No address or configuration setting

Connection Technology

Parameter Specification
Wiring Spring actuation by screwdriver
Connection cross-section solid (s) 0.08 to 1.5 mm²
Connection cross-section stranded (st) 0.08 to 1.5 mm²
Connection cross-section fine-stranded (f) 0.14 to 1.5 mm²
Connection cross-section AWG AWG 28 to 16 (s, st), AWG 26 to 16 (f)
Stripping length 9 to 10 mm

Environmental and Compliance

Parameter Specification
Operating temperature 0 to +55 degC
Storage temperature -25 to +85 degC
Relative humidity 95 %, no condensation
Vibration/shock resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection rating IP20
Installation position Variable
Approvals/markings CE, UL, ATEX, DNVGL
Ex marking II 3 G Ex nA IIC T4 Gc

Installation Guidelines

  1. Ensure the entire control system and local power supplies are completely de-energized before beginning installation or wiring work.
  2. Inspect the terminal housing and pluggable wiring connector for any signs of transport damage or contamination.
  3. Mount the BECKHOFF KS3044 onto a standard 35 mm DIN rail (conforming to EN 60715) by snapping it into place, utilizing the built-in locking mechanism.
  4. Connect adjacent terminals securely using the double slot and key connection system to maintain proper K-bus alignment.
  5. Strip field conductors to the specified length (9 to 10 mm) and insert them into the spring-actuated connection points using a suitable screwdriver.
  6. Verify all signal wiring against system schematics, ensuring correct polarity for the 0 to 20 mA current loop inputs.
  7. Power on the system and verify operational status via the bus coupler and control environment diagnostics.

FAQ

What is the primary function of the BECKHOFF KS3044?

The BECKHOFF KS3044 is a 4-channel analog input Bus Terminal engineered to acquire and process 0 to 20 mA current signals within a BECKHOFF I/O system.

How many channels does the BECKHOFF KS3044 support?

The BECKHOFF KS3044 features four independent single-ended input channels with 12-bit resolution for analog measurements.

What connection technology does the BECKHOFF KS3044 use?

The BECKHOFF KS3044 utilizes pluggable wiring with spring-actuated connection points operated via a screwdriver for secure conductor termination.

Does the BECKHOFF KS3044 require external address configuration?

No, the BECKHOFF KS3044 operates without requiring manual address or configuration settings, integrating automatically into the K-bus structure.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.