BECKHOFF KS4404 Bus Terminal Analog Output Module

BECKHOFF KS4404 Bus Terminal Analog Output Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KS4404

  • Country of origin:Germany

  • Product Type: Bus Terminals

  • Payment: T/T, Western Union

  • Weight: 85g

  • Dimensions: 68 mm x 12 mm x 100 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Engineered for highly reliable industrial automation environments, the BECKHOFF KS4404 is a 4-channel analog output terminal designed to generate precise signals in the 0 to 10 V range. This module converts digital control values from the controller into analog process signals with an increased 12-bit resolution. Each output channel utilizes single-ended technology, ensuring optimal signal processing and high immunity to electrical interference.

The defining feature of the KSxxxx terminal series is its pluggable wiring level. This mechanical design allows the terminal block to be easily disconnected and replaced without removing the pre-configured field cables, significantly reducing downtime during maintenance. Grounding, shielding, and galvanic isolation of 500 V between the K-bus and the field-side signal voltage protect the main controller from voltage spikes and ground loops, rendering this module ideal for distributed control systems (DCS) and PLC networks.

Features

  • Four single-ended analog output channels operating from 0 to 10 V.
  • High-precision 12-bit conversion resolution for critical process variables.
  • Pluggable connection level for fast, toolless terminal replacement.
  • Robust electrical isolation of 500 V between the internal K-bus and the output channels.
  • Short-circuit-proof outputs capable of driving resistive loads greater than 5 kOhm.
  • Support for standard 35 mm DIN rails via double-slot and key housing locks.

Applications

  • Speed control and setpoint transmission for variable frequency drives (VFDs).
  • Actuator positioning and control valve regulation in HVAC systems.
  • Analog input control for downstream industrial controllers and display panels.
  • Process instrumentation control in chemical, power generation, and water treatment plants.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model KS4404
Technology Single-ended
Number of Outputs 4
Signal Voltage Range 0 to 10 V
Load Resistance > 5 kOhm (short-circuit proof)
Output Error < ±0.1 % (relative to full-scale value)
Resolution 12 bit
Conversion Time ~ 4 ms
Electrical Isolation 500 V (K-bus / signal voltage)
Current Consumption (K-bus) typ. 20 mA
Current Consumption (Power Contacts) Load only
Bit Width in Process Image Output: 4 x 16-bit data (optional 4 x 8-bit control/status)
Pluggable Wiring Type KSxxxx series terminal connector
Solid Wire Cross-Section 0.08 to 1.5 mm² (AWG 28 to 16)
Stranded Wire Cross-Section 0.08 to 1.5 mm² (AWG 28 to 16)
Fine-Wire Cross-Section 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Length 9 to 10 mm
Housing Material Polycarbonate
IP Protection Rating IP20
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 85 degC
Relative Humidity 95 %, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Dimensions (L x W x H) 68 mm x 12 mm x 100 mm
Weight 0.085 kg

Connections and Interfaces

Terminal Pin Function Description
1 Analog Output 1 (+)
5 Analog Ground 1 (-)
2 Analog Output 2 (+)
6 Analog Ground 2 (-)
3 Analog Output 3 (+)
7 Analog Ground 3 (-)
4 Analog Output 4 (+)
8 Analog Ground 4 (-)

Installation Guidelines

  • Mounting: Mount the bus terminal horizontally or vertically on a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking latch engages securely.
  • Wiring: Utilize a small screwdriver to actuate the spring connection mechanism. Strip cables precisely to a length of 9 to 10 mm to guarantee full insertion contact without exposing bare conductors.
  • Shielding and Grounding: Shielded analog cables are highly recommended. Connect the cable shield to a low-resistance functional earth ground as close to the terminal entry point as possible to mitigate high-frequency electromagnetic noise.
  • Ventilation: Maintain sufficient clearance above and below the terminal block assembly to allow passive convection cooling, preserving the operating temperature range below 55 degC.

Compliance and Certifications

  • CE: Conforms to relevant European directives.
  • UL: Listed for safety compliance standards.
  • ATEX: II 3 G Ex nA IIC T4 Gc (Certified for Zone 2 hazardous areas).
  • DNVGL: Approved for maritime and offshore installations.
Key Features:

What is the primary difference between Beckhoff KL and KS terminal series?

The KS series (such as the KS4404) features a pluggable wiring level that allows the terminal block to be disconnected and replaced without rewiring, whereas the KL series uses permanent, integrated terminal connections.

Does the KS4404 require software configuration or DIP switches to set its address?

No. The KS4404 operates without manual address or hardware configuration settings, mapping its registers automatically within the K-bus process image.

What is the maximum output current and load specification for each channel on the KS4404?

Each channel is short-circuit proof and designed to drive high-impedance loads greater than 5 kOhm, operating primarily as a voltage signal source rather than a power supply.

Can the KS4404 be used in hazardous locations?

Yes, the KS4404 is ATEX certified with the marking II 3 G Ex nA IIC T4 Gc, making it suitable for deployment in Zone 2 gas-hazardous environments.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Micro Drive Specialist EMS Bets on Custom Engineering to Broaden Market Appeal

UK micro-drive specialist EMS is pairing Faulhaber high-torque gearheads and compact motion controllers with in-house custom engineering—aiming beyond catalog sales into tailored mechatronics.

Bringing Object-Oriented Thinking to PLC Programming

Copy-paste ladder does not scale. Object-oriented PLC techniques—user-defined structures and instructions—cut duplication, propagate fixes once, and keep large multi-device programs readable.

Why Process Safety Management Programs Fail Even When OSHA Boxes Are Checked

OSHA boxes checked is not the same as a living PSM system. Refinery history shows programs fail when procedures, training, contractors, and investigations drift from how the plant actually runs.

What Is SCADA? Supervisory Control Without Replacing the PLC

SCADA sits above PLCs and RTUs: it acquires field data, alarms operators, and issues supervisory commands across plants and remote assets—without replacing local deterministic control.

What Is a VFD? Variable Frequency Drives That Actually Move the Needle

A VFD turns fixed-frequency mains into controlled voltage and frequency so AC motors match real load—cutting pump and fan energy while tightening torque, soft-start, and braking behavior.

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.