Description
The Bently Nevada 3500/65 monitor, utilizing the 145988-02 main module component, is a high-density 16-Channel Temperature Monitor engineered to protect critical industrial machinery by providing continuous thermal tracking. This specialized module accepts 16 channels of temperature inputs from both resistance temperature detectors (RTDs) and isolated tip thermocouples (TCs). It internally conditions these raw transducer signals and continuously compares them against user-programmed alarm and danger setpoints to prevent thermal degradation of critical plant assets.
Configuration and channel mapping are performed using the 3500 Rack Configuration Software. Operators can seamlessly program the 16-channel architecture to process isolated tip thermocouples, 3-wire RTDs, 4-wire RTDs, or a combined arrangement of both TC and RTD sensors within the same chassis slot. For high-integrity environments demanding Triple Modular Redundant (TMR) safety, the monitors must be deployed in groups of 3 adjacent units within the 3500 Series Machinery Protection System rack. In this configuration, the system applies two levels of voting logic to guarantee operational accuracy and mitigate single-point failure risks.
Features
- Processes up to 16 independent temperature sensor inputs within a single rack slot.
- Universal channel allocation accepts mixed configurations of TCs, 3-wire RTDs, and 4-wire RTDs.
- Direct compatibility with the 3500 Rack Configuration Software for field-scale modifications.
- Implements dual-tier internal voting logic when grouped in sets of three for TMR safety protection architectures.
- High-speed data collection rate that updates all channels within a 1-second interval.
- Distinct front-panel LEDs for immediate assessment of hardware validation status (OK), rack communication status (TX/RX), and bypass status.
Applications
- Multi-point bearing temperature tracking on high-speed steam and gas turbines.
- Stator winding and motor casing thermal monitoring inside heavy-duty power generation equipment.
- Process gas and lubricant temperature surveillance in multi-stage centrifugal compressors.
- Boiler, pump, and auxiliary machinery heat protection across petrochemical installations.
Ordering Information
- 145988-02: 3500/65 Monitor
Technical Specifications
| Parameter |
Specification |
|
|
|
|
|
|
| Manufacturer |
Bently Nevada |
|
|
|
|
|
|
| Country of Origin |
USA |
|
|
|
|
|
|
| Power Consumption |
3 Watts nominal |
|
|
|
|
|
|
| Signal Inputs |
1 to 16 RTD or isolated tip TC transducer signals |
|
|
|
|
|
|
| Input Impedance |
Greater than 1 MOhm for each lead input |
|
|
|
|
|
|
| Thermocouple Types & Ranges |
Type E: -100 degC to +1000 degC (-148 degF to +1832 degF) |
|
Type J: 0 degC to +760 degC (32 degF to +1400 degF) |
|
Type K: 0 degC to +1370 degC (32 degF to +2498 degF) |
|
Type T: -160 degC to +400 degC (-256 degF to +752 degF) |
| RTD Types & Ranges |
100 Ohm 3-wire and 4-wire platinum (alpha = 0.00385): -200 degC to +850 degC (-328 degF to +1562 degF) |
|
100 Ohm 3-wire and 4-wire platinum (alpha = 0.00392): -200 degC to +700 degC (-328 degF to +1292 degF) |
|
120 Ohm 3-wire and 4-wire nickel: -80 degC to +260 degC (-112 degF to +500 degF) |
|
10 Ohm 3-wire and 4-wire copper: -100 degC to +260 degC (-148 degF to +500 degF) |
| RTD Current Source Value |
913 +/- 7 uA at 25 degC per transducer (1 supply for 4-wire RTD, 2 supplies for 3-wire RTD) |
|
|
|
|
|
|
| Resolution |
1 degC or 1 degF |
|
|
|
|
|
|
| Internal Termination Accuracy |
Bulkhead Rack: +/-3 degC at +25 degC (+/-5.4 degF at +77 degF) |
|
Standard Rack: +/-3 degC at +25 degC (+/-5.4 degF at +77 degF) |
|
|
|
|
| External Termination Accuracy |
Bulkhead Rack: +/-3 degC at +25 degC (+/-5.4 degF at +77 degF) |
|
Standard Rack: +/-3 degC at +25 degC (+/-5.4 degF at +77 degF) |
|
|
|
|
| Cold Junction Compensation Sensor Accuracy |
+/-2 degC at +25 degC (+/-3.6 degF at +77 degF) |
|
|
|
|
|
|
| Operating Temperature |
-30 degC to +65 degC (-22 degF to +150 degF) |
|
|
|
|
|
|
| Storage Temperature |
-40 degC to +85 degC (-40 degF to +185 degF) |
|
|
|
|
|
|
| Main Module Dimensions (H x W x D) |
241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in) |
|
|
|
|
|
|
| Weight |
0.91 kg (2.0 lbs.) |
|
|
|
|
|
|
Connections/Interfaces
| Connector Type |
Function |
| Internal Chassis Backplane Connector |
Integrates power routing and high-speed data communications with the 3500 rack bus |
| External Termination Blocks / I/O Module |
Direct physical interface for the 16 independent RTD and thermocouple transducer lead wires |
Installation Guidelines
-
TMR Alignment: When configuring a Triple Modular Redundant layout, install the individual temperature monitors in groups of three adjacent structural slots.
-
Sensor Selection Restrictions: Ensure all connected thermocouples are of the isolated-tip type to avoid common ground loop interference across channels.
-
Cabling Practices: Use shielded, twisted-pair field wiring for all RTD and thermocouple runs to mitigate ambient electromagnetic induction.
-
Grounding Shield Integrity: Maintain continuous cable shielding up to the termination blocks, grounding the shields at the designated chassis common point only.
-
Thermal Management: Verify operating environment temperatures stay below 65 degC to ensure compliance with specified internal cold junction compensation parameters.
Compliance and Certifications
FAQ
What is the primary function of the 3500/65 module?
It monitors up to 16 channels of plant machinery temperature using RTD and isolated-tip thermocouple inputs.
Can this temperature monitor accept non-isolated thermocouples?
No, the module is specifically rated to only accept isolated-tip thermocouple models to prevent signal errors.
Which configuration tool is utilized to adjust the alarm setpoints?
All parameter adjustment, sensor selections, and alarm configurations require the 3500 Rack Configuration Software.
What does a steady lit Bypass LED on the front face mean?
It indicates that the monitor has been deliberately placed into Bypass Mode, suppressing programmed output actions.
What is the recommended sensor configuration for standard industrial installations?
Platinum RTDs with an alpha value of 0.00385 are the industry standard and recommended for general applications.
How does the system operate when deployed in a TMR application?
The monitor must be installed in groups of three adjacent rack slots and uses two distinct voting types to prevent single-point failures.
Is manual field calibration required for this device?
No manual field calibration is required as signal conditioning functions are preset and managed via internal software scaling.
What are the input impedance levels per lead wire?
The input impedance measures greater than 1 MOhm for each independent input lead line.
What constant current value is provided for the RTD measurements?
The integrated current source supplies 913 +/- 7 uA at 25 degC per transducer element.
How many internal current supplies are used when a 3-wire RTD is connected?
The hardware engages two distinct current supplies for a 3-wire RTD setup and one supply for a 4-wire RTD setup.