The Danfoss FC111P37KT4 is a high-performance VLT HVAC Basic Drive engineered to optimize energy efficiency in ventilation, heating, and air conditioning applications. Rated for a typical shaft output of 37.0 kW (40.0 hp), this variable frequency drive provides precise motor speed control, effectively reducing operational costs and extending the lifespan of mechanical equipment in HVAC systems.
This VLT HVAC Basic Drive is designed for robustness and reliability in demanding industrial environments. With an IP20 protection rating, it is built to operate within a wide range of input voltages (3x380–480 V) while maintaining high efficiency—up to 97.7% in typical operating conditions. The unit includes advanced current management capabilities to handle both continuous and intermittent loads, ensuring stable performance at varying ambient temperatures.
Features
Optimized for HVAC fan and pump applications
High operational efficiency up to 97.7%
Dual voltage and current ratings for flexible application (380–440 V and 441–480 V)
Supports ambient temperatures up to 50 degC with derated output
Compact IP20 enclosure design
Designed for standard industrial motor control
Applications
Commercial and industrial HVAC systems
Variable air volume (VAV) systems
Cooling tower fans
Centrifugal pump control
Air handling units
Technical Specifications
Feature
Specification
Manufacturer
Danfoss
Model
FC111P37KT4
Product Type
VLT HVAC Basic Drive
Typical Shaft Output
37.0 kW (40.0 hp)
Enclosure Rating
IP20
Efficiency
97.7 %
Power Loss (Typical)
922 W
Max. Cable Size (Mains/Motor)
35 mm2 (2 AWG)
Weight
24.5 kg (54 lb)
Output Performance (at 40 degC ambient):
Voltage Range
Continuous Current
Intermittent Current
3x380–440 V
73.0 A
80.3 A
3x441–480 V
65.0 A
71.5 A
Output Performance (at 50 degC ambient):
Voltage Range
Continuous Current
Intermittent Current
3x380–440 V
58.4 A
64.2 A
3x441–480 V
52.0 A
57.2 A
Installation Guidelines
Ventilation: Due to the 922 W power loss, ensure adequate cabinet ventilation or cooling to prevent overheating, especially when operating near the 50 degC ambient limit.
Cabling: Use shielded cables for motor connections to minimize electromagnetic interference (EMI). Ensure terminals are tightened to accommodate up to 35 mm2 (2 AWG) wire size.
Grounding: Proper earthing of the drive frame is essential for safety and to comply with electromagnetic compatibility (EMC) standards.
Clearance: Maintain the recommended clearance distances around the drive as specified in the manual to ensure optimal airflow through the heat sink.
FAQ
What is the typical power output of the FC111P37KT4 drive?
The typical shaft output is 37.0 kW or 40.0 hp.
How does the ambient temperature affect the output current?
The drive provides full rated current at 40 degC. At 50 degC ambient temperature, the output current is derated (e.g., to 58.4 A for the 380–440 V range) to ensure reliable operation.
What is the IP rating for this HVAC drive?
This model is rated IP20, suitable for mounting within an electrical cabinet.
What is the maximum cable size compatible with this unit?
The mains and motor terminals accept a maximum cable size of 35 mm2 (2 AWG).
A PLC and a microcontroller can both generate step-and-direction motion, but arc welding exposes major differences in EMC, I/O protection, diagnostics, maintainability, safety integration, and...
Piezo pneumatic valves offer low holding power and fine proportional control, but they are not universal solenoid replacements. This guide covers driver electronics, flow limits, contamination, fail...
Built-in sensor timers can reject chatter, stretch short pulses, and simplify local timing—but they do not replace PLC diagnostics or safety logic. Learn how to apply on-delay, off-delay, and...
Reversing a three-phase motor is more than swapping two leads. This guide covers phase sequence, VFD settings, reversing contactors, encoder feedback, load checks, lockout, and commissioning tests.
Grounding one side of a 24 VDC supply can improve fault detection and voltage reference, while floating circuits support isolation. This guide explains bonding, noise, first-fault behavior, and...
Seal-in circuits and OTL/OTU instructions can hold the same command, but they fail differently. This guide compares scan behavior, restart risk, troubleshooting, permissives, and safer PLC design...
Choosing a selection results in a full page refresh.