1 of 3

GE Multilin MMII-PD-1-2-240 Motor Manager II Motor Protection System

GE Multilin MMII-PD-1-2-240 Motor Manager II Motor Protection System

Only 7 item(s) left in stock
  • Manufacturer: General Electric

  • Product No.: MMII-PD-1-2-240

  • Country of origin:United States

  • Product Type: Motor Management Unit

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 1800g

  • Dimensions: 8.3" x 5.625" x 5.8"

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The MMII-PD-1-2-240 provides comprehensive microprocessor-based supervision, management, and diagnostic monitoring for low-voltage electric motor applications. This motor protection system coordinates core protective algorithms including thermal overload tracking, phase unbalance corrections, contactor failure verification, and rotor stall prevention within industrial Motor Control Centers (MCCs). Equipped with both standard Option 1 and Option 2 factory expansions, the module integrates an internal hot winding thermistor sensor layer alongside VT inputs for exact real-time calculation of kilowatt (kW) and kilowatt-hour (kWh) parameters. The MMII-PD-1-2-240 motor protection system features an embedded two-line liquid-crystal panel display and integrates an undervoltage auto-restart tracking circuit to systematically restore system drive assemblies following localized line fluctuations.

Features

  • Microprocessor-driven monitoring matrix protecting low-voltage motors against overloads, phase failure, stalled rotors, and contactor circuit faults.
  • Integrated front-facing control panel featuring a 2-line, 40-character liquid-crystal display (LCD) and a manual tactile keypad.
  • Option 1 hardware expansion pack containing 10 programmable switch inputs, a 4 to 20 mA analog input, and 2 auxiliary electromechanical relays.
  • Option 2 hardware expansion pack providing diagnostic relay timers, contactor A and B relays, voltage transformer (VT) inputs, and an integrated thermistor loop.
  • Functional MOD 625 optimization for arc suppression paths paired with non-functional MOD 605 removable rear terminal blocks.
  • Comprehensive data logging capability capturing standalone trip snapshots alongside corresponding pre-trip operational variables.
  • Network integration through a serial RS485 interface executing Modbus communications up to 19200 bps.

Applications

  • High-density intelligent Motor Control Centers (MCC)
  • Manufacturing assembly drive systems and industrial processing loops
  • Petrochemical, mining, and municipal water treatment low-voltage motor protection

Technical Specifications

Parameter Specification
Manufacturer GE Multilin
Series Motor Manager II (MM2)
Model Number MMII-PD-1-2-240
Product Type MMII Motor Protection System
Mounting Type PD - Panel Mount With Display
Control Voltage 240 VAC
Power Consumption 25 VA (Maximum), 7 VA (Nominal)
Fuse Rating/Type 0.5 A 250 V Fast blow, high breaking capacity
Digital Inputs 16 total optically isolated channels (6 fixed, 10 configurable)
Digital Outputs 4 total channels (2 dedicated contactor outputs, 2 programmable)
Analog Inputs 1 channel (4 to 20 mA via Option 1)
Analog Diagnostics Phase current, ground current, thermal capacity, power/energy levels
Single Phase Accuracy \pm 2 percentage points
Configuration Software EnerVista
Serial Communication RS485 Modbus, 1200 bps to 19200 bps
Manufacturing Origin Markham, Ontario, Canada
Product Net Weight Max. 4 lbs (1.8 kg)
Shipping Dimensions 8.3" x 5.625" x 5.8"

Connections/Interfaces

Interface Node Description / Assignment Function
Removable Rear Terminals Main 240 VAC power input and field signal connection blocks under MOD 605
Contactor Outputs Dedicated terminal pair assigned for primary contactor loop controls
Programmable Outputs Auxiliary electro-mechanical relay terminal pairs for status signaling
VT Input Terminals Voltage transformer interfaces utilized for operational kW/kWh calculations
Thermistor Port Terminal inputs dedicated to localized hot winding thermal resistors
RS485 Serial Port Differential serial connection terminal managing Modbus network paths

Installation Guidelines

  • Cabinet Preparation: Ensure the cutout size on the front sheet metal of the enclosure door matches the dimensional specifications of the MMII-PD panel-mount layout.
  • LOTO Verification: Completely isolate the 240 VAC control circuitry and associated power feeds leading into the starter bucket using standard Lockout/Tagout (LOTO) protocols.
  • Mechanical Security: Insert the housing through the cutout from the front face of the enclosure panel. Attach the specialized side mounting clamps from the rear inside wall of the door and tighten down the hardware until the front sealing ring seals out environment debris.
  • Field Electrical Wiring: Connect the phase current transformer (CT) secondary leads and zero-sequence ground fault lines into the backplane blocks with correct polarity. Route the RS485 communications cabling using shielded twisted-pair conductors.

What does the PD designation mean compared to a C configuration suffix?

The 'PD' code indicates that the relay is equipped with a panel-mount layout containing a 2-line, 40-character liquid-crystal screen and an operator keypad for manual parameter setup. Models marked with a 'C' lack a local interface display and must be configured externally using EnerVista software.

What precise hardware functions are added by Options 1 and 2 in this model?

Option 1 adds 10 programmable switch inputs, a 4 to 20 mA analog input, 2 additional relays, advanced diagnostics, and undervoltage restart tracking. Option 2 provides integrated timers, contactor A/B relays, 2 additional switch inputs, enhanced protection algorithms, VT inputs for kW/kWh calculations, and a winding thermistor loop.

What specific fuse specification is installed for circuit layer protection?

The module utilizes a fast-blow, high breaking capacity internal fuse rated explicitly at 0.5 A and 250 V to shield internal processing electronics from fault overcurrent.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Black
Country of origin
United States
Power source
AC-powered

Recently Viewed Products

Technical knowledge

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...