General Electric

General Electric IC693MDL310 Series 90-30 120 VAC 0.5 A 12-Point AC Output Module

SKU IC693MDL310

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: General Electric

  • Product No.: IC693MDL310

  • Country of origin:United States

  • Product Type: AC Output Module

  • Payment: T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The General Electric IC693MDL310 is a 120 VAC, 0.5 Amp discrete solid-state AC output module designed for the GE Fanuc Series 90-30 programmable logic controller system. It provides 12 output circuits organized into two isolated groups of six points each. Because each group incorporates an independent common connection that is electrically separated from the other inside the module, the groups can operate on distinct phases of an AC power source or draw from a single shared supply.

Each output circuit integrates an RC snubber network to suppress power line transient noise and voltage spikes. The module provides high inrush current tolerance rated at up to 10 times continuous load current (5 Amps peak for one AC cycle), allowing direct operation of inductive and incandescent loads such as contactors, motor starters, indicator lamps, and solenoids. Field power to energize output loads must be provided externally by the user.

The IC693MDL310 installs into any standard I/O slot of a 5-slot or 10-slot Series 90-30 baseplate, including CPU baseplates, expansion baseplates, and remote baseplates. The hinged faceplate door contains an insert card that provides internal terminal wiring diagrams on the reverse side and user identification labeling on the outer surface, bordered by a red edge to designate high-voltage AC field wiring.

Features

  • 12 solid-state AC outputs partitioned into two isolated groups of 6 circuits each.
  • Independent common terminals per group allowing connection to separate AC supply phases.
  • Individual RC snubber suppression on each output point for transient protection.
  • High inrush capability rated at 5 Amps for one line cycle to drive inductive loads.
  • Individual 3 Amp protection fuse per group.
  • Front-panel LED diagnostics featuring 12 green status indicators and 1 red blown-fuse indicator.
  • Hinged front door with high-voltage red color code and terminal assignment reference.

Technical Specifications

Parameter Specification
Module Type Discrete AC Output Module
PLC Platform Series 90-30
Number of Output Points 12 points (2 isolated groups of 6 points)
Rated Voltage 120 VAC
Output Voltage Range 85 to 132 VAC, 50/60 Hz
Output Current per Point 0.5 A maximum
Output Current per Group 1.0 A maximum at 60 degC (140 degF); 2.0 A maximum at 50 degC (122 degF)
Maximum Inrush Current 5.0 A for one cycle
Minimum Load Current 50 mA
Maximum Voltage Drop 1.5 V at 0.5 A load
Maximum Output Leakage Current 3 mA at 120 VAC
Turn-On Response Time 1 ms maximum
Turn-Off Response Time 1/2 cycle maximum
Isolation: Field to Logic 1500 VAC
Isolation: Group to Group 500 VAC
Internal Bus Current Draw 210 mA from +5 VDC bus (all outputs ON)
Internal Group Fusing 3 A fuse per group (2 fuses total)
Status Indicators 12 green logic LEDs (A1-A6, B1-B6); 1 red fuse blown LED (F)
Faceplate Color Band Red (High Voltage)
Baseplate Compatibility Any I/O slot in Series 90-30 5-slot or 10-slot baseplates
Country of Origin United States

Installation and Wiring Guidelines

  • Turn off power to the baseplate and field circuits prior to inserting or removing the module or servicing fuses.
  • Ensure field AC power is routed through appropriate external disconnects, as the module does not supply output power from the backplane.
  • Group 1 uses points A1 through A6, while Group 2 uses points B1 through B6; do not bridge the respective commons if groups operate on differing AC phases.
  • Route high-voltage AC field wiring separately from low-voltage DC communication and analog signal cables to minimize inductive coupling.
  • Inspect the red "F" LED indicator during runtime to quickly identify an open fuse condition in either group.

FAQ

What is the primary function of the General Electric IC693MDL310?

The IC693MDL310 is a 12-point discrete AC output module that provides solid-state 120 VAC switching at up to 0.5 Amps per point for loads connected to a GE Fanuc Series 90-30 PLC system.

How are the output points isolated and powered on the IC693MDL310?

The module's 12 outputs are arranged into two isolated groups of six points each. Each group has its own isolated common terminal, allowing the two groups to be powered from separate AC supply phases or connected to the same source.

What are the maximum current ratings for the IC693MDL310 module?

Each point supports up to 0.5 Amps maximum. Per group, maximum current is rated at 2.0 Amps at 50 degC (122 degF) and derates to 1.0 Amp at 60 degC (140 degF). The peak inrush rating is 5.0 Amps for one line cycle.

How does the IC693MDL310 indicate blown fuse conditions?

The module features a red LED labeled 'F' positioned between its green status indicator rows. If either of the internal 3 Amp group fuses opens, the red 'F' indicator illuminates to notify maintenance personnel.

Which Series 90-30 slots are compatible with the IC693MDL310?

The IC693MDL310 can be installed in any standard I/O slot of a Series 90-30 5-slot or 10-slot baseplate, including CPU baseplates, expansion baseplates, and remote baseplates.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

General Electric IC693MDL310 Series 90-30 120 VAC 0.5 A 12-Point AC Output Module

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 13 item(s) left in stock
Quantity
View full details
Loading product navigation…

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

Derivative Action in PID Control Without Noise Problems

Learn what derivative action contributes to a PID loop, why it can amplify measurement noise and setpoint changes, and how filtering, sampling, and staged tests make D tuning safer.

Designing Industrial Networks That Stay Troubleshootable

A practical guide to segmenting, documenting, and testing industrial Ethernet networks so plant teams can isolate faults quickly, control change, and expand without creating fragile dependencies.

Commissioning IO-Link From Master Ports to IODD Data

Commission IO-Link systematically from master addressing and port modes through IODD selection, PLC byte mapping, parameter backups, device validation, and failure-injection tests.

PowerFlex Dynamic Braking Resistor Design and Testing

A practical PowerFlex braking guide covering regenerative energy, resistor resistance and duty cycle, thermal protection, model-specific parameters, and measured commissioning tests.

Engineering Industrial Joystick Controls for Safe Motion

An industrial joystick is only the first element in a safe motion command chain. This guide covers sensing choices, wiring, signal validation, PLC logic, restart behavior, and commissioning for...

Seeing PID Behavior Before Tuning the Loop

PID tuning becomes safer when engineers can see how proportional, integral, and derivative actions reshape error, output, and response over time. This guide turns live trends into a disciplined...