1 of 3

Honeywell Experion PKS 8C-PAONA2 Analog Output Module (Non-HART)

Honeywell Experion PKS 8C-PAONA2 Analog Output Module (Non-HART)

Only 7 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: 8C-PAONA2

  • Country of origin:United States

  • Product Type: Analog Output Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 15.00 x 10.00 x 4.00 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Product Overview

The Honeywell 8C-PAONA2 (8CPAONA2) is a high-performance Analog Output (AO) module belonging to the Experion PKS Series 8 I/O family. Engineered for precision and mission-critical reliability, this 16-channel module converts digital control commands from the C300 controller into standard 4-20 mA analog signals. The 8C-PAONA2 is primarily used to drive final control elements such as pneumatic valve positioners, variable speed drives (VSD), and dampers. As a "Series 8" component, it features a vertical, slimline design that optimizes cabinet density and promotes natural thermal convection. This specific variant is the "Non-HART" version, providing a cost-effective solution for control loops where digital field device diagnostics are not required, while maintaining the rugged G3-level environmental protection standard in Honeywell's premium I/O line.

Technical Configuration

The 8C-PAONA2 is designed to integrate seamlessly into the Experion PKS architecture, focusing on signal stability and hardware longevity.

  • 16-Channel Density: Provides 16 independent analog output channels, allowing for high-density I/O configurations in a small physical footprint.

  • Series 8 Architecture: Designed to be "plug-and-play" with Series 8 IOTAs (Input Output Termination Assemblies), supporting both non-redundant and redundant configurations.

  • G3 Conformal Coating: The module is factory-treated with a conformal coating to protect internal circuitry against humidity and corrosive atmospheric contaminants (ISA S71.04 Class G3).

  • Galvanic Isolation: Features robust isolation between the I/O Link (backplane) and the field-side electronics, preventing ground loops and protecting the C300 processor from field electrical faults.

  • Fast Loop Response: Optimized for low-latency signal delivery, ensuring that control valve movements are synchronized with the DCS PID logic for stable process modulation.

Technical Specifications

Attribute Specification
Model 8C-PAONA2
Brand Honeywell
Series Experion PKS Series 8
Module Type Analog Output (Non-HART)
Number of Channels 16 Channels
Output Range 4 to 20 mA
Resolution 12-bit Minimum
Operating Temperature -40 to 70 Celsius
Protection G3 Conformal Coated
Power Consumption 5.5 Watts Typical
Weight 0.45 kg
Dimensions 15.00 x 10.00 x 4.00 cm

Technical FAQs

Can the 8C-PAONA2 be used to communicate with HART-enabled valves?

While the 8C-PAONA2 can drive a HART-enabled valve positioner using a standard 4-20 mA signal, it cannot read or write digital HART data. For full HART pass-through and diagnostics, the 8C-PAOHA1 module must be used instead.

How does this module handle a loss of communication with the controller?

The 8C-PAONA2 features a configurable "Fail-Safe" state. In the event of an I/O Link failure or controller shutdown, each channel can be programmed to Hold Last Value (HLV) or go to a pre-defined safe value (e.g., 0 mA or 4 mA).

Is this module compatible with older Series A or Series C IOTAs?

No. The 8C-PAONA2 is strictly a Series 8 module and must be mounted on a Series 8 IOTA, such as the 8C-TAOXA1 (Single) or 8C-TAOXB1 (Redundant).


Engineering & Installation Guide

  • Output Impedance Matching: Ensure that the total loop resistance (including field wiring and the actuator/positioner impedance) does not exceed the module's maximum drive capability, typically 600 Ohms at 24 VDC. Exceeding this limit will result in "Output Low" errors.

  • Hot-Swap Procedure: This module supports Removal and Insertion Under Power (RIUP). When replacing a module in a redundant pair, ensure the "Secondary" LED is stable before removing the "Primary" module to ensure a bumpless transfer of control.

  • Shielding and Noise: Use twisted-pair shielded cable for all 16 channels. The shield should be grounded at the IOTA's grounding bar. Proper shielding is critical to prevent electromagnetic interference (EMI) from inducing "jitter" in the 4-20 mA output signal, which can lead to premature mechanical wear on valve positioners.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
United States
Power source
DC Power

Recently Viewed Products

Technical knowledge

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...

Single-Axis Motion Control Setup with CMZ Servo Drives

This tutorial explores the commissioning of a single-axis servo motion system using a CMZ SBD drive, covering hardware setup, axis scaling, homing configuration, and safe motion verification for...

Mitsubishi FX PLC Integration With FR-D700 VFD and HMI Control

This tutorial explains how Mitsubishi FX PLCs integrate with FR-D700 VFDs and HMI panels for forward/reverse motor control. It covers wiring logic, parameter configuration, ladder programming, and...