1 of 1

KL4001 BECKHOFF 1-Channel Analog Output 0-10V Bus Terminal

KL4001 BECKHOFF 1-Channel Analog Output 0-10V Bus Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KL4001

  • Country of origin:Germany

  • Product Type: Bus Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Product Overview

The KL4001 (KL 4001) is a precision 1-channel analog output terminal designed to transmit analog voltage signals in the 0 to 10 V range. Utilizing a 12-bit resolution and a differential output architecture, this Bus Terminal is engineered for highly accurate control of actuators, frequency inverters, and proportional valves. In demanding industrial sectors such as HVAC regulation, chemical processing, and specialized machine building, the KL4001 serves as a vital control link. Its potential-free output and 500 V electrical isolation between the K-bus and signal voltage ensure superior noise immunity and signal stability, protecting the central controller from field-level electrical interference and preventing ground loops in complex automation networks.

Technical Configuration

The KL4001 architecture is optimized for reliability and precision. It converts digital 16-bit values from the controller into an analog voltage with an output error of less than ±0.1%, ensuring high fidelity in setpoint transmission. The terminal features a conversion time of approximately 1.5 ms and is designed to drive loads greater than 5 kΩ with short-circuit protection. As a standard Bus Terminal, it draws its power directly from the K-bus (typ. 75 mA) and requires no external power contacts. Its "differential" design allows the signal to be measured against its own reference point rather than a shared ground, which is critical for maintaining accuracy over longer cable runs or in environments with fluctuating ground potentials.

Technical Specifications

Attribute Specification Details
Model KL4001
Brand BECKHOFF
Origin Germany
Number of Outputs 1 (Differential)
Signal Voltage 0 to 10 V
Resolution 12 bit
Output Error < ±0.1 % (Relative to end value)
Conversion Time ~ 1.5 ms
Load > 5 kΩ (Short-circuit proof)
Electrical Isolation 500 V (K-bus / Signal voltage)
Current Consumption Typ. 75 mA (K-bus)
Operating Temperature -25 to +60 deg C
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Protection Rating IP20
Weight 85 g
Shipping Weight 2.0 kg
Approvals CE, UL, ATEX (II 3 G Ex nA IIC T4 Gc)

Technical FAQs

Does the KL4001 require any software configuration for basic operation?

No, the KL4001 is designed for immediate integration. It uses 1 x 16-bit data in the process image (with an optional 8-bit control/status byte) and does not require manual address or configuration settings, allowing for a seamless "plug-and-play" experience within the TwinCAT environment.

What is the benefit of the potential-free output?

The potential-free output ensures that the signal voltage is electrically isolated from the internal logic and other terminals. This prevents interference from other modules in the terminal segment and eliminates the risk of ground loops that could distort the 0-10 V signal or damage sensitive analog actuators.

How does the KL4001 handle short circuits on the output line?

The module is short-circuit proof. If a short occurs on the signal line, the terminal limits the current to prevent internal hardware damage. Once the fault is cleared, the terminal resumes standard analog output operation without requiring a hardware reset.


Engineering & Installation Guide

Wiring and Signal Grounding:

To achieve the maximum precision of < ±0.1% error, use shielded twisted-pair cabling for the 0-10 V output. The shield should be grounded only at one end (typically at the control cabinet's entry point) to avoid circulating currents. Ensure the stripping length is 8–9 mm for the spring-loaded terminals to guarantee a gas-tight connection. For the differential output of the KL4001, the signal (+) and signal (-) should be connected directly to the high-impedance input (> 5 kΩ) of the receiving device.

Hazardous Area Compliance:

The KL4001 is ATEX rated (Ex nA IIC T4 Gc) for use in Zone 2 hazardous areas. When installing in these environments, the terminal must be mounted in an IP54-rated enclosure and the 35 mm DIN rail must be connected to a clean functional earth. Do not unplug the terminal or disconnect any wiring while the K-bus power is active to prevent potential ignition sources.

Thermal Management and Mounting:

The terminal is rated for operation from -25 to +60 deg C. To ensure long-term stability of the analog conversion circuitry, maintain a minimum vertical clearance of 30 mm above and below the module for airflow. When mounting side-by-side, the double slot and key connection provides the necessary mechanical stability. If the module is used at the end of a segment, ensure a KL9010 bus end terminal is installed to terminate the K-bus correctly.

 

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
Germany

Recently Viewed Products

Technical knowledge

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...

Single-Axis Motion Control Setup with CMZ Servo Drives

This tutorial explores the commissioning of a single-axis servo motion system using a CMZ SBD drive, covering hardware setup, axis scaling, homing configuration, and safe motion verification for...

Mitsubishi FX PLC Integration With FR-D700 VFD and HMI Control

This tutorial explains how Mitsubishi FX PLCs integrate with FR-D700 VFDs and HMI panels for forward/reverse motor control. It covers wiring logic, parameter configuration, ladder programming, and...