Beckhoff KS3102 is a two-channel analog input Bus Terminal for differential ±10 V signals. The KS version uses the pluggable wiring level while retaining the K-bus electrical and process-data functions of the KL3102 family.

Technical specifications

Manufacturer Beckhoff Automation
Order number KS3102
Inputs 2 differential analog inputs
Signal range −10 V to +10 V
Resolution 16 bit
Conversion time 140 ms, configurable down to 2 ms
Measurement error < ±0.3% of full scale
Input resistance > 200 kΩ
Electrical isolation 500 V between K-bus and signal voltage
K-bus current Typically 65 mA
Mounting 35 mm DIN rail to EN 60715
Protection IP20
Dimensions 12 × 100 × 68 mm (W × H × D)
Net weight Approximately 70 g

Commissioning checks

  • Confirm that the field signal is bipolar ±10 V and that both channels are wired as differential inputs.
  • Keep signal and shield wiring consistent with the terminal-point assignment; do not use shield terminals as signal return.
  • Verify the selected filter and conversion time in the controller configuration before comparing live values.

Shipping data

Estimated packed size: 16 × 12 × 6 cm. Estimated shipping weight: 0.20 kg. Final air-freight data must be confirmed from the packed item.

FAQ

What signal range does the KS3102 accept?

It accepts two differential analog voltage inputs from −10 V to +10 V.

How is KS3102 different from KL3102?

The electrical function is the same family, but KS3102 uses a pluggable wiring level to simplify service replacement and prewiring.

What should be checked before replacing another KS31xx terminal?

Match the exact input range, channel type, process-image mapping, filter and conversion-time settings. Nearby KS31xx order numbers are not range-equivalent.

How should the shield terminals be used?

Follow the Beckhoff terminal-point assignment. The shield/PE points are not substitutes for the differential signal return.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

KS3102 | BECKHOFF | Bus Terminal

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details
Loading product navigation…

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

1746-A7 Chassis Replacement Checks: Slots, Power and Interconnects

An engineering checklist for replacing an Allen-Bradley 1746-A7: verify chassis series, backplane loading, slot plan, interconnect cables, mounting, grounding and receiving condition.

IC200MDL650 Replacement Checks: Logic Polarity, Filters, and Commons

A field replacement guide for GE Fanuc IC200MDL650 covering revision-dependent negative logic, four common groups, 24 VDC thresholds, input filtering, carrier checks and commissioning records.

IC697CPX935 Replacement Checks: Memory, Ports, and Rack Power

A field-focused IC697CPX935 replacement guide covering fast memory, firmware-dependent serial behavior, rack power, cooling, I/O architecture and backup records.

IC693DSM324 Replacement Checks: FSSB, Firmware and Follower Control

A field-focused IC693DSM324 replacement guide covering Series 90-30 host checks, FSSB servo-chain records, 5 V power budget, firmware limits, follower control and commissioning.

HIMA F3430 Replacement Checks: Contact Ratings and Safety Limits

A field-focused HIMA F3430 replacement guide covering relay contact ratings, DC load derating, fusing, F3330/F3331 differences, safety restrictions and commissioning records.

IC697PWR710 Replacement Checks: Load Budget and Dual-Rack Limits

A field-focused IC697PWR710 replacement guide covering 5 V load calculations, dual-rack limits, extension cables, input checks, protection behavior and hardware revision risks.