Mitsubishi Electric

Mitsubishi Electric FR-F840-03250-2-60 FR-F800 Series Inverter

SKU FR-F840-03250-2-60

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Mitsubishi Electric

  • Product No.: FR-F840-03250-2-60

  • Country of origin:United States

  • Product Type: Variable Frequency Drives (VFD)

  • Payment: T/T, Western Union

  • Weight: 74000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

Optimizing flow control in heavy-duty pump and fan installations, the Mitsubishi Electric FR-F840-03250-2-60 functions as a heavy-capacity variable frequency drive from the FR-F800 series. This industrial inverter is engineered specifically for fan, pump, and compressor control, delivering high-efficiency operation through intelligent energy-saving algorithms. Incorporating advanced excitation control, it continuously monitors load demand to optimize torque and reduce power consumption in real time.

Features

  • Advanced Optimum Excitation Control: Automatically balances motor magnetic flux to achieve high energy efficiency even under changing load conditions.
  • Dual Overload Rating: Supports Super Light Duty (SLD) and Light Duty (LD) operational configurations to match specific load profiles.
  • Multi-Pump Control: Built-in advanced PID and multi-pump control algorithms allow coordinated operation of multiple auxiliary pumps.
  • Integrated Safety Function: Features functional safety inputs compliant with SIL 2 / PL d safety standards.
  • Onboard PLC Functionality: Enables basic logic programming directly within the inverter, reducing the need for external mini-PLCs.

Applications

  • Water and Wastewater: Intake pumps, booster stations, and aeration blower systems.
  • HVAC Systems: Large-scale industrial air handling units (AHUs), cooling towers, and chillers.
  • Factory Automation: Dust collectors, exhaust fans, and municipal ventilation systems.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number FR-F840-03250-2-60
Series Name FR-F800 Series
Input Voltage Range 3-Phase 380 to 500 VAC (50/60 Hz)
Rated Output Current (SLD) 325 A
Rated Output Current (LD) 290 A
Control Method V/f Control, Advanced Magnetic Flux Vector Control, Optimum Excitation Control
Enclosure Protection Rating IP00 (Open Type)
Operating Ambient Temperature -10 to +50 degC (non-freezing, LD rating up to +40 degC without derating)
Shipping Weight (Calculated) 74.0 kg

Connections and Interfaces

Terminal Group Function Assignment
R/L1, S/L2, T/L3 3-Phase AC main power input connections.
U, V, W 3-Phase AC motor power output connections.
P/+, PR, N/- DC link terminals for optional braking units or shared DC bus configurations.
Control Terminals Analog inputs (voltage/current), multi-function digital inputs, safety stop (S1/S2/SIC), and relay outputs.

Alternative Models & Compatibility

The unit acts as a direct modern replacement for the legacy FR-F740-03250 series. When replacing older F700 series models, parameter configuration files can be migrated using the FR Configurator2 software suite. Note that physical dimensions and mounting bolt patterns may differ slightly from the legacy series; ensure layout spacing in enclosed cabinets allows for the ventilation clearances required by the FR-F800 design.

Application Pitfalls & Engineering Notes

This large-capacity inverter exhibits significant thermal dissipation requirements during peak loads. Ensure your electrical enclosure has active ventilation capable of moving hot air away from the drive heat sinks, especially if operating continuously in ambient environments above 40 degC. For installations exceeding 1000 meters above sea level, apply a current derating factor of 1% per 100 meters up to a maximum altitude of 2500 meters.

Commissioning & Wiring Tips

Always ground the drive independently using a Class D grounding connection with a low impedance path. Ground currents generated by high-frequency PWM switching can interfere with sensitive near-field analog signals. It is highly recommended to run encoder, transducer, and control loops in separate, shielded conduits isolated from the main U/V/W motor output cables by at least 30 cm.

Installation Guidelines

CRITICAL WARNING: HIGH-VOLTAGE RISK

Before beginning any installation, maintenance, or terminal wiring work, completely disconnect the main power source. Wait at least 10 minutes for the internal DC bus capacitors to discharge safely. Verify that the charge indicator lamp on the front cover is completely off and measure the voltage across terminals P/+ and N/- to confirm it is below 30 VDC.

1
Mount the inverter vertically onto a flat, non-flammable vertical surface (such as a metal backplate) to guarantee optimal convective airflow across the rear-mounted heat sinks.
2
Connect structural grounds to the designated ground terminals. Securely connect the R/L1, S/L2, and T/L3 incoming power lines and the U, V, and W motor cables using the specified M8/M10 terminal bolt torque specs.
3
Wire the external safety inputs to the dual-channel S1/S2 safety terminals if emergency stop integration is required, ensuring the jumper is removed if using an external safety relay.

FAQ

What is the difference between Super Light Duty (SLD) and Light Duty (LD) ratings for this inverter?

The SLD rating supports continuous currents up to 325 A with 110 percent overload capacity for 60 seconds, ideal for low-torque fan and centrifugal pump loads. The LD rating supports up to 290 A with 120 percent overload capacity for 60 seconds, providing higher torque handling for general-purpose applications.

Can this drive run without an external 24 VDC control power supply?

Yes, the inverter can operate utilizing the internal power generated from the main AC input line. However, an external 24 VDC supply can be connected to the control terminal block to keep control circuits and communications active when main power is disconnected.

How do I address electromagnetic interference (EMI) issues affecting nearby analog sensors?

Ensure the motor cable is shielded with 360-degree grounding at both ends, separate signal wiring from power cables by a minimum of 30 cm, and utilize the built-in EMC filter by confirming the physical grounding jumper is correctly installed.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.

Replacing a 1769-OW8: Checks Before Moving Relay Loads

A field checklist for replacing Allen-Bradley 1769-OW8 relay output modules without losing load-group, wiring, and commissioning details.