1 of 1

Mitsubishi Electric GT2708-VTBD GOT2000 Series Graphic Operation Terminal

Mitsubishi Electric GT2708-VTBD GOT2000 Series Graphic Operation Terminal

Only 10 item(s) left in stock
  • Manufacturer: Mitsubishi Electric

  • Product No.: GT2708-VTBD

  • Country of origin:United States

  • Product Type: Human-Machine Interfaces

  • Payment: T/T, Western Union

  • Weight: 1500g

  • Dimensions: 241 mm x 194 mm x 52 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Engineered for high-resolution industrial visualization, the GT2708-VTBD is an 8.4-inch TFT color human-machine interface (HMI) within the high-performance GOT2000 Series. This terminal acts as a central control and monitoring hub, enabling seamless interaction between operators and automation systems. Equipped with a VGA display, it provides crisp graphical readouts of complex processes, machinery status, and diagnostic alarms.

The unit features an active-matrix TFT LCD designed for reliability in harsh industrial environments. Its self-cooling design and extensive terminal connectivity allow it to integrate cleanly into standard electrical control panels. Ideal for interfacing with programmable logic controllers (PLCs), motion controllers, and variable frequency drives, the terminal ensures stable operation under varying mechanical and electrical demands.

Features

  • High-clarity 8.4-inch TFT color screen supporting VGA (640 x 480) resolution.
  • Flexible layout configurations accommodating both horizontal and vertical mounting orientations.
  • Low-power standalone mode that reduces consumption to 8 W when the backlight is disabled.
  • Robust physical architecture compliant with international standards for mechanical shock and vibration.
  • Self-cooling system requiring no active fan components, minimizing dust intake.

Applications

  • Automotive assembly and robotic integration cells.
  • Water and wastewater treatment plant control stations.
  • Packaging, food, and beverage processing lines.
  • Power generation and auxiliary process monitoring.

Technical Specifications

ManufacturerPart Number / ModelSeriesDisplay SizeDisplay TypeResolutionFrame ColorInput Power Supply VoltageMaximum Power ConsumptionPower Consumption (Standalone)Power Consumption (Backlight Off)Inrush CurrentOperating Ambient Temperature (Horizontal)Operating Ambient Temperature (Vertical)Storage Ambient TemperatureOperating/Storage HumidityImpact ResistanceInsulation ResistanceWithstand VoltageCooling MethodExternal Dimensions (W x H x D)Weight
Mitsubishi Electric
GT2708-VTBD
GOT2000 Series (GT27)
8.4 inches
TFT Color LCD
VGA (640 x 480 pixels)
Black
24VDC (+25%, -20%)
39 W or less
13 W
8 W
5A or less (for 20 ms at 25 degC, max load)
0 to 55 degC
0 to 50 degC
-20 to 60 degC
10 to 90% RH (non-condensing)
Conforms to JIS B 3502 and IEC 61131-2 (147 m/s2 [15G], 3 times in X, Y, and Z axes)
10 MOhm or higher via 500VDC insulation tester (between power terminal and ground)
350VAC for 1 minute (between power terminal and ground)
Self-cooling
241 mm x 194 mm x 52 mm
1.5 kg (excluding mounting brackets)

Connections and Interfaces

Applicable Wire SizeTerminal Screw TypeTightening TorqueCompatible Solderless Terminals
Interface/Terminal Component Specification / Type
0.75 to 2 mm2
M3 Screw Clamp Terminals
0.5 to 0.8 N.m
RAV1.25-3, V2-S3.3, V2-N3A, FV2-N3A

Installation Guidelines

  • Mount the terminal inside a sealed electrical control enclosure to safeguard against greasy fumes, corrosive gases, and conductive dust.
  • Ensure adequate surrounding clearance to maintain clear self-cooling airflow paths.
  • Verify that the operating angle does not exceed thermal limitations (derate maximum operating temperature to 50 degC if mounted vertically).
  • Ground the terminal using the designated ground point with a dedicated Class D ground connection (100 ohms or less) to minimize electromagnetic interference.

Compliance and Certifications

  • IEC 61131-2 (Industrial-process control instruments - Specifications and tests)
  • JIS B 3502 (Japanese Industrial Standards for Programmable Controllers)
Loading product navigation…

What is the acceptable input voltage range for the GT2708-VTBD?

The terminal is rated for 24VDC with an acceptable input voltage tolerance of +25% to -20% (19.2VDC to 30VDC).

Does the HMI support vertical installation, and are there environmental restrictions?

Yes, vertical installation is supported. However, the maximum allowable operating ambient temperature is derated to 50 degC compared to 55 degC for horizontal installation.

What size and type of wire is required for the power terminal block?

The terminal block accepts wire sizes ranging from 0.75 to 2 mm2, utilizing M3 clamp screws with a recommended tightening torque of 0.5 to 0.8 N.m.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...