Mitsubishi Electric

Mitsubishi Electric QD81DL96 MELSEC-Q High-Speed Data Logger Unit

SKU QD81DL96

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Mitsubishi Electric

  • Product No.: QD81DL96

  • Country of origin:United States

  • Product Type: High-Speed Data Logger Units

  • Payment: T/T, Western Union

  • Weight: 150g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

Directly interfacing with the system backplane, the Mitsubishi Electric QD81DL96 high-speed data logger unit provides robust data logging capabilities for MELSEC-Q series PLC platforms. This module eliminates the need for dedicated personal computers or complex SCADA-based logging applications by recording system variables directly to localized memory media. Designed for precision diagnostics and predictive maintenance, the unit accesses and logs data from up to 64 connected CPUs in a multi-CPU configuration, matching sequence scan cycles with microsecond-level synchronization.

The QD81DL96 supports dual collection methodologies: high-speed trigger logging for transient events, and general-purpose continuous logging for historical trend analysis. Utilizing industry-standard file formats such as CSV, BIN, and Excel-compatible files, this module ensures that logged data is readily accessible by analytical packages, database engines, and supervisory control systems. Automated data transfer is facilitated through integrated FTP client/server protocols and email notification functions over a standard 100 Mbps Ethernet connection.

Features

  • Multi-CPU Integration: Accesses up to 64 CPUs simultaneously across the controller backplane.
  • Synchronized High-Speed Collection: Enables sequence scan time synchronization with collection intervals as fast as 1 ms for trigger logging and 3 ms for continuous logging.
  • Dual Logging Profiles: Offers both continuous and trigger-based data capture with configurable pre-trigger and post-trigger boundaries.
  • Direct Excel Report Generation: Automatically formats collected data into standard xls files directly on the local module.
  • Advanced Notification & Transfer: Embedded FTP client/server and SMTP capabilities allow automatic transmission of logged files to central servers and automated event notification emails.
  • Robust Storage Support: Features an integrated slot for industrial-grade CompactFlash (Type I) cards.

Applications

  • Traceability and quality assurance in high-speed manufacturing lines.
  • Transient fault analysis and sequence of events (SOE) recording in power distribution.
  • Long-term environmental and process variable trend monitoring in water treatment plants.
  • Equipment performance tracking and predictive maintenance in heavy machining.

Technical Specifications

Manufacturer Mitsubishi Electric
Part Number / Model QD81DL96
Series MELSEC-Q Series
Module Type High-speed data logger unit
Network Interface 10BASE-T / 100BASE-TX (RJ45)
Communication Mode Full duplex / Half duplex (with Auto-negotiation)
Storage Media Slot CompactFlash Card Type I (3.3 V DC, Max. 150 mA)
Occupied I/O Points 32 points (Intelligent function module)
Maximum CPUs Accessed Up to 64 CPUs
Logging Data Formats CSV, BIN, XLS (Excel)
Email Authentication No authentication, SMTP, AUTH (PLAIN, LOGIN, CRAM-MD5), POP before SMTP
Internal Current Consumption (5 V DC) 0.50 A
Height 98 mm
Width 27.4 mm
Depth 90 mm
Weight 0.15 kg

Connections and Interfaces

Interface Port Function Description
RJ45 Port Ethernet connection for FTP client/server communication, SMTP email transfer, and configuration utility interfacing.
CF Card Slot Dedicated Type I CompactFlash slot for industrial memory cards containing configuration data, system logs, recipes, and Excel reports.

Installation Guidelines

  • Backplane Insertion: Turn off the main rack power supply before inserting or removing the module from the Q-series base unit.
  • CompactFlash Handling: Format the CF card using the correct FAT file system before operation. Do not eject the card while the access LED is illuminated.
  • Shielding and Grounding: Use category 5 (or higher) shielded twisted pair (STP) cables for high-noise industrial environments to avoid signal loss or log interruption.
  • Ventilation: Ensure at least 30 mm of clearance above and below the base unit for proper heat dissipation.

FAQ

What memory card standard does the QD81DL96 support?

The module is designed with a dedicated slot for a Type I CompactFlash (CF) card, operating at 3.3V with a maximum supply power capacity of 150 mA.

Can the QD81DL96 access data from multiple CPUs in a single chassis?

Yes, it can access device memory and registers across up to 64 different CPUs in a multi-CPU system configuration.

What is the fastest data collection interval supported by this logger?

For trigger logging, the module supports sequence scan time synchronization down to a collection interval of 1 ms to 32767 ms. Continuous logging supports intervals from 3 ms to 32767 ms.

What file output formats does the QD81DL96 generate?

It can save data in CSV (.CSV) or Binary (.BIN) format for standard logging, and can output layout files in Excel (.XLS) format for report generation.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

First TwinCAT PLC Project on a Beckhoff IPC

Build and verify a first TwinCAT PLC project on a Beckhoff IPC. This checklist covers target selection, EtherCAT discovery, I/O mapping, safe activation, restart tests, and commissioning records.

Commissioning OPC UA in KEPServerEX: A Field Checklist

A practical commissioning sequence for KEPServerEX OPC UA connections: define data ownership, test tags locally, configure endpoint and certificate trust, limit access, then verify failure recovery...

Set a PLC Commissioning Laptop IP Without Losing Access

Commissioning an Ethernet-connected PLC often starts with the laptop, not the controller. Learn how to record existing settings, choose a temporary address, test connectivity, and restore the plant...

Designing Automation for Combustible Dust Hazards

Combustible dust controls require more than alarms. Learn how to map dust generation, select instrumentation, design interlocks, handle failed feedback, test safe states, and maintain the full...

Hairpin Stators: Benefits, Limits, and Inspection

Hairpin windings raise slot fill and support compact traction motors, but conductor geometry, AC losses, insulation damage, weld quality, and cooling determine whether the design meets its targets.

Using Ansible for Controlled SCADA Server Changes

Use Ansible to standardize SCADA server changes without expanding OT risk. This guide covers inventories, idempotent playbooks, staged testing, credentials, logging, and practical rollback controls.