Designed to facilitate seamless serial communication within Rockwell Automation CompactLogix control platforms, the ProSoft MVI69E-MBS provides high-speed integration of Modbus RTU and ASCII protocol devices. By acting as a direct interface module on the 1769 backplane, this module enables CompactLogix processors to interface easily with up to two independent Modbus networks. The device functions as either a Modbus Master or Slave, utilizing user-defined memory mapping to transfer up to 240 words of register data per direction. Configuration is managed via the dedicated ProSoft Configuration Builder utility, allowing field engineers to define baud rates, parity, and data transfer offsets without writing complex ladder logic.
| Parameter | Specification |
|---|---|
| Manufacturer | ProSoft Technology |
| Model Number | MVI69E-MBS |
| Compatible Backplane | Rockwell Automation 1769 CompactLogix |
| Backplane Current Draw | 500 mA at 5 VDC |
| Serial Ports | 2 x RJ45 (RS-232, RS-422, RS-485 configurable) |
| Baud Rate Range | 110 bps to 115.2 kbps |
| Data Map Size | Up to 240 16-bit read/write registers |
| Configuration Software | ProSoft Configuration Builder (PCB) |
| Operating Temperature | 0 to 60 degC |
| Storage Temperature | -40 to 85 degC |
| Shipping Weight (Calculated) | 3.0 kg |
The MVI69E-MBS serves as an upgraded alternative to the legacy MVI69-MCM module. While physical footprints are identical, the 'E' series utilizes Add-On Instructions (AOI) rather than traditional ladder-logic based block transfers. Existing legacy system conversions require updating the controller tag structures within Studio 5000 and downloading the latest .L5X files from ProSoft.
Observe the 1769 power supply distance rating when planning system layouts. The module has a distance rating of 4, meaning it cannot be installed more than 4 slots away from the power supply module. Exceeding this distance limit will result in intermittent backplane communication failures and module startup issues.
Always utilize the provided RJ45-to-DB9 terminal adapters to guarantee pin alignment for RS-485 multi-drop topologies. If you are constructing custom RJ45 cables, maintain proper shielding practices and terminate long RS-485 runs with 120-ohm resistors across Rx/Tx terminals to mitigate signal reflections.