Description
The Siemens 6AV7881-4AF00-4DT0 is a SIMATIC IPC277D Nanopanel PC, an integrated human-machine interface (HMI) solution for industrial environments. This unit features a 15-inch touch TFT display, an Intel Atom E660 (1.3 GHz) processor, and 2 GB of RAM for demanding visualization and control tasks. It is equipped with a comprehensive set of interfaces, including dual Gigabit Ethernet ports, multiple USB 2.0 ports, and a serial port, all powered by a standard 24 V DC supply. The system comes pre-loaded with Windows Embedded Standard 7 SP1 and includes licenses for WinCC Advanced RT, providing a ready-to-deploy platform for automation projects.
Features
- 15-inch color TFT resistive touch display
- Fanless design with Intel Atom E660 1.3 GHz processor
- 2 GB of integrated RAM
- 16 GB CompactFlash card for storage and operating system
- Pre-installed Windows Embedded Standard 7 SP1 (WES 7 SP1)
- Includes WinAC RTX F 2010, WinCC Advanced RT V13, and WinCC RT Advanced V14 license package
- Dual 10/100/1000 Mbps Ethernet interfaces for network connectivity
- Multiple USB 2.0 ports, including a front-accessible port
- Operates on a 24 V DC power supply
Applications
- Machine-level operator control and monitoring
- Process visualization (SCADA/HMI)
- Data acquisition and logging
- Factory and process automation control systems
- Manufacturing Execution Systems (MES) terminals
Technical Specifications
| Specification |
Value |
| Product Type |
Nanopanel PC |
| Display |
15" Touch TFT |
| Processor |
Intel Atom E660 (1.3 GHz) |
| Memory (RAM) |
2 GB |
| Storage |
16 GB SIMATIC PC CompactFlash |
| Operating System |
Windows Embedded Standard 7 SP1 (WES 7 SP1) |
| Pre-installed Software |
WinAC RTX F 2010; WinCC Advanced RT V13 2048 PT; WinCC RT Adv. V14 License Package |
| Power Supply |
24 V DC |
| Ethernet Ports |
2x 10/100/1000 Mbps Ethernet RJ45 |
| USB Ports |
1x Front USB; 3x USB V2.0 (High Current) |
| Serial Port |
1x Serial (COM 1) |
| Expansion Slots |
1x CompactFlash Slot |
| Product Lifecycle Status |
Phase-Out |
| Manufacturer |
Siemens |
| Country of Origin |
Germany (Estimated) |
| Package Dimensions (Calculated) |
60.50 x 41.50 x 6.50 cm |
| Shipping Weight |
4.55 kg |
Installation Guidelines
CRITICAL WARNING: Hazardous voltages may be present. Installation must be performed by qualified personnel only. Ensure all power sources are de-energized and locked out/tagged out (LOTO) before commencing any installation, wiring, or maintenance activities. Failure to comply can result in severe injury or death.
-
1
Panel Cutout and Mounting: Prepare the control cabinet panel cutout according to the manufacturer's dimensional drawings. Ensure the mounting surface is clean, flat, and rigid. Insert the Panel PC into the cutout and secure it evenly using all provided mounting clamps to maintain the specified ingress protection rating.
-
2
Protective Earth (PE) Connection: Connect the chassis to the control cabinet's protective earth system using a low-impedance conductor. Use the designated PE terminal on the Panel PC. This connection is critical for electrical safety and noise immunity.
-
3
Power Supply Wiring: Connect a stable, filtered 24 V DC power source to the designated power supply terminals. Verify correct polarity (+/-) before energizing. Use appropriately sized conductors and ensure the power supply is adequately rated for the PC's current draw.
-
4
Interface Connections: Connect Ethernet, USB, and serial cables as required by the application. Use shielded cables for all data communication lines and ensure shields are properly terminated to ground at one end to minimize electromagnetic interference (EMI). Route data cables separately from high-voltage power lines.
-
5
System Power-Up and Configuration: After verifying all connections, remove the LOTO device and apply power to the unit. The pre-installed operating system will boot. Proceed with network configuration, application software installation, and system commissioning as required.