ABB PM891K01 Replacement: Check Redundancy Before Ordering
ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.
Manufacturer: Triconex
Product No.: 3624
Country of origin:United States
Product Type: Digital Output Module
Payment: T/T, Western Union
Weight: 2700g
Dimensions: 25 x 430 x 400 mm (W x H x D)
Shipping port: Xiamen
Warranty: 12 months
Triconex 3624 is a 24 VDC TMR supervised digital output module for Tricon fault-tolerant control systems. It provides 16 commoned digital output points for controlling field devices in critical process applications.
The module receives output data from the three Tricon Main Processors through separate channels. Each set of three output signals is processed by a fully fault-tolerant quadruplicated output switch before being sent to the field termination.
Voltage and current loopback circuits continuously verify the output switches, field circuit, and connected load. These diagnostics operate without changing the commanded output state.
The supervision circuitry detects loss of field power, open loads, missing loads, shorted loads, and field shorts that could energize a load incorrectly. The module supports hot-spare operation and requires a separate external termination panel.
| Model | Product Description |
|---|---|
| 3624 | 24 VDC TMR supervised digital output module with 16 commoned points |
| Manufacturer | Triconex |
|---|---|
| Model | 3624 |
| Product Type | TMR Supervised Digital Output Module |
| System | Tricon |
| Architecture | Triple Modular Redundant |
| Output Type | Supervised digital output |
| Output Isolation | Opto-isolated |
| Output Configuration | Commoned |
| Number of Output Points | 16 |
| Nominal Field Voltage | 24 VDC |
| Field Voltage Range | 16 to 30 VDC |
| Maximum Field Voltage | 36 VDC |
| Voltage Drop | < 1.5 VDC, typical |
| Power Module Load | < 10 W |
| Maximum Current per Point | 0.7 A |
| Maximum Surge Current | 4.8 A for 10 ms |
| Minimum Required Load | 30 mA |
| Maximum Load Leakage | 4 mA |
| Output Protection | Self-protecting |
| Point Isolation | 1,500 VDC |
| Point Status Indicators | One On or Off indicator per point |
| Module Status Indicators | PASS, FAULT, ACTIVE |
| Field Alarm Indicators | POWER and LOAD, one per point |
| Module Color Code | Turquoise green |
| Operating Temperature | 0 degC to 60 degC, ambient at the bottom of the chassis |
| Storage Temperature | -40 degC to 75 degC |
| Relative Humidity | 5% to 95%, non-condensing |
| Sinusoidal Vibration | 2 G at 10 to 150 Hz per axis |
| Shock | 15 G for 6 to 11 ms in each axis |
| Hot-Spare Support | Supported |
| Field Termination | Separate external termination panel required |
| Termination Type | Compatible Model | Function |
|---|---|---|
| Commoned Termination Panel | 9662-610F | Commoned field termination for 24 VDC digital outputs |
| Basic Termination Panel | 9653-610F | Basic field wiring termination |
| Nonincendive Termination Panel | 9671-610F | Nonincendive field termination |
| Fanned-Out Cable | 9101-010F | Connects the chassis backplane to separately marshalled field wiring |
| Chassis Interface | Tricon I/O Bus | Transfers output and diagnostic data between the module and Main Processors |
Global Express Shipping
Returns & Warranty

Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Color pattern |
Black
|
| Country of origin |
United States
|
| Power source |