What Is SCADA? Supervisory Control Without Replacing the PLC
SCADA sits above PLCs and RTUs: it acquires field data, alarms operators, and issues supervisory commands across plants and remote assets—without replacing local deterministic control.



The Yokogawa SDV531-S33 is an 8-channel, 24 V DC safety-related digital output module designed for integration into Yokogawa ProSafe-RS safety instrumented systems (SIS). This high-reliability module provides galvanic module isolation and outputs discrete ON/OFF status signals to safeguard and control critical field equipment.
Equipped with autonomous field wiring diagnostic functions, the Yokogawa SDV531-S33 actively protects process environments. When a short-circuit fault occurs on the field side, the module automatically drives the corresponding output channel to an OFF state. After the line fault is cleared, the output channel can be securely restored via an intentional system Output Enable Operation to resume running application logic values. Without this deliberate enable command, the channel remains locked in its designated fail-safe value to ensure plant security.
| Model | Suffix Codes | Description |
|---|---|---|
| SDV531 | --- | Digital output module (8-channel, 24 V DC, module isolation) |
| --- | -S | Standard type |
| --- | 3 | With signal cable interface adapter and no explosion protection? (Note: User configuration overrides to 3) |
| --- | 3 | With ISA Standard G3 and temperature (-20 to 70 degC) |
| Parameter | Specification |
|---|---|
| Manufacturer | Yokogawa Electric Corporation |
| Country of Origin | Japan |
| System Compatibility | ProSafe-RS FIO Systems |
| Number of Outputs | 8-channel, module isolation |
| Output Voltage | 24 V DC |
| Output Voltage Drop | 1 V maximum |
| Output Format | Current source |
| External Power Supply | 24 V DC +20%/-10%, current capacity: 5 A |
| External Power Supply Rating | 24 V DC, 5 A minimum |
| Maximum Leak Current (Output OFF) | 1.6 mA |
| Maximum Load Current | 0.6 A per output line (4.8 A total for all output lines) |
| Minimum Load Current | 35 mA |
| Load Resistance Range | 40 to 685 Ohm |
| Output Response Time | 30 ms maximum |
| Withstand Voltage | 2 kV AC between output signal lines and system for 1 minute |
| Current Consumption | 280 mA maximum (5 V DC), 140 mA maximum (24 V DC) |
| Weight | Approx. 0.34 kg (With dedicated signal cable interface adapter) |
| Dimensions | 130 mm x 32.8 mm x 124 mm (Module depth 130 mm, height 124 mm, width 32.8 mm with interface adapter) |
| External Connection | Dedicated signal cable (AKB331) |
| Connector Type / Interface | Function |
|---|---|
| Signal Cable Interface Adapter | Connects to the field side via dedicated signal cable AKB331 |
| System Side Interface | Internal bus communication matching the Safety Node Unit / Safety Control Unit slots |
Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Color pattern |
Orange
|
| Country of origin |
Japan
|
| Power source |
DC Power
|