Allen-Bradley 1756-LSP GuardLogix 5560 Safety Partner Module

Allen-Bradley 1756-LSP GuardLogix 5560 Safety Partner Module

Only 4 item(s) left in stock
  • Manufacturer: Allen-Bradley

  • Product No.: 1756-LSP

  • Country of origin:สหรัฐอเมริกา

  • Product Type: Safety Partner Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 340g

  • Dimensions: 27 x 17 x 7 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

ปริมาณ
ดูรายละเอียดทั้งหมด

Description

The Allen-Bradley 1756-LSP serves as a dedicated, hardware-isolated redundant co-processor within safety-instrumented systems to execute multi-channel diagnostic and lockstep safety verification logic. Operating as a specialized safety partner module paired with a primary controller, this unit establishes an isolated secondary execution environment to safely handle safety-related functions up to and including SIL 3 and Performance Level e requirements. The device contains no localized user memory for standard operations; instead, its configuration parameters, clock operations, and safety memory structures are bound to and managed by the corresponding master unit.

Features

  • 1-Slot Co-Processing Footprint: Occupies a single slot immediately adjacent to the primary controller, forming a two-slot processing pair within the chassis backplane.
  • Dynamic Safety Memory Allocation: Safety allocation corresponds directly to the paired master unit, providing 1 MB when paired with 1756-L61S or 1756-L62S, and 3.75 MB when linked with a 1756-L63S.
  • High Connection Density: Manages up to 250 data connections for handling complex industrial safety interlock distributions.
  • Integrated Diagnostics: Built-in LED status indicators provide immediate local visual confirmation of execution states, errors, and sync conditions.
  • Nonvolatile Flash Backup: Ships complete with a pre-installed CompactFlash card to ensure secure storage of firmware images and operating parameters.

Applications

  • SIL 3 and Performance Level e (PL e) emergency shutdown loops in high-risk industrial fields.
  • Lockstep co-processing pairs within automated burner management systems (BMS) and pressing cells.
  • Fail-safe interlock handling in manufacturing setups requiring strict isolation from standard control logic execution paths.

Technical Specifications

Parameter Specification
Manufacturer Allen-Bradley / Rockwell Automation
Model Part Number 1756-LSP
Module Type Safety Partner Module
Series GuardLogix 5560
Compatible Primary Controllers 1756-L61S, 1756-L62S, 1756-L63S
Supported Connections 250
User / Standard Memory N/A (None)
Current Draw @ 5.1V DC 1200 mA
Current Draw @ 24V DC 14 mA
Power Dissipation 3.5 W
Thermal Dissipation 11.9 BTU/hr
Isolation Voltage 30V Continuous (Basic Insulation, Type-tested from RS-232 port-to-system at 720V DC for 60 seconds)
Local Serial Interface 1 x RS-232 port
Backup Battery Element 1756-BA2 (0.50 g lithium assembly)
Chassis Slot Width Allocation 1 slot (Requires adjacent slot for primary module; 2 slots total for operation)
Chassis Compatibility 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power Supply Compatibility 1756-PA50, 1756-PA72, 1756-PA75, 1756-PB50, 1756-PB72, 1756-PB75
Enclosure Class None (Open-Style)
Operating Temperature Range 0 Celsius to 60 Celsius
Non-Operating Temperature -40 Celsius to 85 Celsius
Relative Environmental Humidity 5-95% non-condensing
Mechanical Shock (Operating) 30 g
Mechanical Shock (Non-Operating) 50 g
Vibration Stress Tolerance 2 g at 10-500 Hz
Shipping Weight (Calculated) 0.75 lbs (0.34 kg)
Physical Dimensions (Calculated) 27 x 17 x 7 cm (10.63 x 6.69 x 2.76 in.)

Alternative Models & Compatibility

The 1756-LSP safety partner is structurally locked to the GuardLogix 5560 architecture. It functions solely when paired alongside a 1756-L61S, 1756-L62S, or 1756-L63S safety controller. Attempting to link this safety module with standard ControlLogix non-safety processors or newer ControlLogix 5570/5580 systems will result in backplane verification errors and halt CPU configuration loading.

Application Pitfalls & Engineering Notes

A major engineering pitfall occurs when calculating available workspace inside open enclosures. If the safety partner is not placed in the slot directly to the right of its primary controller, the pair cannot satisfy structural SIL 3 requirements, causing a total breakdown of safety loop integrity. Furthermore, because this card relies completely on the master controller for communication links and configuration parameters, its onboard RS-232 port cannot be independently utilized for broad network mapping or logic modification. Ensure the onboard 1756-BA2 lithium battery cell is monitored regularly; low energy levels can corrupt clock operations during complete system power blackouts.

Installation Guidelines

CRITICAL WARNING: De-energize and lock out all main backplane paths and external auxiliary supply voltages before mounting or extracting the co-processor hardware. Handling module installation steps while the rack contains active residual voltage risks triggering unexpected backplane noise spikes, communication drops on adjacent nodes, or component degradation.
1
Verify the position of the primary master controller (1756-L61S, -L62S, or -L63S) within the selected standard 1756 chassis rack.
2
Clear the unmanaged slot situated immediately to the right of that primary unit to allow proper mechanical alignment for SIL 3 tracking.
3
Align the circuit card tracks of the safety partner module with the plastic guides of the intended empty slot.
4
Slide the unit smoothly backward into the slot until the upper and lower mechanical clips seat flush and snap lock onto the chassis rim.
5
Restore power to the chassis and examine the forward LED cluster to confirm initialization and paired connection handshakes with the primary processor.

Does this safety partner module possess independent memory for user application logic?

No. The module contains no independent user memory for standard operations. It functions strictly as a redundant co-processor whose safety memory allocation depends on the memory footprint of the paired primary unit.

Can this module be placed in any open slot inside a ControlLogix chassis?

To satisfy SIL 3 safety compliance, the module must be mounted in the slot located immediately to the right of the primary safety controller.

What is the memory size allocation when pairing this unit with a 1756-L63S master processor?

When integrated with a 1756-L63S primary controller, the safety partner matches it by providing a safety memory structure of 3.75 MB.

What replacement battery type is required for this co-processor unit?

The module requires a 1756-BA2 lithium battery assembly, which contains approximately 0.50 grams of lithium to maintain clock and internal backup parameters.

การจัดส่งด่วนทั่วโลก

  • การจัดส่งมาตรฐาน: 4-6 วันทำการ ผ่าน DHL, FedEx และ UPS
  • จัดส่งด่วน: จัดส่งในวันเดียวกันสำหรับคำสั่งซื้อที่มีในสต็อกและสั่งก่อนเวลา 14:00 น. (GMT+8)
  • ครอบคลุมทั่วโลก: ให้บริการมากกว่า 150 ประเทศ รวมถึงการจัดส่งด่วนไปยังซาอุดีอาระเบียและสหรัฐอาหรับเอมิเรตส์

การคืนสินค้าและการรับประกัน

  • การรับประกัน 30 วัน: รับคืนสินค้าที่มีในสต็อกในบรรจุภัณฑ์เดิมที่ปิดผนึกจากโรงงาน
  • การรับประกัน 12 เดือน: อะไหล่อุตสาหกรรมทุกชิ้นได้รับการรับประกันทางเทคนิคจากผู้เชี่ยวชาญของเรา

คำสั่งซื้อจะถูกดำเนินการและจัดส่งในวันจันทร์ถึงวันศุกร์ (ไม่รวมวันหยุดราชการ)


สำหรับคุณสมบัติครบถ้วน ค่าธรรมเนียมการเติมสินค้าใหม่ และรายละเอียดการคืนสินค้าระหว่างประเทศ กรุณาดูที่เว็บไซต์อย่างเป็นทางการของเรา นโยบายการคืนเงินและการคืนสินค้า .

TECHNICAL SPECIFICATIONS

Color pattern
สีดำ
Country of origin
สหรัฐอเมริกา
Power source
ไฟฟ้ากระแสตรง ใช้พลังงานจากแบตเตอรี่

สินค้าที่ดูล่าสุด

ความรู้ทางเทคนิค

ตัวกระตุ้นไฟฟ้าที่ออกแบบมาเพื่อทดแทนระบบพลังงานของเหลว: คู่มือการทำงานอัตโนมัติในอุตสาหกรรมอย่างเป็นประโยชน์

บทความนี้อธิบายถึงวิธีที่แอคชูเอเตอร์ไฟฟ้าแบบบูรณาการ เช่น ซีรีส์ e-Actuator ของ SMC กำลังเปลี่ยนแปลงการควบคุมการเคลื่อนที่ในอุตสาหกรรมโดยการทดแทนระบบนิวเมติกและไฮดรอลิกแบบดั้งเดิม...

การดำเนินการทางคณิตศาสตร์โดยใช้ OpenPLC สำหรับแอปพลิเคชันระบบอัตโนมัติในอุตสาหกรรม

บทความนี้อธิบายวิธีที่ระบบ PLC ดำเนินการคำนวณทางคณิตศาสตร์พื้นฐาน เช่น การบวก การลบ การคูณ การหาร โมดูลัส และการยกกำลังในระบบอัตโนมัติอุตสาหกรรม...

ตรรกะบูลีนขั้นสูงด้วยการเขียนโปรแกรม FBD PLC: การประยุกต์ใช้งานในอุตสาหกรรมที่เกินกว่าตรรกะพื้นฐาน

บทความนี้อธิบายฟังก์ชันตรรกะบูลีนขั้นสูงหลายอย่างที่ใช้ในการเขียนโปรแกรม PLC นอกเหนือจากการดำเนินการพื้นฐานอย่าง AND, OR และ NOT โดยครอบคลุมถึงการใช้เครื่องมือต่างๆ เช่น ตารางความจริง มัลติเพล็กเซอร์...

ตรรกะบูลีนในการเขียนโปรแกรม PLC: ทำความเข้าใจเกตตรรกะ FBD

ตรรกะบูลีนเป็นพื้นฐานของโปรแกรม PLC ทุกโปรแกรม ตั้งแต่การควบคุมเครื่องจักรง่ายๆ ไปจนถึงระบบอัตโนมัติในอุตสาหกรรมที่ซับซ้อน...

คู่มือเชิงลึกเกี่ยวกับไฟร์วอลล์อุตสาหกรรมและการแบ่งส่วนเครือข่าย OT

ไฟร์วอลล์อุตสาหกรรมมีบทบาทสำคัญในความปลอดภัยไซเบอร์ของ OT โดยปกป้องเครือข่าย PLC, DCS และ SCADA ผ่านการแบ่งส่วน การควบคุมการเข้า/ออก และการผสานรวม IDS/IPS ที่สอดคล้องกับหลักการ IEC 62443

คู่มือการใช้งานกริปเปอร์หุ่นยนต์: ตั้งแต่การจับที่ละเอียดอ่อนจนถึงระบบอัตโนมัติสำหรับงานหนัก

กริปเปอร์หุ่นยนต์สมัยใหม่กำลังพัฒนาก้าวข้ามกรามกลไกแบบดั้งเดิม ตั้งแต่ระบบกาวที่ได้แรงบันดาลใจจากจิ้งจกและกริปเปอร์นุ่มที่ใช้ในอาหาร ไปจนถึงเครื่องมือคลังสินค้าที่ขับเคลื่อนด้วย AI...