1 / 3

Allen-Bradley 1794-IR8 FLEX I/O RTD Input Module

Allen-Bradley 1794-IR8 FLEX I/O RTD Input Module

Only 4 item(s) left in stock
  • Manufacturer: Allen-Bradley

  • Product No.: 1794-IR8

  • Country of origin:Amerika Birleşik Devletleri

  • Product Type: RTD Input Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 150g

  • Dimensions: 46 mm x 94 mm x 53 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Adet
Tüm ayrıntıları görüntüle

Description

The 1794-IR8 is a high-density resistance temperature detector (RTD) input module serving as an integrated component within the FLEX I/O distributed network terminal matrix. This field-side hardware solution interfaces directly with diverse temperature elements to capture highly accurate thermal variations, executing precise analog-to-digital data conversions across an isolated backplane. By shifting conversion processes directly to remote processing junctions on standard DIN rails, the device reduces complex analog cable lengths back to central processing nodes, transmitting values over communication adapters including EtherNet/IP, ControlNet, and DeviceNet.

This industrial unit features eight non-isolated input channels configured to process two-wire, three-wire, or four-wire RTD sensors, as well as pure resistance sensor signals. The 1794-IR8 plugs directly into a standard compatible terminal base unit, drawing operational power and establishing bus backplane lines automatically upon connection. This assembly is standard across petrochemical refining facilities, plastic extrusion plants, power grid sub-stations, and commercial cold-storage installations requiring continuous multi-point ambient and medium thermal monitoring.

Features

  • Eight channels for flexible scaling of thermal instrumentation.
  • Native compatibility with diverse platinum, nickel, and copper RTD types alongside pure ohmic sensor paths.
  • Selectable digital filtering settings minimizing high-frequency electrical background noise.
  • Live insertion capability supporting hardware swaps without interrupting communication to adjacent rail components.
  • Direct register mapping via the FlexBus backplane configuration for seamless integration into the host database.

Applications

  • Multi-point motor bearing temperature protection networks.
  • Petrochemical vessel and jacketed chemical reactor temperature tracking.
  • Food processing pasteurization line monitoring.
  • HVAC air-handler heat-exchanger efficiency verification loops.

Technical Specifications

Parameter Specification
Manufacturer Rockwell Automation / Allen-Bradley
Brand FLEX I/O
Part Number 1794-IR8
Module Type RTD Input Module
Number of Inputs 8 Channels, Non-Isolated
Supported Sensor Types 100, 200, 500, 1000 ohm Platinum; 120 ohm Nickel; 10 ohm Copper; 0 to 433 ohm Resistance
Resolution 16-bit across full range
Accuracy 0.1% of full scale
FlexBus Current Draw 20 mA at 5V DC
External Power Supply 24V DC nominal
Operational Voltage Range 10V DC to 31.2V DC
Power Dissipation 5.5 W maximum at 31.2V DC
Operating Temperature 0 to 55 degC
Storage Temperature -40 to 85 degC
Relative Humidity 5% to 95% non-condensing
Country of Origin USA
Approximate Weight 0.09 kg
Approximate Dimensions 46 mm x 94 mm x 53 mm

Connections/Interfaces

Terminal Block Connection (Typical 1794-TB3G) Function
L(+) / L(-) Ext. Power Supply 24V DC Input / Return Nodes
Channel 0 to Channel 7 Source Current Excitation Source Terminals for RTD Sensors
Channel 0 to Channel 7 Sense (+) Positive Differential Voltage Input Pins
Channel 0 to Channel 7 Return (-) Negative Common Return Reference Connections

Installation Guidelines

DIN Rail Installation

Hook the top groove of the module enclosure under the upper lip of standard 35 mm DIN tracking. Apply continuous firm downward pressure on the lower half of the housing until the integrated spring-loaded retention tab snaps shut behind the bottom tracking bar.

Terminal Base Seating

Align the dual guide tracks of the electronic module with the matching alignment grooves on the pre-wired terminal base unit. Slide the device flush into the base socket matrix until the top and bottom latch bars snap outward into their locked configurations.

Shielding and Grounding

Run all RTD sensor circuits utilizing individual high-quality shielded twisted-pair cables. Terminate the overall copper braided shield drain wire explicitly at the dedicated functional chassis ground points built into the terminal base assembly.

Sensor Cable Length Constraints

Keep three-wire and four-wire sensor cable runs within official resistance tolerances to prevent adding lead-wire impedance offset values to the internal temperature computation register matrix.

FAQ

What is the core function of this module assembly?

It provides an automated tracking interface that reads analog resistance values from RTD sensors and translates them into digital registers.

Can this unit handle two-wire and three-wire RTD sensors simultaneously?

Yes, each channel can be wired independently to match two-wire, three-wire, or four-wire probe layouts based on terminal configurations.

Are the individual instrumentation channels isolated from each other?

No, the eight measurement channels share a common internal reference within the conversion circuitry, though they are isolated from the main control bus.

How does the module deal with an open sensor wire fault?

The module sets an over-range status flag register for the damaged channel and outputs a specific value to indicate a broken sensor circuit.

Is it safe to pull this module off the rail while the main PLC is running?

Yes, it features removal and insertion under power capabilities, which allows engineers to perform field hot-swaps safely without disabling the network.

What terminal base units are compatible with this device?

The module is commonly paired with the 1794-TB3G, 1794-TB3GS, or 1794-TB32 terminal base units to manage the RTD signal wiring paths.

Does this device require a separate external power connection?

Yes, a nominal 24V DC external power source must be run to the terminal base block to power the internal sensor excitation and conversion matrices.

Can this device read raw ohm values instead of temperature parameters?

Yes, the channels can be software-configured to work in a pure resistance mode, measuring raw ohm values up to 433 ohms.

How is the sensor selection configured inside the system?

The target sensor material profile and wire configuration are designated by setting configuration parameters in the controller programming environment.

What is the digital conversion resolution of the measurement data?

The internal analog-to-digital converters process inputs using a precise 16-bit resolution matrix to deliver accurate temperature steps.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Gri Beyaz
Country of origin
Amerika Birleşik Devletleri
Power source
DC Güç

Recently Viewed Products

Technical knowledge

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robotik tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...

Geçmişe Dönüş: Erken Elektrik Motorları Yeraltı Madenciliğini Nasıl Değiştirdi?

Halatla çalışan DC kompresörlerden bataryalı maden arabalarına kadar, erken madencilik faaliyetleri endüstriyel elektrifikasyonda bir dönüm noktası oldu. Bu makale, elektrik motorlarının modern...

Factory I/O: Endüstriyel Otomasyon Eğitimi için Modern Bir PLC Simülasyon Aracı

Factory I/O, öğrenciler, mühendisler ve bakım ekipleri için sürükleyici 3D endüstriyel simülasyonlar sunarak PLC eğitimini dönüştürüyor. Platform, teori ile gerçek dünya otomasyon uygulamaları...

CMZ Servo Sürücüsünde Tek Eksenli Hareket Döngülerinin Programlanması

Bu eğitim, bir CMZ SBD servo sürücüsündeki dahili PLC işlevselliğinin, harici bir PLC olmadan homing mantığı, konum kontrolü ve döngüsel eksen hareketi dahil olmak üzere bağımsız hareket...

CMZ Servo Sürücülerle Tek Eksenli Hareket Kontrol Kurulumu

Bu eğitim, endüstriyel otomasyon ortamları için CMZ SBD sürücü kullanarak tek eksenli servo hareket sisteminin devreye alınmasını, donanım kurulumu, eksen ölçeklendirme, sıfırlama yapılandırması ve...