1 -ın, -in, -un, -ün (bağlama göre değişir) 1

Mitsubishi Electric FR-A840-01160-2-60 FR-A800 Variable Frequency Drive

Mitsubishi Electric FR-A840-01160-2-60 FR-A800 Variable Frequency Drive

Stokta sadece 10 adet kaldı
  • Üretici: Mitsubishi Electric

  • Ürün No.: FR-A840-01160-2-60

  • Menşei ülke:Amerika Birleşik Devletleri

  • Ürün Türü: Variable Frequency Drives

  • Ödeme: T/T, Western Union

  • Ağırlık: 41000g

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

Designed to meet the rigorous demands of heavy industrial motor control, the Mitsubishi Electric FR-A840-01160-2-60 is a high-performance variable frequency drive (VFD) from the flagship FR-A800 series. This 400V class inverter delivers precise control with a Super Light Duty (SLD) rated current of 116A, making it ideal for high-capacity fan, pump, and machinery installations. Engineered with a specialized varnished circuit board coating (-60 specification), it provides reliable defense against humidity and dust in demanding environments. Its IP00 open-type physical structure is optimized for integration into centralized control panels, leveraging forced air cooling to maintain thermal efficiency under continuous operation.

Features

  • Varnished Circuit Boards: Enhanced conformal coating (-60 spec) safeguards control and power electronics from atmospheric contamination without plated conductors.
  • High Current Capacity: Operates at 116A under Super Light Duty (SLD) rating, supporting demanding heavy-duty continuous operations.
  • Robust Voltage Tolerances: Designed for standard three-phase 380V to 500V AC power systems, with a reliable fluctuation tolerance of 323V to 550V AC.
  • Panel-Optimized Design: Open-type IP00 rating allows efficient, space-saving panel installations with integrated forced-air cooling.
  • High-Precision Control: Part of the advanced FR-A800 family, supporting real sensorless vector control and vector control options.

Applications

  • Industrial Ventilation Systems: High-volume fan arrays, blowers, and clean-room exhaust systems requiring continuous speed modulation.
  • Water and Wastewater Management: Centrifugal pumps, booster stations, and fluid processing plants.
  • Heavy Machinery Control: Extruders, large conveyor lines, and material handling systems requiring steady-state torque control.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number FR-A840-01160-2-60
Series FR-A800 Inverter Series
Voltage Class 400V Class
Rated Input AC Voltage Three-phase 380V to 500V AC, 50Hz/60Hz
Permissible AC Voltage Fluctuation 323V to 550V AC, 50Hz/60Hz
Permissible Frequency Fluctuation +/-5%
SLD Rated Current 116 A
Control/Structure Type Standard Model (-2 = CA Type)
Protective Structure Open Type (IP00)
Cooling Method Forced Air Cooling
Circuit Board Coating Varnished Conformal Coating (-60 specification)
Plated Conductor None
Product Weight 41 kg (90.4 lbs)
Shipping Weight (Calculated) 43 kg (94.8 lbs)

Connections and Interfaces

Terminal Block / Interface Functional Allocation
R/L1, S/L2, T/L3 Three-Phase AC Mains Power Input Terminals
U, V, W Three-Phase Variable Frequency AC Output to Motor
P/+, N/- DC Link Connection Terminals for Brake Unit or Shared DC Bus
PE Protective Earth / Chassis Ground Terminal
Control Terminals Dedicated I/O, Analog inputs (0-10V, 4-20mA), and multi-function relay outputs

Empirical Engineering Insights

Alternative Models & Compatibility

When migrating legacy systems from the FR-A700 series, the FR-A800 series provides backward parameters conversion. Parameter configurations can be imported using Mitsubishi’s FR Configurator2 software. Note that control terminal assignments are closely matched, but manual confirmation of safety-stop circuit allocations is required because of the safety standards implementation in the FR-A800 architecture.

Application Pitfalls & Engineering Notes

Because this VFD has a 41 kg weight footprint and relies on high-velocity forced air cooling, panel builders must ensure adequate airflow. Sealed enclosures require active heat exchangers or air conditioning units to handle the thermal load generated by the drive under continuous 116A SLD load conditions. Maintaining a minimum clearance of 100 mm above and below the cooling fans is necessary to prevent thermal shutdown events.

Commissioning & Wiring Tips

During initial power-up, verify that parameter 9 (electronic thermal O/L relay) matches your specific motor's nameplate data. Ensure all control-signal cables (such as 0-10V analog speed inputs) are routed in dedicated, shielded conduits distinct from high-power input/output cabling to eliminate high-frequency electromagnetic coupling.

Installation Guidelines

CRITICAL WARNING: Before commencing any installation or maintenance procedures, ensure all AC power sources feeding the R/L1, S/L2, and T/L3 terminals are physically locked out and tagged out. After power-off, wait a minimum of 10 minutes to allow the internal DC bus link capacitors to discharge completely. Verify that the voltage between terminals P/+ and N/- is 0V using a calibrated digital multimeter before handling terminals.
1

Mount the VFD vertically on a rigid, flat, heat-resistant surface inside the electrical enclosure to maximize convective air currents.

2

Connect the dedicated ground terminal (PE) directly to the system grounding plate using a low-impedance copper conductor.

3

Perform input power and motor terminal connections using calibrated torque tools, ensuring correct phase sequence on U, V, and W outputs.

Loading product navigation…

What is the physical meaning of the -60 suffix on the FR-A840-01160-2-60?

The -60 suffix specifies that the control and power printed circuit boards are treated with a specialized varnished conformal coating to improve environmental robustness, while omitting plated conductors.

What is the nominal and permissible voltage range for this inverter?

The drive accepts a nominal three-phase supply of 380V to 500V AC at 50/60Hz, with a maximum allowable voltage fluctuation range of 323V to 550V AC.

Can this unit be mounted horizontally to save enclosure space?

No. The FR-A840-01160-2-60 must be mounted vertically on a flat panel surface to preserve the effectiveness of its forced-air cooling system and prevent localized heat buildup.

How long must I wait after de-energization before performing wiring maintenance?

You must wait at least 10 minutes to allow the large internal DC-link capacitors to discharge. Always measure the voltage across terminals P/+ and N/- to confirm it is below safe thresholds before starting work.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Birleşik Devletleri

Son Görüntülenen Ürünler

Teknik bilgi

Sıvıların Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Uygulamalı Eğitim

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...