Omron CJ1W-DA021 CJ Series Analog Output Module

Omron CJ1W-DA021 CJ Series Analog Output Module

Stokta sadece 8 adet kaldı
  • Üretici: Omron

  • Ürün No.: ÿCJ1W-DA021

  • Menşei ülke:Japonya

  • Ürün Türü: PLC Analog Output Modules

  • Ödeme: T/T, Western Union

  • Ağırlık: 150g

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

Regulating analog actuators and control loops within Sysmac PLC architectures is the primary functional role of the Omron CJ1W-DA021. This CJ-series Special I/O Unit provides two high-resolution analog output channels, supporting standard industrial current and voltage ranges. Built with internal photocoupler isolation between the controller backplane and the external interface, this module prevents field electrical noise from corrupting core logic operations. The physical connection is established through an 18-point detachable terminal block with M3 screws, facilitating rapid wiring, commissioning, and simplified hot-swap unit replacement during field maintenance.

Key Features

  • Dual-Channel Output: Supports two independent analog outputs configurable for voltage or current loops.
  • Flexible Signal Ranges: Compatible with standard industry spans including 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, and 4 to 20 mA.
  • High Resolution: Operates at a maximum conversion resolution of up to 40,000 for precise variable control.
  • Photocoupler Isolation: Secure isolation barrier between the internal PLC controller backplane and external output circuitry.
  • Maintenance-Friendly Terminal Block: Detachable 18-point block with M3 screws allows replacement without disconnecting field wiring.

Applications

  • Variable Speed Drive Regulation: Direct frequency and speed commanding for industrial inverters and VFDs.
  • Proportional Valve Control: Modulating flow rates, pneumatic pressures, and hydraulic positions in process loops.
  • HVAC Damper Actuation: Positioning air dampers and control valves based on real-time environmental demands.
  • External Chart Recording: Routing physical process variables to analog instrumentation, displays, or recording units.

Technical Specifications

Parameter Value / Specification
Manufacturer Omron
Model Code CJ1W-DA021
Product Type CJ-series Special I/O Unit (Analog Output Module)
Number of Outputs 2 channels
Output Ranges (Voltage) 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V
Output Ranges (Current) 4 to 20 mA
Max Resolution 1/40,000 (Set data: 16-bit binary)
Output Impedance (Voltage) 0.5 Ohm max.
Max Output Current (Voltage) 12 mA (for 1 point)
Max Permissible Load Resistance 600 Ohm (for current output)
Backplane Current Consumption 5 VDC, 120 mA max.
External Power Supply Requirements 24 VDC +10% -15%, 140 mA max. (Inrush: 20 A max., 1 ms min. pulse)
Isolation Method Photocoupler isolation between I/O and controller backplane (No isolation between channels)
External Connections 18-point detachable terminal block (M3 screws)
Unit Weight 0.15 kg
Shipping Weight 1.50 kg (including secure export packaging)

Connections and Interfaces

Terminal Assignment Signal Name Functional Circuit Assignment
V OUT 1 Voltage Output 1 Positive voltage output connection for Channel 1
I OUT 1 Current Output 1 Positive current output connection for Channel 1
COM 1 Output Common 1 Common return terminal for Channel 1
V OUT 2 Voltage Output 2 Positive voltage output connection for Channel 2
I OUT 2 Current Output 2 Positive current output connection for Channel 2
COM 2 Output Common 2 Common return terminal for Channel 2
24 VDC External Power Supply (+) Positive supply terminal for external 24 VDC input
0 VDC External Power Supply (-) Negative/Ground reference for external 24 VDC input

Empirical Engineering Insights

Alternative Models & Compatibility

The CJ1W-DA021 serves as a direct drop-in replacement for older CJ1W-DA021 revision versions. When planning retrofits from older Sysmac platforms (such as the C200H series), direct logic mapping is required because of backplane addressing variations. Ensure your CJ1G, CJ1H, or CJ2H CPU unit has been allocated corresponding DM and CIO Area channels using CX-Programmer or Sysmac Studio software to match the unit's rotary physical address switches.

Application Pitfalls & Engineering Notes

A key layout constraint is that no isolation exists between output channels 1 and 2. Both channels share a common internal ground point. If you connect this module to two field devices that are separately grounded at different physical points, ground loops can form, causing signal drift or module damage. To prevent this, always route outputs to devices with internally isolated inputs, or add physical external loop isolators between the module and any non-isolated field targets.

Commissioning & Wiring Tips

Ensure that the external 24 VDC power supply is fully active before or simultaneously with the PLC CPU backplane startup. If the external 24 VDC drops below the -15% tolerance limit (20.4 VDC), the module's orange status indicator will trip, and an I/O verification error will register at the processor level. Always use shielded, twisted-pair cables for analog routing and ground the shield only at the PLC chassis ground terminal to avoid ambient RF noise infiltration.

Installation Guidelines

CRITICAL WARNING

Disconnect all electrical power to the PLC rack and field-side circuits before physically attaching or removing this Special I/O Unit. Failure to completely de-energize the assembly can destroy internal components or cause erratic PLC CPU behavior.

1

Set the unit number rotary dials on the front panel of the CJ1W-DA021 to the desired address (0 to 95) prior to mounting. Avoid duplicating unit numbers across the PLC backplane.

2

Align the upper and lower track hooks of the module with the adjacent rack unit, slide the unit securely into position, and engage the locking slide clamps on the top and bottom of the CJ-series rack.

3

Wire the 18-point detachable terminal block with crimped M3 terminals, ensuring positive 24 VDC external supply connections are completed before powering on the system.

Loading product navigation…

Does the CJ1W-DA021 provide isolated outputs between individual channels?

No. The module provides optical isolation between the controller backplane and the overall analog circuit, but the individual output channels (Channel 1 and Channel 2) share a common internal return line (COM) and are not isolated from each other.

What behavior occurs if the external 24 VDC power supply drops out?

If external 24 VDC power is disconnected or falls below the minimum limit (20.4 VDC), the module will deactivate its analog outputs, the orange status indicator will illuminate, and the host PLC CPU will trigger a Special I/O Unit error.

How is the CJ1W-DA021 address configured in the PLC software?

The module unit number is set manually using the front-panel rotary switches. The PLC CPU reserves memory blocks in the Special I/O Unit CIO and DM areas corresponding directly to this hardware address, where configuration parameters are written via CX-Programmer.

Can I use voltage and current outputs simultaneously on the CJ1W-DA021?

Yes. Each channel is configured independently in the PLC memory settings, and you can wire Channel 1 for a current loop (such as 4-20 mA) while wiring Channel 2 for a voltage loop (such as 0-10 V) using the dedicated V OUT and I OUT terminals.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Japonya

Son Görüntülenen Ürünler

Teknik bilgi

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...

Geçmişe Dönüş: Erken Elektrikli Motorlar Yeraltı Madenciliğini Nasıl Değiştirdi

Halatla çalışan DC kompresörlerden bataryalı maden arabalarına kadar, erken madencilik faaliyetleri endüstriyel elektrifikasyonda bir dönüm noktası oldu. Bu makale, elektrik motorlarının modern...