1 -ın, -in, -un, -ün (bağlama göre değişir) 1

Omron NX-CIF210 NX Series Communications Interface Unit

Omron NX-CIF210 NX Series Communications Interface Unit

Stokta sadece 3 adet kaldı
  • Üretici: Omron

  • Ürün No.: NX-CIF210

  • Menşei ülke:Japonya

  • Ürün Türü: PLC Communication Modules

  • Ödeme: T/T, Western Union

  • Ağırlık: 1500g

  • Boyutlar: 7.1cm x 3.0cm x 10cm

  • Gönderim limanı: Xiamen

  • Garanti: 12 ay

Miktar
Tüm detayları görüntüle

Description

Integrating legacy serial instruments and third-party peripherals into modern Sysmac architectures is streamlined using the Omron NX-CIF210. This high-density serial communications interface unit expands the capabilities of NX-series I/O systems and NJ/NX CPU racks by adding two independent, non-isolated RS-232C ports. Operating primarily under "No-protocol" transmission modes, it allows raw ASCII or hexadecimal data exchange with devices such as barcode readers, weight scales, and industrial sensors, without requiring complex protocol stacks.

Features

  • Dual-Channel Interface: Equipped with two independent RS-232C communication channels utilizing industry-standard D-Sub 9-pin connectors.
  • Flexible Architecture: Mounts seamlessly to NX-series EtherCAT Coupler Units or directly to compatible NX-series Controller Units.
  • High-Speed Bus Sync: Synchronizes serial data buffering with the internal NX-bus cycle for deterministic control execution.
  • Simplified Configuration: Full setup, baud rate adjustment, and diagnostics integrated directly within the Sysmac Studio software environment.
  • Space-Saving Profile: Compact 30 mm housing width reduces overall footprint inside electrical control panels.

Applications

  • Connecting factory-floor barcode scanners and handheld RFID readers.
  • Interfacing with precision electronic weigh scales and laboratory instruments.
  • Establishing serial point-to-point links with legacy HMIs or display panels.
  • Data acquisition from temperature controllers and flow meters via serial command sets.

Technical Specifications

Specification Parameter Value / Detail
Manufacturer Omron
Model Number NX-CIF210
Product Series NX Series I/O System
Module Type Serial Communications Interface Unit
Number of Ports 2
Physical Interface RS-232C (D-Sub 9-pin Female connectors)
Communications Protocol No-protocol (Host Link support available depending on master controller configuration)
Isolation Method No isolation (between ports or internal bus circuits)
Product Dimensions 100 mm (H) x 30 mm (W) x 71 mm (D)
Net Weight 0.091 kg (91 grams)
Shipping Weight (Calculated) 1.50 kg (including commercial protective packaging)
Country of Origin Japan

Connections and Interfaces

The unit features two front-facing 9-pin D-sub connectors. The pin assignment conforms to standard RS-232C signal layouts:

Pin Number Signal Abbreviation Signal Direction Description
1 CD Input Carrier Detect
2 RDD (RXD) Input Receive Data
3 SDR (TXD) Output Transmit Data
4 DTR Output Data Terminal Ready
5 SG -- Signal Ground
6 DSR Input Data Set Ready
7 RTS Output Request to Send
8 CTS Input Clear to Send
9 RI Input Ring Indicator

Alternative Models & Compatibility

For installations requiring screwless push-in clamping terminals instead of D-Sub 9 connectors, the NX-CIF101 provides a single-channel RS-232C port. If RS-422A or RS-485 serial communication is required, the NX-CIF105 should be selected instead. Confirm firmware compatibility inside Sysmac Studio when mixing older unit revisions with newer NX1P2 or NX102 series controllers.

Application Pitfalls & Engineering Notes

Because this module is non-isolated, ensure that both the NX-series system ground and the ground of the connected RS-232C device are at identical electrical potentials. Significant potential differences can cause ground loop currents, resulting in communication errors or permanent damage to the module's transceiver IC. To preserve signal integrity, the maximum allowable cable length for RS-232C connections is strictly 15 meters.

Commissioning & Wiring Tips

When assembling custom RS-232C cables, always connect the cable shield to the metal hood of the D-Sub connector on the NX-CIF210 end only. This path routes high-frequency noise directly to the DIN rail ground system. If communication failures occur during startup, use the Sysmac Studio monitoring tools to verify if the frame length matches the buffer configuration set in the memory allocation table.

Installation Guidelines

CRITICAL WARNING

Always completely isolate the 24 VDC control power supply to the NX-bus and any connected serial devices before mounting, sliding, or unmounting the unit. Failure to fully de-energize the assembly can cause backplane communication lockouts or damage the internal bus contacts.

1

Align the interlocking guide rails of the NX-CIF210 with the adjacent NX unit on the DIN rail and slide the module together until the side lock click is engaged.

2

Hook the bottom mounting latch to the DIN rail and apply light upward pressure until the module locks firmly into place.

3

Insert the D-Sub 9-pin connector cables and hand-tighten the retaining screws to prevent loose contacts and maintain a continuous shield path.

Loading product navigation…

Can the NX-CIF210 be used for Modbus-RTU master communication?

Yes. When configured under Sysmac Studio and paired with an appropriate Omron CPU (such as the NX1P2 or NJ series), the unit supports Modbus-RTU master communication by utilizing dedicated system function blocks for serial send and receive.

How does the NX-CIF210 differ from the NX-CIF101?

The NX-CIF210 features two independent RS-232C channels terminated in standard D-Sub 9-pin female connectors. The NX-CIF101 features a single RS-232C channel terminated with screwless push-in clamping terminals.

Is there electrical isolation between the two RS-232C ports?

No, the two RS-232C ports on the unit are not electrically isolated from each other or from the internal NX-bus. Proper grounding and equipotential bonding are required to avoid ground loops.

What is the maximum cable length supported by this module?

Consistent with RS-232C standard specifications, the maximum cable run length from the unit to any connected peripheral is 15 meters.

Küresel Ekspres Kargo

  • Standart Teslimat: DHL, FedEx ve UPS ile 4-6 iş günü.
  • Hızlı Gönderim: Saat 14:00 (GMT+8) öncesi verilen stoktaki siparişler aynı gün gönderilir.
  • Dünya Çapında Hizmet: Suudi Arabistan ve BAE'ye hızlı teslimat dahil 150'den fazla ülkeye hizmet veriyoruz.

İadeler ve Garanti

  • 30 Günlük Garanti: Stokta bulunan ürünler, orijinal, fabrika mühürlü ambalajında iade kabul edilir.
  • 12 Aylık Garanti: Her endüstriyel bileşen profesyonel teknik garantimizle desteklenmektedir.

Siparişler Pazartesi-Cuma günleri işlenir ve teslim edilir (resmi tatiller hariç).


Tam uygunluk, stok yenileme ücretleri ve uluslararası iade detayları için lütfen resmi sayfamızı inceleyin İade ve Geri Ödeme Politikası .

TECHNICAL SPECIFICATIONS

Country of origin
Japonya

Son Görüntülenen Ürünler

Teknik bilgi

Akışkan Güç Sistemlerinin Yerini Almak İçin Tasarlanmış Elektrikli Aktüatörler: Pratik Bir Endüstriyel Otomasyon Rehberi

Bu makale, SMC’nin e-Actuator serisi gibi entegre elektrikli aktüatörlerin, geleneksel pnömatik ve hidrolik sistemlerin yerini alarak endüstriyel hareket kontrolünü nasıl dönüştürdüğünü...

Endüstriyel Otomasyon Uygulamaları için OpenPLC Kullanarak Matematiksel İşlemler

Bu makale, PLC sistemlerinin endüstriyel otomasyonda toplama, çıkarma, çarpma, bölme, mod alma ve üs alma gibi temel matematiksel işlemleri nasıl gerçekleştirdiğini açıklar. Bu fonksiyon bloklarının,...

FBD PLC Programlamada Gelişmiş Boolean Mantığı: Temel Mantığın Ötesinde Pratik Endüstriyel Uygulamalar

Makale, temel AND, OR ve NOT işlemlerinin ötesinde PLC programlamada kullanılan birkaç gelişmiş Boolean mantık fonksiyonunu açıklar. Doğruluk tabloları, çoklayıcılar, darbe üreteçleri ve Schmitt...

PLC Programlamada Boolean Mantığı: FBD Mantık Kapılarını Anlamak

Boolean mantığı her PLC programının temelidir. Basit makine kontrollerinden karmaşık endüstriyel otomasyon sistemlerine kadar, mantık kapıları kontrolörlerin değişen girişlere ve çalışma koşullarına...

Endüstriyel Güvenlik Duvarları ve OT Ağ Segmentasyonu İçin Derinlemesine Rehber

Endüstriyel güvenlik duvarları, PLC, DCS ve SCADA ağlarını segmentasyon, giriş/çıkış kontrolü ve IEC 62443 prensipleriyle uyumlu IDS/IPS entegrasyonu yoluyla koruyarak OT siber güvenliğinde kritik...

Robotik Tutucular Rehberi: Hassas İşlemeden Ağır Hizmet Otomasyonuna

Modern robot tutucular, geleneksel mekanik çenelerin ötesine geçiyor. Geckoya ilham veren yapışkan sistemlerden yumuşak gıda sınıfı tutuculara ve yapay zeka destekli depo araçlarına kadar gelişmiş...