1 trong số 1

Bently Nevada 177230-01-01-05 Seismic Transmitter

Bently Nevada 177230-01-01-05 Seismic Transmitter

Only 5 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 177230-01-01-05

  • Country of origin:Hoa Kỳ

  • Product Type: Seismic Transmitter

  • Payment: T/T, Western Union

  • Weight: 131g

  • Dimensions: 66.0 mm x 25.4 mm x 25.4 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Description

The Bently Nevada 177230-01-01-05 is a loop-powered seismic transmitter designed for machinery condition monitoring. It integrates directly into programmable logic controllers (PLCs), DCS, and SCADA systems that provide internal loop power. The 177230-01-01-05 processes vibration measurements and outputs a primary 4 to 20 mA current loop representing velocity vibration, along with a secondary raw dynamic voltage output representing acceleration for detailed signal analysis.

Features

  • Interfaces directly with PLCs, DCS, and SCADA control systems.
  • Provides a primary 4 to 20 mA loop-powered velocity output and a secondary raw dynamic voltage output.
  • Requires no field configuration or adjustments.
  • Features a hermetically sealed 316L stainless steel case for demanding environments.
  • Includes self-test capabilities and a protected interface.

Applications

  • Machinery asset condition monitoring
  • Overall plant vibration measurement
  • Balance-of-plant rotating machinery protection
  • Integration into PLC, DCS, and SCADA control loops

Ordering Information

Option / Ordering Code Description
177230-AA-BB-CC Seismic Transmitter
AA: Measurement Range 01 = 0 to 25.4 mm/s (0 to 1.0 in/s)
BB: Frequency 01 = 10 Hz to 1 kHz (600 to 60 kcps) rms
CC: Approvals 05 = Multiple Approvals (CSA/NRTL/C, ATEX/IECEx)

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada
Model 177230-01-01-05
Product Type Seismic Transmitter
Main Loop Sensitivity (Signal One) 0.0 to 25.4 mm/s (0 to 1.0 in/s) +/- 10% FS, broadband rms
Output Format (Pin A ref Pin B) 4 to 20 mA current loop, velocity vibration
Dynamic Signal Sensitivity (Signal Two) 10.2 mV/m/s2 (100 mV/g) +/- 20%
Output Format (Pin C ref Pin B) Voltage, acceleration vibration, unbuffered
Dynamic Signal Frequency Response 2.5 Hz to 10 kHz (150 cpm to 600 kcpm) +/- 10%
Main Loop Frequency Response 10 Hz to 1 kHz (600 cpm to 60 kcpm) +/- 10%
Excitation Voltage 12 to 30 Vdc (current limited to 40 mA)
Settling Time Less than 15 seconds within 2% of final value
Linearity +/- 1%
Output Bias (ref Pin B) 2.5 V +/- 0.1 V
Full Scale Range 147 m/s2 (15 g's) peak
Mounted Resonant Frequency Greater than 12 kHz
Transverse Sensitivity Less than 5% of sensitivity
Sensing Element Type Ceramic / Shear
Operating Temperature Range -40 degC to +85 degC (-40 degF to +185 degF)
Electrical Isolation Greater than 10^8 ohms
Isolation Breakdown Voltage 600 Vrms with less than 1 mA leakage current
Sensor Seal Hermetically sealed
Relative Humidity To 100% non-submerged
Case Material 316L stainless steel
Connector Type 3-pin MIL-C-5015, 316L stainless steel
Mounting Hole / Threads 1/4-28 UNF; supplied with M6x1, M8x1.25, and 1/4-28 UNF adapters
Mounting Torque 4 to 7 N-m (35.4 to 62.0 in-lbf)
Transmitter Weight 131 g (4.62 oz) typical
Dimensions 25.4 mm (1.00 in) Diameter x 66.0 mm (2.60 in) Height

Connections/Interfaces

Connector Pin Function
Pin A 4-20 mA Positive Loop (Positive with reference to Pin B)
Pin B 4-20 mA Negative Loop / Return for Dynamic Signal
Pin C Dynamic Signal in voltage, unbuffered (Referenced to Pin B)

Installation Guidelines

  • Mounting Method: Mount directly to the machine surface using the provided stud adapters and torque to 4 to 7 N-m.
  • Magnetic Base Precaution: If using a magnetic base, roll the base onto the machine surface. Avoid snapping the unit onto the machine, as sudden impact can generate large voltage spikes that may damage internal electronics.
  • Grounding and Signal Isolation: Ensure the dynamic signal return (Pin B) is isolated from external grounds. Grounding this terminal shorts the 4 to 20 mA current loop, resulting in signal loss.

Compliance and Certifications

  • FCC: Complies with Part 15 of FCC Rules.
  • EMC: EMC Directive 2014/30/EU.
  • RoHS: RoHS Directive 2011/65/EU.
  • CSA/NRTL/C: Class I, Div 1, Groups A, B, C, D; Class II, Div 1, Groups E, F, G; Class III, Div 1 (Ex ia IIC T4 / AEx ia IIC T4); Class I, Div 2, Groups A, B, C, D (Ex nL IIC T4 / AEx nA IIC T4).
  • ATEX/IECEx: II 1 G Ex ia IIC T4 Ga / II 3 G Ex na IIC T4 Gc (Ta = -40 degC to +80 degC).
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 177230-01-01-05 Seismic Transmitter

What power supply is required to operate the device?

The device operates on a 12 to 30 Vdc loop power excitation voltage, current limited to 40 mA, typically supplied directly by host PLCs or DCS controllers.

What outputs are provided by the unit?

The device provides a primary 4 to 20 mA loop-powered velocity output on Pin A and a secondary unbuffered dynamic acceleration voltage output on Pin C.

What mounting precaution should be followed when using a magnetic base?

The device must be rolled onto the machine surface rather than snapped into place, preventing mechanical shocks that can produce high voltage spikes and damage internal electronics.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Bạc
Country of origin
Hoa Kỳ

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.

What It Really Takes to Learn Industrial Automation in 2026

Learning industrial automation now means mastering PLCs, networks, and protection systems—not just robots. This guide maps skills, pitfalls, and career paths for engineers entering control-heavy...

Hiện đại hóa HMI Bailey INFI 90 Symphony chạy trên OpenVMS Alpha

Hướng dẫn thực tiễn về việc thay thế các trạm vận hành Bailey Symphony đã cũ chạy trên OpenVMS Alpha. Tài liệu so sánh phương án giả lập Alpha, chuyển đổi sang OpenVMS x86, tái nền tảng OPC và hiện...

Vì sao dữ liệu bảo trì thiết yếu đối với độ tin cậy trong công nghiệp

Dữ liệu bảo trì kết nối các lệnh công việc, tín hiệu cảm biến, lịch sử tài sản, chi phí và kiến thức của kỹ thuật viên. Khi được sử dụng hiệu quả, dữ liệu này giúp cải thiện công tác lập kế hoạch, độ...

Bộ truyền động điện được thiết kế để thay thế hệ thống truyền động chất lỏng: Hướng dẫn thực tiễn về tự động hóa công nghiệp

Bài viết này giải thích cách các bộ truyền động điện tích hợp, chẳng hạn như dòng e-Actuator của SMC, đang chuyển đổi hoạt động điều khiển chuyển động trong công nghiệp bằng cách thay thế các hệ...

Các phép toán bằng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện những phép toán cốt lõi như cộng, trừ, nhân, chia, chia lấy dư và lũy thừa trong tự động hóa công nghiệp. Bài viết trình bày cách các khối hàm...