1 trong số 3

HIMA F 7133 H51q System Family 4-Fold Power Distribution Module

HIMA F 7133 H51q System Family 4-Fold Power Distribution Module

Only 10 item(s) left in stock
  • Manufacturer: HIMA

  • Product No.: F7133

  • Country of origin:Đức

  • Product Type: Power Distribution Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 160g

  • Dimensions: 2cm x 18.8cm x 12.8cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Description

The HIMA F 7133 is a non-interactive 4-fold power distribution module designed for the H51q System Family to provide fuse monitoring and L- distribution. The module functions within the I/O subrack (occupying slots 18 to 21) to supply and protect I/O modules, sensor contacts, and actuator circuits. It incorporates four miniature fuses that provide line protection, with each fuse monitored via an internal evaluation logic block. Power for the I/O modules is fed into the rear side of the power distribution modules via XG. 7/8/9/10, allowing specific slots to allocate power to designated groups of I/O slots. Built-in failure signalization is achieved through dedicated front-panel LEDs and an integrated relay contact to report missing or faulty fuse states safely.

Features

  • Provides 4-channel power distribution with independent fuse protection for each current path.
  • Integrates evaluation logic to monitor the operational state of each miniature fuse continuously.
  • Features front-panel LED indicators that stay on when a path is functional, flash when a fuse is faulty or missing, and turn off if supply voltage fails.
  • Equipped with a safety-related relay contact that remains closed when all fuses are functional and de-energizes automatically if any fuse is missing or faulty.
  • Designed as a non-interactive module ensuring isolated line protection across subrack assemblies.

Applications

  • 24 V DC power supply and distribution for safe routing to I/O slots within HIMA safety subracks.
  • Fused power circuit distribution for external sensors and actuator contacts.
  • Failure-signaling and monitored power marshalling in industrial automation and safety-instrumented systems.

Ordering Information

Part Type Designation Alternative Designation Functional Description
F 7133 F7133 4-fold power distribution with fuse monitoring and L- distribution

Technical Specifications

Parameter Value
Manufacturer HIMA Paul Hildebrandt GmbH + Co KG
Fuses max. 4 A slow blow
Switching Time approx. 100 ms (relay)
Loadability of the Relay Contacts 30 V/4 A (continuous load)
Residual Voltage (Fuse Tripped) 0 V
Residual Current (Fuse Tripped) 0 mA
Residual Voltage (Missing Supply) max. 3 V
Residual Current (Missing Supply) < 1 mA
Space Requirement 4 TE
Operating Data 24 V DC: 60 mA

Connections/Interfaces

Connector Pin Function
Front Contacts 1, 2, 3, 4 Connection for L+ resp. EL+ to supply the I/O modules and sensor contacts
Front Contact L- Connection for L- distribution
Rear Contacts d6, d10, d14, d18 Terminals for 24 V supply of one I/O slot each
Relay Contacts d22/z24 Safety monitoring loop contact (closed when all fuses are in order)

Installation Guidelines

  • Subrack Positioning: Install the module into slots 18 to 21 of the I/O subrack based on the specific group of I/O slots requiring power distribution.
  • Wiring Setup: Wire the supply inputs directly to the front-side contact pins (1, 2, 3, 4, and L-) via the front cable plug to establish the monitoring circuit.
  • Rear Connection Check: Secure the power feed to the rear side of the modules using XG. 7/8/9/10 connectors for proper distribution to the bus board.

Compliance and Certifications

  • CE

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

HIMA F 7133 H51q System Family 4-Fold Power Distribution Module

What is the maximum rating permitted for the integrated fuses on this module?

The module permits a maximum of 4 A slow blow miniature fuses to handle line protection across each current path.

How does the device communicate an internal line fault or a missing fuse condition?

An internal evaluation logic drives front-panel status LEDs to flash, and opens an integrated relay contact (d22/z24) if a fuse is faulty or missing.

What is the typical reaction time associated with the safety signaling relay contact?

The relay contact features an operational switching time of approximately 100 ms.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Xanh lá cây
Country of origin
Đức

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Bộ truyền động điện được thiết kế để thay thế hệ thống thủy lực: Hướng dẫn tự động hóa công nghiệp thực tiễn

Bài viết này giải thích cách các bộ truyền động điện tích hợp, như dòng e-Actuator của SMC, đang thay đổi điều khiển chuyển động công nghiệp bằng cách thay thế các hệ thống khí nén và thủy lực truyền...

Các phép toán toán học sử dụng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện các phép toán cơ bản như cộng, trừ, nhân, chia, modulo và lũy thừa trong tự động hóa công nghiệp. Nó trình bày cách các khối chức năng này...

Logic Boolean Nâng Cao với Lập Trình PLC FBD: Ứng Dụng Công Nghiệp Thực Tiễn Vượt Xa Logic Cơ Bản

Bài viết giải thích một số hàm logic Boolean nâng cao được sử dụng trong lập trình PLC ngoài các phép toán cơ bản AND, OR và NOT. Nó trình bày cách các công cụ như bảng chân trị, bộ chọn đa kênh, bộ...

Logic Boolean trong Lập trình PLC: Hiểu về Cổng Logic FBD

Logic Boolean là nền tảng của mọi chương trình PLC. Từ các điều khiển máy đơn giản đến các hệ thống tự động hóa công nghiệp phức tạp, các cổng logic quyết định cách các bộ điều khiển phản ứng với các...

Hướng Dẫn Chi Tiết Về Tường Lửa Công Nghiệp và Phân Vùng Mạng OT

Tường lửa công nghiệp đóng vai trò quan trọng trong an ninh mạng OT, bảo vệ các mạng PLC, DCS và SCADA thông qua phân đoạn, kiểm soát truy nhập/ra vào và tích hợp IDS/IPS phù hợp với các nguyên tắc...

Hướng dẫn về Càng Robot: Từ Xử lý Nhẹ Nhàng đến Tự động Hóa Công Suất Nặng

Các bộ kẹp robot hiện đại đang phát triển vượt ra ngoài các hàm cơ học truyền thống. Từ hệ thống dính lấy cảm hứng từ tắc kè, bộ kẹp mềm đạt chuẩn thực phẩm đến các công cụ kho hàng được trang bị trí...