1 trong số 1

Mitsubishi Electric FR-A840-01160-2-60 FR-A800 Variable Frequency Drive

Mitsubishi Electric FR-A840-01160-2-60 FR-A800 Variable Frequency Drive

Only 10 item(s) left in stock
  • Manufacturer: Mitsubishi Electric

  • Product No.: FR-A840-01160-2-60

  • Country of origin:Hoa Kỳ

  • Product Type: Variable Frequency Drives

  • Payment: T/T, Western Union

  • Weight: 41000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Description

Designed to meet the rigorous demands of heavy industrial motor control, the Mitsubishi Electric FR-A840-01160-2-60 is a high-performance variable frequency drive (VFD) from the flagship FR-A800 series. This 400V class inverter delivers precise control with a Super Light Duty (SLD) rated current of 116A, making it ideal for high-capacity fan, pump, and machinery installations. Engineered with a specialized varnished circuit board coating (-60 specification), it provides reliable defense against humidity and dust in demanding environments. Its IP00 open-type physical structure is optimized for integration into centralized control panels, leveraging forced air cooling to maintain thermal efficiency under continuous operation.

Features

  • Varnished Circuit Boards: Enhanced conformal coating (-60 spec) safeguards control and power electronics from atmospheric contamination without plated conductors.
  • High Current Capacity: Operates at 116A under Super Light Duty (SLD) rating, supporting demanding heavy-duty continuous operations.
  • Robust Voltage Tolerances: Designed for standard three-phase 380V to 500V AC power systems, with a reliable fluctuation tolerance of 323V to 550V AC.
  • Panel-Optimized Design: Open-type IP00 rating allows efficient, space-saving panel installations with integrated forced-air cooling.
  • High-Precision Control: Part of the advanced FR-A800 family, supporting real sensorless vector control and vector control options.

Applications

  • Industrial Ventilation Systems: High-volume fan arrays, blowers, and clean-room exhaust systems requiring continuous speed modulation.
  • Water and Wastewater Management: Centrifugal pumps, booster stations, and fluid processing plants.
  • Heavy Machinery Control: Extruders, large conveyor lines, and material handling systems requiring steady-state torque control.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number FR-A840-01160-2-60
Series FR-A800 Inverter Series
Voltage Class 400V Class
Rated Input AC Voltage Three-phase 380V to 500V AC, 50Hz/60Hz
Permissible AC Voltage Fluctuation 323V to 550V AC, 50Hz/60Hz
Permissible Frequency Fluctuation +/-5%
SLD Rated Current 116 A
Control/Structure Type Standard Model (-2 = CA Type)
Protective Structure Open Type (IP00)
Cooling Method Forced Air Cooling
Circuit Board Coating Varnished Conformal Coating (-60 specification)
Plated Conductor None
Product Weight 41 kg (90.4 lbs)
Shipping Weight (Calculated) 43 kg (94.8 lbs)

Connections and Interfaces

Terminal Block / Interface Functional Allocation
R/L1, S/L2, T/L3 Three-Phase AC Mains Power Input Terminals
U, V, W Three-Phase Variable Frequency AC Output to Motor
P/+, N/- DC Link Connection Terminals for Brake Unit or Shared DC Bus
PE Protective Earth / Chassis Ground Terminal
Control Terminals Dedicated I/O, Analog inputs (0-10V, 4-20mA), and multi-function relay outputs

Empirical Engineering Insights

Alternative Models & Compatibility

When migrating legacy systems from the FR-A700 series, the FR-A800 series provides backward parameters conversion. Parameter configurations can be imported using Mitsubishi’s FR Configurator2 software. Note that control terminal assignments are closely matched, but manual confirmation of safety-stop circuit allocations is required because of the safety standards implementation in the FR-A800 architecture.

Application Pitfalls & Engineering Notes

Because this VFD has a 41 kg weight footprint and relies on high-velocity forced air cooling, panel builders must ensure adequate airflow. Sealed enclosures require active heat exchangers or air conditioning units to handle the thermal load generated by the drive under continuous 116A SLD load conditions. Maintaining a minimum clearance of 100 mm above and below the cooling fans is necessary to prevent thermal shutdown events.

Commissioning & Wiring Tips

During initial power-up, verify that parameter 9 (electronic thermal O/L relay) matches your specific motor's nameplate data. Ensure all control-signal cables (such as 0-10V analog speed inputs) are routed in dedicated, shielded conduits distinct from high-power input/output cabling to eliminate high-frequency electromagnetic coupling.

Installation Guidelines

CRITICAL WARNING: Before commencing any installation or maintenance procedures, ensure all AC power sources feeding the R/L1, S/L2, and T/L3 terminals are physically locked out and tagged out. After power-off, wait a minimum of 10 minutes to allow the internal DC bus link capacitors to discharge completely. Verify that the voltage between terminals P/+ and N/- is 0V using a calibrated digital multimeter before handling terminals.
1

Mount the VFD vertically on a rigid, flat, heat-resistant surface inside the electrical enclosure to maximize convective air currents.

2

Connect the dedicated ground terminal (PE) directly to the system grounding plate using a low-impedance copper conductor.

3

Perform input power and motor terminal connections using calibrated torque tools, ensuring correct phase sequence on U, V, and W outputs.

What is the physical meaning of the -60 suffix on the FR-A840-01160-2-60?

The -60 suffix specifies that the control and power printed circuit boards are treated with a specialized varnished conformal coating to improve environmental robustness, while omitting plated conductors.

What is the nominal and permissible voltage range for this inverter?

The drive accepts a nominal three-phase supply of 380V to 500V AC at 50/60Hz, with a maximum allowable voltage fluctuation range of 323V to 550V AC.

Can this unit be mounted horizontally to save enclosure space?

No. The FR-A840-01160-2-60 must be mounted vertically on a flat panel surface to preserve the effectiveness of its forced-air cooling system and prevent localized heat buildup.

How long must I wait after de-energization before performing wiring maintenance?

You must wait at least 10 minutes to allow the large internal DC-link capacitors to discharge. Always measure the voltage across terminals P/+ and N/- to confirm it is below safe thresholds before starting work.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Country of origin
Hoa Kỳ

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Bộ truyền động điện được thiết kế để thay thế hệ thống thủy lực: Hướng dẫn tự động hóa công nghiệp thực tiễn

Bài viết này giải thích cách các bộ truyền động điện tích hợp, như dòng e-Actuator của SMC, đang thay đổi điều khiển chuyển động công nghiệp bằng cách thay thế các hệ thống khí nén và thủy lực truyền...

Các phép toán toán học sử dụng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện các phép toán cơ bản như cộng, trừ, nhân, chia, modulo và lũy thừa trong tự động hóa công nghiệp. Nó trình bày cách các khối chức năng này...

Logic Boolean Nâng Cao với Lập Trình PLC FBD: Ứng Dụng Công Nghiệp Thực Tiễn Vượt Xa Logic Cơ Bản

Bài viết giải thích một số hàm logic Boolean nâng cao được sử dụng trong lập trình PLC ngoài các phép toán cơ bản AND, OR và NOT. Nó trình bày cách các công cụ như bảng chân trị, bộ chọn đa kênh, bộ...

Logic Boolean trong Lập trình PLC: Hiểu về Cổng Logic FBD

Logic Boolean là nền tảng của mọi chương trình PLC. Từ các điều khiển máy đơn giản đến các hệ thống tự động hóa công nghiệp phức tạp, các cổng logic quyết định cách các bộ điều khiển phản ứng với các...

Hướng Dẫn Chi Tiết Về Tường Lửa Công Nghiệp và Phân Vùng Mạng OT

Tường lửa công nghiệp đóng vai trò quan trọng trong an ninh mạng OT, bảo vệ các mạng PLC, DCS và SCADA thông qua phân đoạn, kiểm soát truy nhập/ra vào và tích hợp IDS/IPS phù hợp với các nguyên tắc...

Hướng dẫn về Càng Robot: Từ Xử lý Nhẹ Nhàng đến Tự động Hóa Công Suất Nặng

Các bộ kẹp robot hiện đại đang phát triển vượt ra ngoài các hàm cơ học truyền thống. Từ hệ thống dính lấy cảm hứng từ tắc kè, bộ kẹp mềm đạt chuẩn thực phẩm đến các công cụ kho hàng được trang bị trí...