1 от 1

Beckhoff EL3112-0011 EtherCAT Terminal 2-Channel Analog Input Module

Beckhoff EL3112-0011 EtherCAT Terminal 2-Channel Analog Input Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL3112-0011

  • Country of origin:Германия

  • Product Type: EtherCAT Terminals

  • Payment: T/T, Western Union

  • Weight: 55g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Количество
Покажи пълните подробности

Description

Designed for high-precision industrial data acquisition, the Beckhoff EL3112-0011 is a 2-channel analog input terminal optimized for differential current measurement. This module processes bipolar signals in the range of -20 mA to +20 mA with a high-resolution performance of 16 bits (including sign). Operating directly within the modular EtherCAT terminal system, it leverages Distributed Clocks (DC) to ensure highly synchronized measurements across distributed networks with precision down to less than 1 microsecond.

Engineered for high-speed dynamic applications, the EL3112-0011 offers a standard conversion time of approximately 50 microseconds, which can be accelerated to 35 microseconds in fast mode. It features configurable analog filters (FIR/IIR) and limit value monitoring to preprocess signals directly at the I/O level, reducing communication bus load and streamlining control loop response.

Features

  • Two differential analog inputs for bipolar current measurements (-20 to +20 mA).
  • High-precision 16-bit resolution (including sign) for accurate signal reconstruction.
  • Integrated Distributed Clocks (DC) ensuring synchronization accuracy of << 1 µs.
  • Selectable digital filtering options (FIR/IIR) and limit value monitoring.
  • Fast conversion rates with a dedicated fast-mode response (~ 35 µs).
  • Galvanic isolation of 500 V between the E-bus and signal channels for enhanced noise immunity.

Applications

  • High-speed closed-loop control systems.
  • Industrial process monitoring and telemetry.
  • Test bench setups and quality control systems.
  • Power generation and distribution monitoring.

Technical Specifications

ParameterSpecification
Manufacturer Beckhoff
Part Number / Model EL3112-0011
Number of Inputs 2 (differential)
Signal Current Range -20 to +20 mA
Resolution 16 bit (including sign)
Distributed Clocks (DC) Yes (precision << 1 µs)
Internal Resistance typ. < 85 Ohm
Input Filter Limit Frequency 5 kHz
Conversion Time ~ 50 µs (Fast Mode: ~ 35 µs)
Measuring Error < ±0.3 % (relative to full scale value)
Surge Voltage Resistance 35 V DC
Electrical Isolation 500 V (E-bus / signal voltage)
Current Consumption E-bus typ. 170 mA
Bit Width in Process Image Inputs: 8 byte
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95 %, non-condensing
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Housing Material Polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Weight approx. 55 g

Installation Guidelines

  • Mounting: Mount horizontally or vertically on a standard 35 mm DIN rail conforming to EN 60715 using the integrated locking mechanism.
  • Wiring: Use solid, flexible, or ferruled conductors. Connection relies on a tool-actuated tension clamp connection. Wire strip length must be between 8 mm and 9 mm.
  • Power & Grounding: Ensure the E-bus connections are clean and aligned during side-by-side terminal mounting. Implement proper shielding for differential analog signals to prevent electro-magnetic interference.

Compliance and Certifications

  • CE
  • UL
  • ATEX: II 3 G Ex nA IIC T4 Gc

What is the primary function of the Beckhoff EL3112-0011 terminal?

The EL3112-0011 is a 2-channel differential analog input terminal designed to measure current signals in the range of -20 mA to +20 mA with a 16-bit resolution.

Does this module support Distributed Clocks?

Yes, it supports Distributed Clocks (DC) with synchronization precision of less than 1 microsecond, making it ideal for highly synchronized applications.

What are the standard and fast-mode conversion times?

The standard conversion time is approximately 50 microseconds, while the fast-mode conversion time is approximately 35 microseconds.

What hazardous area classifications does the EL3112-0011 hold?

It is ATEX certified with the marking II 3 G Ex nA IIC T4 Gc for safe deployment in Zone 2 hazardous environments.

Глобална експресна доставка

  • Стандартна доставка: 4-6 работни дни чрез DHL, FedEx и UPS.
  • Експресна изпращане: Изпращане в същия ден за налични поръчки, направени преди 14:00 ч. (GMT+8).
  • Глобално покритие: Обслужваме над 150 държави, включително бърза доставка до Саудитска Арабия и ОАЕ.

Връщания и гаранция

  • 30-дневна гаранция: Връщания се приемат за налични продукти в оригинална, фабрично запечатана опаковка.
  • 12-месечна гаранция: Всеки индустриален компонент е подкрепен с нашата професионална техническа гаранция.

Поръчките се обработват и доставят от понеделник до петък (с изключение на официалните празници).


За пълна информация относно допустимост, такси за презареждане и международни връщания, моля, разгледайте нашия официален Политика за възстановяване и връщане .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Наскоро разгледани продукти

Технически знания

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...