1 от 4

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Only 2 item(s) left in stock
  • Manufacturer: Emerson

  • Product No.: KJ3002X1-BG2

  • Country of origin:Съединени щати

  • Product Type: Input Card

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 200g

  • Dimensions: 8.1cm x 7.9cm x 8.8cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Количество
Покажи пълните подробности

Description

The Emerson KJ3002X1-BG2 is a Thermocouple, mV Card developed for the DeltaV scalable process system. This interface component enables the direct conversion of low-level analog millivolt signals from temperature sensors and standard voltage sources into structured digital data for process automation loops. Operating on local bus infrastructures, the KJ3002X1-BG2 interfaces field temperature variables with central system controllers across diverse hazardous industrial plant architectures.

Features

  • Integrates a dedicated rotary keying mechanical mechanism to guarantee hardware alignment between interface units and field terminal blocks.
  • Features integrated diagnostic capability and electrical isolation design tailored for low-amplitude sensor signal routing.
  • Contains internal electrical path tracing optimized for direct field thermocouple and millivolt sensor hookups without external conversion hardware.

Applications

  • High-temperature process furnaces and process vessel monitoring.
  • Thermal monitoring infrastructures in industrial processing environments.
  • Continuous temperature multi-channel data acquisition within distributed control topologies.

Technical Specifications

Parameter Specification
Manufacturer Emerson Process Management
Manufacturing Origin Austin, Texas
Part Number D803060X012 (12P1731X082)
LocalBus Power Rating 12 VDC at 350 mA
Field Circuit Rating 5.5 VDC at 0.6 mA/channel
Terminal Block Key Position B2
Ambient Temperature Limit 0 to 60 degC
Relative Humidity Bounds 5 to 95% Non-Condensing
Enclosure Rating IP 20
Operational Shock Resistance 10g half Sinewave for 11 msec
Operational Vibration Limit 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz
Environmental Gaseous Protection ISA-S71.04-1985 Airborne Contaminants Class G3

Connections/Interfaces

Mechanical Alignment Component Assignment Function
Terminal Block Key Position B2 Ensures hardware compatibility between the I/O card and the specific field terminal block

Installation Guidelines

  • Field Power Disconnection: All field power supplied to the device, either at the field terminal or as bussed field power through the carrier, must be completely removed before disconnecting or removing the unit.
  • Energized Maintenance Conditions: This unit may be removed or inserted while system power is energized under the following conditions: Only one unit at a time may be removed with system power energized. It must be used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power.
  • Inductance Limitations: The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance) must be utilized.
  • Fuse Handling: A terminal block fuse may NOT be removed with field power energized for non-sparking circuits.
  • Hardware Adjustments: This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.

Compliance and Certifications

  • ATEX Certification Number | Nemko No. 02ATEX431U |
  • ATEX Code | II 3 G EEx nL IIC T4 |
  • FM Approval | Class I Division 2 Groups A, B, C, D Hazardous Locations, Temperature Rating T4 |
  • CSA Certification | LR87534 |
  • CE Mark | Certified |

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Can this device be hot-swapped while the system is powered?

Yes, a single unit may be removed or inserted while system power is energized, provided it is used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power, and the primary circuit wiring inductance is less than 23 uH.

What are the requirements for handling terminal block fuses?

A terminal block fuse must not be removed while field power is energized for non-sparking circuits.

Does the device require regular maintenance or calibration?

No, the device contains no user serviceable parts, must not be disassembled, and does not require calibration.

Глобална експресна доставка

  • Стандартна доставка: 4-6 работни дни чрез DHL, FedEx и UPS.
  • Експресна изпращане: Изпращане в същия ден за налични поръчки, направени преди 14:00 ч. (GMT+8).
  • Глобално покритие: Обслужваме над 150 държави, включително бърза доставка до Саудитска Арабия и ОАЕ.

Връщания и гаранция

  • 30-дневна гаранция: Връщания се приемат за налични продукти в оригинална, фабрично запечатана опаковка.
  • 12-месечна гаранция: Всеки индустриален компонент е подкрепен с нашата професионална техническа гаранция.

Поръчките се обработват и доставят от понеделник до петък (с изключение на официалните празници).


За пълна информация относно допустимост, такси за презареждане и международни връщания, моля, разгледайте нашия официален Политика за възстановяване и връщане .

TECHNICAL SPECIFICATIONS

Color pattern
Черно
Country of origin
Съединени щати
Power source
Постоянен ток

Наскоро разгледани продукти

Технически знания

Електрически задвижващи механизми, проектирани да заменят хидравлични и пневматични системи: Практическо ръководство за индустриална автоматизация

Тази статия обяснява как интегрираните електрически задвижвания, като серията e-Actuator на SMC, трансформират индустриалното управление на движението, като заменят традиционните пневматични и...

Математически операции с OpenPLC за индустриални автоматизационни приложения

Тази статия обяснява как PLC системите изпълняват основни математически операции като събиране, изваждане, умножение, деление, модуло и степенуване в индустриалната автоматизация. Показва как тези...

Разширена булева логика с FBD PLC програмиране: Практически индустриални приложения отвъд основната логика

Статията обяснява няколко усъвършенствани булеви логически функции, използвани в програмирането на PLC, извън основните операции AND, OR и NOT. Тя разглежда как инструменти като таблици на...

Булева логика в програмирането на PLC: Разбиране на логическите врати в FBD

Булевата логика е основата на всяка програма за PLC. От прости машинни управления до сложни индустриални автоматизационни системи, логическите врати определят как контролерите реагират на променящите...

Подробно ръководство за индустриални защитни стени и сегментиране на OT мрежи

Индустриалните защитни стени играят ключова роля в киберсигурността на OT, като защитават мрежите PLC, DCS и SCADA чрез сегментация, контрол на входящия/изходящия трафик и интеграция на IDS/IPS в...

Ръководство за роботизирани захвати: от деликатно боравене до тежка автоматизация

Съвременните роботизирани захвати се развиват отвъд традиционните механични челюсти. От системи с лепкави повърхности, вдъхновени от геконите, и меки захвати за хранителни продукти до инструменти за...