1 от 1

Mitsubishi Electric FR-E840-0300-4-60 FR-E800 Variable Frequency Drive

Mitsubishi Electric FR-E840-0300-4-60 FR-E800 Variable Frequency Drive

Only 10 item(s) left in stock
  • Manufacturer: Mitsubishi Electric

  • Product No.: FR-E840-0300-4-60

  • Country of origin:Съединени щати

  • Product Type: Variable Frequency Drives

  • Payment: T/T, Western Union

  • Weight: 4900g

  • Shipping port: Xiamen

  • Warranty: 12 months

Количество
Покажи пълните подробности

Description

Engineered to deliver highly reliable speed and torque regulation for three-phase induction and permanent magnet motors, the Mitsubishi Electric FR-E840-0300-4-60 is a high-performance 400V class variable frequency drive from the robust FR-E800 family. This specific configuration features a rated normal duty (ND) current of 30.0 A, utilizing source logic for safety and input control configurations. To ensure durability in harsh industrial manufacturing environments, this unit is supplied with conformal board coating (-60 designation), safeguarding critical control circuits from airborne contaminants, moisture, and conductive dust.

Key Features

  • Conformal PCB Coating: Manufactured with protective circuit board coating to comply with demanding atmospheric conditions.
  • Optimized Input Configuration: Configured for 400 V class three-phase input systems with an initial base frequency setting of 50 Hz.
  • Source Logic Interface: Standard safety stop and digital input configurations utilize source logic wiring protocols.
  • Analog Monitoring: Includes terminal AM voltage analog output for precise real-time operational feedback.
  • Advanced Thermal Design: Forced-air cooling system engineered for optimal heat dissipation within compact electrical enclosures.

Applications

  • Automated material handling and conveyor line control systems.
  • Industrial pump networks and local fluid distribution systems.
  • HVAC ventilation, heavy-duty industrial fan systems, and blowers.
  • Packaging, wrapping, and secondary assembly machinery.

Technical Specifications

Specification Parameter Value / Rating
Manufacturer Mitsubishi Electric
Model Number FR-E840-0300-4-60
Product Series FR-E800 Series
Voltage Class 400 V Class (Three-Phase Input)
Rated ND Current 30.0 A
Initial Base Frequency 50 Hz
Control Logic Type Source Logic
Circuit Board Coating With Conformal Coating
Plated Conductor Without Plating
Safety Circuitry Source Logic (Fixed), STO Capable
Monitoring Terminal Voltage Output (Terminal AM)
Net Weight 4.9 kg
Shipping Weight (Calculated) 7.0 kg

Connections and Interfaces

Terminal Block Terminal Label Function / Circuit Assignment
Main Power Circuits R/L1, S/L2, T/L3 Three-phase AC power input connections
U, V, W Three-phase AC output connections to motor
Control & Monitoring AM Analog voltage monitoring (0 to 10 VDC)
PC External 24 VDC power supply common (Source logic reference)
S1, S2, SIC Safety stop signal inputs (Source logic configuration)

Empirical Engineering Insights

Alternative Models & Compatibility: The FR-E840-0300-4-60 acts as a modern replacement for legacy FR-E740 series configurations. When upgrading, engineers must account for minor physical housing adjustments and use FR Configurator2 software to systematically convert the parameter map, particularly verifying that safety circuit wiring is transitioned to match the fixed source safety logic of the E800 series.

Application Pitfalls & Engineering Notes: Although the conformal coating on this model (indicated by the -60 suffix) provides increased protection against chemical gases and dust ingress, the drive unit must still be mounted vertically within a clean air environment or sealed NEMA 12/IP54 enclosure if high-density metallic dust is present. Avoid installing the drive horizontally, as this disrupts the convective heat flow and reduces the cooling capacity of the onboard fans.

Commissioning & Wiring Tips: Ensure control signaling cables are run through dedicated, grounded steel conduits separate from the main motor output lines. Always wire the analog AM monitoring terminal using shielded twisted-pair (STP) cabling to eliminate high-frequency electromagnetic interference (EMI) from the drive's internal IGBT switching actions.

Installation Guidelines

CRITICAL WARNING: Hazardous voltages persist on power terminals even after line-side power is removed. De-energize all primary input sources and wait a minimum of 10 minutes for internal DC bus capacitors to discharge safely below 50 VDC. Always verify zero voltage state with an engineered digital multimeter before touching power circuitry.
1
Mechanical Mounting: Fasten the VFD vertically to a flat, non-combustible rear panel using appropriate M5 mounting screws. Ensure a minimum of 50 mm space above and below the cooling duct path.
2
Earth Grounding: Establish a low-impedance ground connection directly to the main system PE bus. Do not daisy-chain ground terminals across adjacent drives.
3
Power Terminals: Wire the main AC lines to R/L1, S/L2, and T/L3, and connect the corresponding motor phases to U, V, and W. Ensure all wire terminations are torqued to manufacturer specifications.
4
Control Logic Inspection: Verify the external control loops match the source logic configuration, connecting terminal PC as the digital common reference.

What is the purpose of the -60 suffix in this product code?

The -60 suffix denotes that the printed circuit boards have an industrial conformal coating applied for enhanced environmental defense against humidity and corrosive gas, and are manufactured without plated conductors.

Is this drive configured for Sink or Source logic?

This model is configured for Source control logic as its initial factory setting for both control inputs and fixed safety stop circuits.

What safety rating does the STO functionality provide?

The integrated Safe Torque Off (STO) safety inputs comply with SIL 3 / PL e standards when wired in a redundant circuit design.

What is the rated normal duty (ND) current of this model?

This drive has a rated normal duty (ND) output current of 30.0 Amps, suitable for 400V class operations.

Глобална експресна доставка

  • Стандартна доставка: 4-6 работни дни чрез DHL, FedEx и UPS.
  • Експресна изпращане: Изпращане в същия ден за налични поръчки, направени преди 14:00 ч. (GMT+8).
  • Глобално покритие: Обслужваме над 150 държави, включително бърза доставка до Саудитска Арабия и ОАЕ.

Връщания и гаранция

  • 30-дневна гаранция: Връщания се приемат за налични продукти в оригинална, фабрично запечатана опаковка.
  • 12-месечна гаранция: Всеки индустриален компонент е подкрепен с нашата професионална техническа гаранция.

Поръчките се обработват и доставят от понеделник до петък (с изключение на официалните празници).


За пълна информация относно допустимост, такси за презареждане и международни връщания, моля, разгледайте нашия официален Политика за възстановяване и връщане .

TECHNICAL SPECIFICATIONS

Country of origin
Съединени щати

Наскоро разгледани продукти

Технически знания

Електрически задвижващи механизми, проектирани да заменят хидравлични и пневматични системи: Практическо ръководство за индустриална автоматизация

Тази статия обяснява как интегрираните електрически задвижвания, като серията e-Actuator на SMC, трансформират индустриалното управление на движението, като заменят традиционните пневматични и...

Математически операции с OpenPLC за индустриални автоматизационни приложения

Тази статия обяснява как PLC системите изпълняват основни математически операции като събиране, изваждане, умножение, деление, модуло и степенуване в индустриалната автоматизация. Показва как тези...

Разширена булева логика с FBD PLC програмиране: Практически индустриални приложения отвъд основната логика

Статията обяснява няколко усъвършенствани булеви логически функции, използвани в програмирането на PLC, извън основните операции AND, OR и NOT. Тя разглежда как инструменти като таблици на...

Булева логика в програмирането на PLC: Разбиране на логическите врати в FBD

Булевата логика е основата на всяка програма за PLC. От прости машинни управления до сложни индустриални автоматизационни системи, логическите врати определят как контролерите реагират на променящите...

Подробно ръководство за индустриални защитни стени и сегментиране на OT мрежи

Индустриалните защитни стени играят ключова роля в киберсигурността на OT, като защитават мрежите PLC, DCS и SCADA чрез сегментация, контрол на входящия/изходящия трафик и интеграция на IDS/IPS в...

Ръководство за роботизирани захвати: от деликатно боравене до тежка автоматизация

Съвременните роботизирани захвати се развиват отвъд традиционните механични челюсти. От системи с лепкави повърхности, вдъхновени от геконите, и меки захвати за хранителни продукти до инструменти за...