Managing complex industrial machinery requires high-density control, which the Mitsubishi Electric FX3U-80MT/ES-A delivers as a high-speed, expandable base controller within the MELSEC FX3U family. Engineered with 40 integrated 24 VDC inputs (configurable as either sink or source) and 40 high-speed transistor outputs (source-type), this unit provides 80 local I/O points out of the box. By utilizing local extension blocks and decentralized network architectures, the system can scale up to 384 I/O points. Featuring a fast execution speed of 0.065 microseconds per basic instruction and a massive 64,000-step EEPROM program memory, this unit handles complex arithmetic, positioning, and high-frequency pulse-train applications without performance bottlenecks.

Key Features

  • High-Speed Processing: Executes basic commands in 0.065 microseconds, enabling responsive closed-loop control.
  • Dual-Logic Inputs: 40 digital inputs support both sink (NPN) and source (PNP) configurations via a dedicated S/S terminal.
  • High-Frequency Pulse Outputs: 3 integrated pulse outputs (Y000, Y001, Y002) supporting up to 100 kHz for precise multi-axis positioning.
  • Expandable Architecture: Built-in bus connection supports left-side adapter boards (ADP) and right-side expansion modules.
  • Integrated Real-Time Clock: Synchronizes system events, maintenance logs, and scheduling commands natively.

Applications

  • Multi-Axis Packaging Machinery: Accurate positioning of servo/stepper motors via high-speed transistor pulse outputs.
  • Conveyor and Sorting Systems: High-density local I/O for sensor arrays and pneumatic actuator banks.
  • Environmental Control Systems: Integration with analog modules for temperature, humidity, and pressure regulation in mechanical rooms.
  • Automated Assembly Lines: Fieldbus communication interface for distributed pneumatic valve terminals and operator panels.

Technical Specifications

Parameter Value / Specification
Manufacturer Mitsubishi Electric
Model Number FX3U-80MT/ES-A
Supply Voltage 100 to 240 VAC (+10% / -15%), 50/60 Hz
Power Consumption 50 VA
Integrated Digital Inputs 40 points (24 VDC, 5-7 mA, sink/source configurable)
Integrated Digital Outputs 40 points (Transistor, source logic)
Output Switching Capacity 5 to 30 VDC, maximum 0.5 A per point (0.8 A per common terminal)
Program Memory 64,000 steps EEPROM (built-in)
Instruction Execution Speed 0.065 microseconds (basic instructions)
High-Speed Counters Up to 8 channels (single-phase 100 kHz, dual-phase up to 50 kHz)
Integrated Pulse Outputs 3 channels (Y000, Y001, Y002) up to 100 kHz
Programming Environment GX Works2 / GX Developer
Operating Temperature 0 to 55 degC (storage: -25 to 75 degC)
Dimensions (W x H x D) 285 mm x 90 mm x 86 mm
Net Weight 1.2 kg
Shipping Weight (Calculated) 1.5 kg
Country of Origin Japan

Connections and Interfaces

Terminal / Port Functional Assignment & Description
L / N AC Power Input (100 to 240 VAC, 50/60 Hz, screw terminal block)
24V / 0V Auxiliary Service Power Supply output (24 VDC, 500 mA maximum)
S/S Sink / Source selector terminal for standard input points (X000 to X047)
+V0 to +V3 External Power Supply connection for transistor output groups (Source configuration)
Y000 - Y002 High-speed transistor outputs dedicated for pulse train emission (up to 100 kHz)
RS-422 Port Integrated 8-pin Mini-DIN connector for programming and HMI communication

Empirical Engineering Insights

Alternative Models & Compatibility

When migrating legacy systems from the FX2N series, the FX3U-80MT/ES-A serves as a direct upgrade path. It has a matching mounting footprint but offers double the instruction execution speed and vastly expanded memory capacity. Ensure your development software is upgraded to GX Works2 (v1.08J or higher) to configure and program the extended features of this CPU. If replacing an older FX2N-80MT-D, verify your input wiring logic because the ES-A suffix defaults to a flexible S/S input circuit and source-type outputs, whereas legacy "-D" models were sink-only.

Application Pitfalls & Engineering Notes

The integrated 24 VDC service power output (maximum 500 mA) is often overloaded when powering multiple inductive proximity sensors or high-current HMI units. Ensure any auxiliary sensor loads are routed to an external 24 VDC switched-mode power supply, linking the 0V reference lines to stabilize the common signal plane. Additionally, when switching high-frequency inductive loads with the transistor outputs, verify that flyback suppression diodes are mounted across the load to prevent premature transistor degradation.

Commissioning & Wiring Tips

To configure the FX3U-80MT/ES-A for PNP (Source) inputs, connect the S/S terminal to the 0V terminal of the service power supply. For NPN (Sink) input logic, jump the S/S terminal to the 24V terminal. When utilizing the high-speed pulse outputs (Y000-Y002) for servo drive indexing, always use shielded twisted-pair cabling for the pulse and direction lines and ground the shield at a single point to mitigate electromagnetic interference.

Installation Guidelines

CRITICAL WARNING: Ensure that the incoming AC supply voltage is completely de-energized before mounting, wiring, or removing any terminal blocks. Wait a minimum of 5 minutes post-power-down to allow internal bus capacitors to fully discharge before handling internal circuitry or extension blocks.
  1. 1 Mount the PLC on a standard 35mm symmetrical DIN rail or secure it to a flat cabinet backplate using standard M4 screws. Always maintain a 50mm clearance on all sides of the housing to guarantee natural convection airflow.
  2. 2 Connect the protective earth (PE) terminal to the cabinet's main ground bar using a low-impedance copper wire of at least 2.0 mm² to prevent high-frequency noise interference.
  3. 3 Wire the 100-240 VAC power input using M3 terminal ring crimps, ensuring the phase line is fused externally with a slow-blow 2A fuse.
  4. 4 After completing all physical point-to-point wiring checks, secure the protective plastic terminal covers before energizing the electrical panel.

What is the difference between ES-A and DS versions of this controller?

The ES-A suffix indicates a 100-240 VAC main power supply, 24 VDC inputs, and transistor source (PNP) outputs. The DS suffix indicates a 24 VDC main power supply with transistor source outputs.

Can this unit be programmed using modern GX Works3 software?

Yes. While it is native to GX Works2 and GX Developer, you can program and configure FX3U series hardware in GX Works3 using its integrated backward compatibility environment.

Does the FX3U-80MT/ES-A support analog signals directly out of the box?

No. The base unit includes digital I/O only. Analog inputs or outputs require adding FX3U-ADP adapter boards to the left or FX2N/FX3U expansion blocks to the right.

How do you switch the digital inputs between NPN and PNP configurations?

By changing the S/S terminal reference wire. Connect S/S to the internal 24V terminal for NPN (sink) logic, or connect S/S to 0V for PNP (source) logic.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Modernizace HMI Bailey INFI 90 Symphony běžících na OpenVMS Alpha

Praktický průvodce výměnou zastaralých operátorských stanic Bailey Symphony běžících na OpenVMS Alpha. Porovnává emulaci Alpha, migraci OpenVMS na x86, přemostění OPC a postupnou modernizaci ABB.

Proč jsou údaje o údržbě nezbytné pro průmyslovou spolehlivost

Údaje o údržbě propojují pracovní příkazy, signály ze senzorů, historii majetku, náklady a znalosti techniků. Správné využití těchto dat zlepšuje plánování, spolehlivost, prediktivní údržbu, kontrolu...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...