ABB REB670 Relion 670 Series Busbar Protection Intelligent Electronic Device

ABB REB670 Relion 670 Series Busbar Protection Intelligent Electronic Device

Nur noch 5 Artikel auf Lager verfügbar
  • Hersteller: ABB

  • Produkt-Nr.: REB670

  • Herkunftsland:Schweden

  • Produkttyp: Busbar Protection IED

  • Strichcode: 85371091

  • Zahlung: T/T, Western Union

  • Gewicht: 12000g

  • Abmessungen: 242 mm x 266 mm x 449 mm (D x H x W)

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

ABB REB670 is a busbar protection intelligent electronic device (IED) designed for the protection, control, and monitoring of busbars, T-connections, and meshed corners from medium to extra high voltage levels. This busbar protection IED provides selective, reliable, and fast fault clearance for all types of internal phase-to-phase and phase-to-earth faults in solidly earthed or low-impedance earthed power systems. It is also capable of handling internal multi-phase faults in isolated or high-impedance earthed power systems. Belonging to the Relion protection and control product family, the ABB REB670 implements the core design requirements of the IEC 61850 standard to deliver fully interoperable and future-proof substation automation applications.

Features

  • Extensive input/output capability supporting single, double, and triple busbar layouts with or without transfer bus arrangements.
  • Phase segregated measurement providing selective protection for complex substation layouts.
  • Integrated software-based dynamic Zone Selection for seamless adaptation to shifting substation topologies, such as one-and-a-half breaker stations, double breaker stations, and ring busbars.
  • Integrated check zone feature independent of disconnector positions to secure differential protection stability during improper status indications.
  • Efficient merging of differential zones during load-transfer conditions initiated by bus-sectionalizing disconnectors.
  • Built-in open CT detection and differential protection supervision to prevent unwanted operations during secondary circuit failures.
  • Advanced backup protection capabilities, including breaker failure protection, end fault protection, and overcurrent protection options.
  • Extensive protocol support covering IEC 61850-8-1, IEC 61850-9-2LE process bus, IEC 60870-5-103, DNP3.0, LON, and SPA protocols.

Applications

  • Single, double, and triple busbar configurations with or without transfer bus, double-circuit breaker, or one-and-a-half circuit breaker arrangements.
  • Substations requiring up to six differential zones and twenty-four analog current inputs.
  • High-voltage and extra-high-voltage utility and industrial substations utilizing isolated, high-impedance, low-impedance, or solidly earthed power networks.
  • Complex substation layouts utilizing dynamic zone selection, requiring large counts of binary and analog inputs/outputs.
  • Process-bus environments operating with sampled values according to the IEC 61850-9-2LE standard.

Ordering Information

Pre-configured Variant Phase Configuration Maximum Bay Capacity Differential Zones
REB670-A20 3-Phase 4 Bays 2 Zones
REB670-A31 3-Phase 8 Bays 2 Zones
REB670-B20 1-Phase 12 Bays 2 Zones
REB670-B21 1-Phase 12 Bays (Extendable to 24 CT inputs) 2 Zones
REB670-B31 1-Phase 24 Bays 2 Zones

Technical Specifications

Parameter Specification / Value
Manufacturer ABB / Hitachi Energy 
Product Version 2.2 
Rated Frequency 50 Hz / 60 Hz 
Operating Slope (Two-zone / Six-zone) Fixed at 53% 
Operating Slope (Four-zone) User settable among [0.53, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85] 
Max Binary Inputs Up to 176 channels simultaneously activated 
Max Relay Outputs Up to 96 channels (Maximum 72 outputs simultaneously activated within nominal range) 
Auxiliary DC Supply Voltage 24-60 V DC ± 20%, 90-250 V DC ± 20% 
Voltage Ripple Influence Max 2% (Operative range), Full wave rectified 15% of EL 
DC Interruption Ride-Through 0-50 ms without restart 
Ambient Temperature (Operate Range) -25 degC to +55 degC 
Relative Humidity (Operative Range) 10-90% 
Transformer Input Combinations 12 inputs per galvanic separation module (Ring lug or compression type) 

Installation Guidelines

  • Grounding: Secure the IED case to the station earth using a low-impedance copper wire before making any electrical connections.
  • Shielding: Employ twisted-pair shielded cables for all binary signal lines and communication networks to reduce the effects of EMI/RFI noise.
  • Mounting: Install the unit into standard 19-inch racks or panel cutouts using the certified ABB mounting kit accessories.
  • Cooling and Ventilation: Maintain adequate clearance around the top and bottom of the enclosure to promote natural convection and prevent heat accumulation.
  • Cable Routing: Maintain clean separation between heavy-current primary cables, analog secondary transformer connections, and low-voltage digital signal wiring.
  • Polarity: Verify correctness of all auxiliary DC voltage wiring connections before energizing the IED power supply module.

Compliance and Certifications

  • Council of the European Communities Directive on Electromagnetic Compatibility (EMC Directive 2004/108/EC) 
  • Low-Voltage Directive (2006/95/EC) 
  • Product Standard EN 60255-26 (EMC requirements) 
  • Product Standards EN 60255-1 and EN 60255-27 (Low voltage requirements) 
  • International Standards of the IEC 60255 series
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

ABB REB670 Relion 670 Series Busbar Protection Intelligent Electronic Device

What is the recommended operating temperature range for the device?

The recommended nominal ambient temperature range for operation is from -25 degC to +55 degC.

What auxiliary DC supply options are available for the device?

The device accommodates two auxiliary DC voltage ranges: 24-60 V DC and 90-250 V DC.

How many differential zones can the device support?

The device supports up to six differential protection zones depending on the selected configuration layout.

Which communication protocols are natively supported by the device?

The device supports communication via IEC 61850-8-1, IEC 61850-9-2LE, IEC 60870-5-103, DNP3.0, LON, and SPA protocols.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails sehen Sie bitte unsere offiziellen Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Schweden

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe zur Ablösung von Fluidkraftsystemen: Ein praktischer Leitfaden für die industrielle Automatisierung

Dieser Artikel erklärt, wie integrierte elektrische Antriebe, wie die e-Actuator-Serie von SMC, die industrielle Bewegungssteuerung revolutionieren, indem sie herkömmliche pneumatische und...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere fortgeschrittene Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Backen hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...