1 von 1

BECKHOFF IP2041-B510 Fieldbus Box 8-Channel Digital Output Module

BECKHOFF IP2041-B510 Fieldbus Box 8-Channel Digital Output Module

Nur noch 10 Artikel auf Lager verfügbar
  • Hersteller: BECKHOFF

  • Produkt-Nr.: IP2041-B510

  • Herkunftsland:Deutschland

  • Produkttyp: Fieldbus Boxes

  • Zahlung: T/T, Western Union

  • Gewicht: 2000g

  • Abmessungen: 30 mm x 175 mm x 26.5 mm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

Designed to handle demanding decentralized control environments, the IP2041-B510 accommodates eight digital outputs in a robust, space-saving Fieldbus Box form factor. This distributed I/O module interfaces directly with a CANopen network, enabling high-speed transmission of binary control signals from a master controller to actuators, lamps, or solenoids. Its IP67-rated enclosure ensures reliable operations without requiring a protective control cabinet, making it ideal for field-level industrial automation. The module supports a maximum output current of 2 A per channel, with integrated short-circuit protection to maintain system reliability and prevent damage to field cabling.

Features

  • Features eight independent digital outputs supporting ohmic, inductive, and lamp loads.
  • Integrated CANopen fieldbus interface with automatic baud rate detection ranging from 10 kbaud up to 1 Mbaud.
  • Provides individual short-circuit protection on each channel with a typical short-circuit current limit of 4 A.
  • Configurable via the KS2000 software tool or directly via controller Service Data Objects (SDO).
  • Compact and rugged polyamide PA6 housing designed for cabinet-free installation.
  • Enhanced network diagnostics including Node Guarding, Life Guarding, Emergency Objects, and Variable Mapping.

Applications

  • Automotive assembly and body-in-white production lines
  • Material handling systems and decentralized conveyor lines
  • Packaging machinery and automated bottling lines
  • Water and wastewater processing facilities
  • General manufacturing and heavy industry distributed control

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model IP2041-B510
Product Series Fieldbus Box (IPxxxx-B51x series)
Number of Outputs 8 digital outputs
Output Connections M8, screw-type
Nominal Output Voltage 24 V DC (-15 % / +20 %)
Max. Output Current 2 A per channel (total current max. 12 A; sum of ch 0-3: 4 A, ch 4-5: 4 A, ch 6-7: 4 A)
Fieldbus Protocol CANopen
Bus Interface 1 x M12 plug, 5-pin
Data Transfer Rates 10 kbaud to 1 Mbaud (automatic detection)
I/O Communication Types Event-driven, cyclic, synchronous, polling
Electrical Isolation Control voltage/fieldbus: 500 V
Box Supply Current 45 mA + sensor current consumption (max. 0.5 A)
Power Supply Connection Feed: 2 x M8 male socket, 4-pin (no downstream connection)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
Housing Material PA6 (polyamide)
Dimensions (W x H x D) 30 mm x 175 mm x 26.5 mm
Shipping Weight 2.0 kg

Connections and Interfaces

Interface Type Connector Style Function
Fieldbus Connection 1 x M12 plug, 5-pin CANopen network connection
Digital Outputs (0 to 7) 8 x M8 female sockets Actuator and load connections
Power Supply Input 2 x M8 male sockets, 4-pin 24 V DC control and load voltage feed

Installation Guidelines

  • Mount the module directly onto a flat machine frame or mounting plate using two fixing holes with a 3.5 mm diameter suitable for M3 screws.
  • Ensure that all unused M8 and M12 sockets are sealed with protective screw caps to maintain the specified IP67 protection rating.
  • Route power supply and network cables separately from high-voltage motor or drive cabling to avoid electromagnetic interference.
  • Ensure correct common ground references between the fieldbus box control voltage and the CANopen network ground.

Compliance and Certifications

  • CE
  • UL
  • RoHS Compliant
Loading product navigation…

What is the maximum output current limit for the IP2041-B510 module?

The module supports up to 2 A per channel, with a maximum total output current limit of 12 A for the entire unit. The channels are divided into sum-current groups of 4 A max (channels 0-3, channels 4-5, and channels 6-7).

Can this module be mounted in wet or dusty industrial environments?

Yes, the IP2041-B510 is built with a rugged polyamide PA6 housing featuring an IP65, IP66, and IP67 rating (when all connections are properly sealed), making it resistant to dust and water exposure without requiring an enclosure.

How does the IP2041-B510 handle network configuration?

The module can be configured using the Beckhoff KS2000 software tool or via Service Data Objects (SDOs) direct from the CANopen network controller.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails sehen Sie bitte unsere offiziellen Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe zur Ablösung von Fluidkraftsystemen: Ein praktischer Leitfaden für die industrielle Automatisierung

Dieser Artikel erklärt, wie integrierte elektrische Antriebe, wie die e-Actuator-Serie von SMC, die industrielle Bewegungssteuerung revolutionieren, indem sie herkömmliche pneumatische und...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere fortgeschrittene Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Backen hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...