1 von 3

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Nur noch 2 Artikel auf Lager verfügbar
  • Hersteller: Emerson

  • Produkt-Nr.: KJ3002X1-BG2

  • Herkunftsland:Vereinigte Staaten

  • Produkttyp: Input Card

  • Strichcode: 8537101190

  • Zahlung: T/T, Western Union

  • Gewicht: 200g

  • Abmessungen: 8.1cm x 7.9cm x 8.8cm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

The Emerson KJ3002X1-BG2 is a Thermocouple, mV Card developed for the DeltaV scalable process system. This interface component enables the direct conversion of low-level analog millivolt signals from temperature sensors and standard voltage sources into structured digital data for process automation loops. Operating on local bus infrastructures, the KJ3002X1-BG2 interfaces field temperature variables with central system controllers across diverse hazardous industrial plant architectures.

Features

  • Integrates a dedicated rotary keying mechanical mechanism to guarantee hardware alignment between interface units and field terminal blocks.
  • Features integrated diagnostic capability and electrical isolation design tailored for low-amplitude sensor signal routing.
  • Contains internal electrical path tracing optimized for direct field thermocouple and millivolt sensor hookups without external conversion hardware.

Applications

  • High-temperature process furnaces and process vessel monitoring.
  • Thermal monitoring infrastructures in industrial processing environments.
  • Continuous temperature multi-channel data acquisition within distributed control topologies.

Technical Specifications

Parameter Specification
Manufacturer Emerson Process Management
Manufacturing Origin Austin, Texas
Part Number D803060X012
LocalBus Power Rating 12 VDC at 350 mA
Field Circuit Rating 5.5 VDC at 0.6 mA/channel
Terminal Block Key Position B2
Ambient Temperature Limit 0 to 60 degC
Relative Humidity Bounds 5 to 95% Non-Condensing
Enclosure Rating IP 20
Operational Shock Resistance 10g half Sinewave for 11 msec
Operational Vibration Limit 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz
Environmental Gaseous Protection ISA-S71.04-1985 Airborne Contaminants Class G3

Connections/Interfaces

Mechanical Alignment Component Assignment Function
Terminal Block Key Position B2 Ensures hardware compatibility between the I/O card and the specific field terminal block

Installation Guidelines

  • Field Power Disconnection: All field power supplied to the device, either at the field terminal or as bussed field power through the carrier, must be completely removed before disconnecting or removing the unit.
  • Energized Maintenance Conditions: This unit may be removed or inserted while system power is energized under the following conditions: Only one unit at a time may be removed with system power energized. It must be used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power.
  • Inductance Limitations: The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance) must be utilized.
  • Fuse Handling: A terminal block fuse may NOT be removed with field power energized for non-sparking circuits.
  • Hardware Adjustments: This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.

Compliance and Certifications

  • ATEX Certification Number | Nemko No. 02ATEX431U |
  • ATEX Code | II 3 G EEx nL IIC T4 |
  • FM Approval | Class I Division 2 Groups A, B, C, D Hazardous Locations, Temperature Rating T4 |
  • CSA Certification | LR87534 |
  • CE Mark | Certified |
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Emerson KJ3002X1-BG2 Thermocouple mV Input Card

Can this device be hot-swapped while the system is powered?

Yes, a single unit may be removed or inserted while system power is energized, provided it is used with a KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power, and the primary circuit wiring inductance is less than 23 uH.

What are the requirements for handling terminal block fuses?

A terminal block fuse must not be removed while field power is energized for non-sparking circuits.

Does the device require regular maintenance or calibration?

No, the device contains no user serviceable parts, must not be disassembled, and does not require calibration.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage via DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir bedienen über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails, sehen Sie bitte unsere offizielle Seite ein Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Color pattern
Schwarz
Country of origin
Vereinigte Staaten
Power source
Gleichstromversorgung

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe als Ersatz für Flüssigkeiten: Praktisches Tutorial

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung