Endress+Hauser RN221N-B1 Active Barrier

Endress+Hauser RN221N-B1 Active Barrier

Nur noch 356 Artikel auf Lager verfügbar
  • Hersteller: Endress+Hauser

  • Produkt-Nr.: RN221N-B1

  • Herkunftsland:Deutschland

  • Produkttyp: Active Barrier

  • Zahlung: T/T, Western Union

  • Gewicht: 499g

  • Abmessungen: 22.5 mm x 110 mm x 112 mm (W x H x D)

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

The Endress+Hauser RN221N-B1 is an active barrier with an integrated transmitter power supply designed for the safe separation of 4 to 20 mA current signal circuits. This device provides galvanic isolation between the input and output circuits, making it ideal for removing large loop circuits and powering 2-wire transmitters in process control environments. Equipped with an intrinsically safe input option for hazardous locations, it supports bi-directional HART communication to transmit status information and sensor configurations smoothly from the field to control instrumentation. The Endress+Hauser RN221N-B1 features a compact 22.5 mm housing suited for standard top hat DIN rail mounting, ensuring efficient use of cabinet space across various industrial automation systems.

Features

  • Provides reliable galvanic isolation for 4 to 20 mA current signaling paths.
  • Integrates a built-in loop power supply to energize field-mounted 2-wire transmitters.
  • Supports bi-directional HART communication transmission and includes front-mounted communication sockets.
  • Housed in a space-saving 22.5 mm wide enclosure designed for side-by-side installations.

Applications

  • Galvanic isolation and loop separation of 4 to 20 mA field circuits.
  • Intrinsically safe power distribution to transmitters situated in Ex-areas.
  • Industrial process liquid monitoring, flow, pressure, and temperature registration architectures.

Ordering Information

Order Code Product Structure / Component
RN221N-B1 Active barrier RN221N, transmitter power supply, 4-20mA, 1:1 transmission, bi-directional HART communication, SIL2, housing 22.5mm, top hat DIN rail 35mm, IP20. Approval: ATEX II (1)GD (EEx ia) IIC. Power supply; diagnosis: 20-250 VDC/AC; none.

Optional Accessories

Order Code Accessory
51002468 Protective housing IP66 for field mounting 
51004148 Adhesive label, printed (max. 2x16 chars) 
51002393 Metal tag for tag number 

Technical Specifications

Specification Value
Manufacturer Endress+Hauser 
Number of Inputs
Input Supply Voltage 16.7 V +/- 0.2 V (for I = 20 mA) 
Open Circuit Voltage (Input) 26 V +/- 5% 
Short Circuit Current (Input) <= 40 mA 
Internal Resistance (Input) 328 Ohm 
Overrange (Input/Output) 10% 
Number of Outputs
Open Circuit Voltage (Output) 24 V +/- 10% 
Load (Impedance) 10 to 700 Ohm (without communication resistance) 
Galvanic Isolation To all other current circuits 
Supply Voltage 20 to 250 V DC/AC, 50/60 Hz 
Power Consumption Max. 2.5 W (without HART diagnosis) 
Electrical Safety To IEC 61010-1, protection class I, overvoltage category II, pollution degree 2, overload protection <= 10 A, fuse 315 mA T 
Linearity <= 0.15% 
Load Influence <= 0.1% 
Ambient Temperature Influence <= 0.1% in range 0 degC to 50 degC; <= 0.2%/10K in range -20 degC to 0 degC 
Ambient Temperature Limits -20 to +50 degC (-4 to 122 F) 
Storage Temperature -20 to +70 degC (-4 to 158 F) 
Operating Height To IEC 61010-1: < 2000 m (6561 ft) above sea level 
Climate Class To IEC 60654-1 Class B2 
Degree of Protection IP 20 
Electromagnetic Compatibility (EMC) Immunity to IEC 61326, Class A (Industrial environment) 
Weight Approx. 150 g (1.1 lb) 
Housing Material Plastic PC/ABS, UL 940 
Terminals Keyed plug-on screw terminals, core size 2.5 mm2 solid, or strands with ferrules 

Installation Guidelines

  • Mount the device on a top hat DIN rail according to IEC 60715 TH35.
  • There are no restrictions regarding the installation angle, allowing flexible positioning inside control enclosures.
  • Select a vibration-free installation point and implement measures to protect the housing from external heating sources.
  • Keep all terminal connections secure, utilizing the keyed plug-on screw design with up to 2.5 mm2 core size solid wires or strands with ferrules.

Compliance and Certifications

  • ATEX: II (1)GD (EEx ia) IIC 
  • Functional Safety: SIL2 / FMEDA according to IEC 61508/IEC 61511
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Endress+Hauser RN221N-B1 Active Barrier

What is the primary function of the active barrier?

The active barrier provides safe galvanic isolation for 4 to 20 mA current signal circuits and powers 2-wire transmitters.

What are the allowed power supply parameters for this device?

The device accepts a wide-range supply voltage of 20 to 250 V DC or AC at 50/60 Hz.

Does this model include HART diagnostic evaluation elements?

No, the specific configuration of this model does not include the optional HART diagnosis or its associated error behavior settings.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage via DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir bedienen über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails, sehen Sie bitte unsere offizielle Seite ein Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe zur Ablösung von Fluidkraftsystemen: Ein praktischer Leitfaden für die industrielle Automatisierung

Dieser Artikel erklärt, wie integrierte elektrische Antriebe, wie die e-Actuator-Serie von SMC, die industrielle Bewegungssteuerung revolutionieren, indem sie herkömmliche pneumatische und...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie SPS-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...