GE Vernova 750-P5-G5-D5-HI-A1-R Multilin 750 Feeder Management Relay

GE Vernova 750-P5-G5-D5-HI-A1-R Multilin 750 Feeder Management Relay

Nur noch 2 Artikel auf Lager verfügbar
  • Hersteller: General Electric

  • Produkt-Nr.: 750-P5-G5-D5-HI-A1-R

  • Herkunftsland:Vereinigte Staaten

  • Produkttyp: Feeder Management Relay

  • Strichcode: 8537101190

  • Zahlung: T/T, Western Union

  • Gewicht: 8500g

  • Abmessungen: 220 mm x 275 mm x 300 mm (W x H x D)

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

GE Vernova Multilin 750 Feeder Management Relay is a digital system intended for the comprehensive management, primary protection, and control of distribution feeders. Designed without automatic recloser functionality to distinguish it from the 760 series, this relay provides robust backup protection for buses, transformers, and transmission lines within a convenient draw-out construction. Equipped with full metering capabilities and analog input/output options, it ensures high asset visibility and integrates into monitoring and control infrastructures.

Description

The GE Multilin 750-P5-G5-D5-HI-A1-R is an industrialized protection system tailored for distribution feeders on solidly grounded, high-impedance grounded, or resonant grounded networks. The unit features dedicated 5 A phase current inputs, 5 A zero-sequence ground current inputs, and 5 A sensitive ground current inputs to accommodate specific fault detection profiles. Operating under a wide high-voltage control power range, the relay incorporates an independent analog output channel alongside a front-panel red breaker closed LED indicator. By utilizing standard industrial protocols and options for serial and Ethernet physical layers, the Multilin 750 executes fast fault processing, interlocking, and status reporting to optimize substation automation and protect upstream transformers and distribution buses.

Features

  • Complete protection suite containing phase, neutral, ground, and negative sequence instantaneous and time overcurrent elements.
  • Comprehensive ground protection capabilities via 5 A sensitive ground current inputs paired with neutral and ground overcurrent diagnostics.
  • High-voltage universal power supply options supporting both AC and DC industrial stations.
  • Dedicated analog output channel configurable for remote PLC or SCADA tracking.
  • Standard front panel red LED indicator for distinct local breaker closed status confirmation.
  • Draw-out construction type enabling quick chassis maintenance and minimized replacement downtime.
  • Built-in diagnostic testing system featuring simulation modes to preview fault, pre-fault, and post-fault characteristics.

Applications

  • Primary protection and control for distribution feeders on solidly grounded, high-impedance grounded, or resonant (Peterson Coil) systems.
  • Bus blocking and interlocking protection coordination schemes.
  • High-speed fault detection for arc flash mitigation.
  • Voltage and frequency element-based automatic load shedding schemes.
  • Backup protection for transmission lines, feeders, distribution buses, and power transformers.

Ordering Information

Selection Code Description
750 Base Model: Feeder Management Relay (Without Autoreclose)
P5 Phase Current Inputs: 5 A secondary
G5 Ground Current Inputs: 5 A zero sequence
D5 Sensitive Ground Current Inputs: 5 A sensitive ground
HI Power Supply: 88 to 300 VDC, 70 to 265 VAC @ 48 to 62 Hz
A1 Analog Outputs: Eight 0 to 1 mA analog outputs*
R Breaker Status LED: Red breaker closed LED

* Note: Based on standard engineering documentation, the A1 suffix provides 0 to 1 mA outputs, while alternative options like A20 provide 4 to 20 mA configurations. The overall hardware accommodates scalable transducer signaling for standard industrial loops.

Technical Specifications

Parameter Specification
Manufacturer GE Vernova
Base Series 750 Series Feeder Management Relay
Phase Current Input (P5) 5 A current transformer (CT) secondary input
Zero Sequence Current Input (G5) 5 A zero sequence current input
Sensitive Ground Current Input (D5) 5 A sensitive ground current input
Control Power Supply Options (HI) 88 to 300 VDC, or 70 to 265 VAC @ 48 to 62 Hz
Analog Outputs (A1) Eight 0 to 1 mA analog outputs
Breaker Status LED (R) Red breaker closed LED
Phase/Neutral/Ground TOC Pickup Level 0.05 to 20.00 x CT in steps of 0.01
Sensitive Ground TOC Pickup Level 0.005 to 1.000 x CT in steps of 0.001
TOC Curve Shapes ANSI Extremely/Very/Moderately/Normally Inverse; Definite Time; IEC Curve A/B/C and Short; FlexCurve A/B; IAC Extreme/Very/Inverse/Short
IOC Delay Accuracy 0 to +20 ms (at non-zero time delay)
Frequency Range 16 to 65 Hz
Frequency Accuracy ±0.02 Hz
Current Metering Accuracy ±0.5% of full scale
Voltage Metering Accuracy 0.25% of full scale

 

Installation Guidelines

  • Mounting: Ensure proper panel mounting alignment matching standard draw-out dimensions. Keep clearance optimized for ventilation.
  • Grounding: Establish a dedicated low-impedance ground connection at the chassis ground terminal before making any current transformer or control power connections.
  • CT Wiring: Verify secure insertion into the automatic shorting terminals. Phase, ground, and sensitive ground inputs must match the specified 5 A primary or secondary CT ratios to prevent overcurrent saturation or measurement inaccuracies.
  • Control Power Protection: Route lines through an external fuse or circuit breaker matching the HI voltage limits (88 to 300 VDC or 70 to 265 VAC) to avoid power circuit component failure.
  • Shielding: Ground the communication line shields at the PLC or computer side only to prevent ground loop interference.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

GE Vernova 750-P5-G5-D5-HI-A1-R Multilin 750 Feeder Management Relay

What is the primary difference between the 750 and 760 series relays?

The 750 series serves as a feeder management relay without automatic recloser functionality, whereas the 760 series includes a built-in 4-shot recloser mechanism.

What power ranges are supported by the HI control supply designation?

The HI option supports a high-voltage input range of 88 to 300 VDC or 70 to 265 VAC at frequencies between 48 and 62 Hz.

Are the sensitive ground current terminals rated for standard 1 A inputs?

No, the D5 technical designation in this model configures the sensitive ground current channel exclusively for a 5 A secondary current transformer input.

Can the analog output channel be connected directly to a PLC network?

Yes, the integrated analog output channels provide standardized transducer signaling suitable for transmission to automated PLC or supervisory SCADA platforms.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails sehen Sie bitte unsere offiziellen Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Color pattern
Schwarz
Country of origin
Vereinigte Staaten
Power source
Gleichstromversorgung

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe zur Ablösung von Fluidkraftsystemen: Ein praktischer Leitfaden für die industrielle Automatisierung

Dieser Artikel erklärt, wie integrierte elektrische Antriebe, wie die e-Actuator-Serie von SMC, die industrielle Bewegungssteuerung revolutionieren, indem sie herkömmliche pneumatische und...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere fortgeschrittene Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Backen hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...