1 von 1

Weidmuller 8965360000 ACT20X-HDI-SDO-S Isolating Switch Amplifier

Weidmuller 8965360000 ACT20X-HDI-SDO-S Isolating Switch Amplifier

Nur noch 10 Artikel auf Lager verfügbar
  • Hersteller: Weidmuller

  • Produkt-Nr.: 8965360000

  • Herkunftsland:Deutschland

  • Produkttyp: Isolating Switch Amplifiers

  • Zahlung: T/T, Western Union

  • Gewicht: 1200g

  • Abmessungen: 117.2 mm x 22.5 mm x 113.6 mm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Anzahl
Vollständige Details anzeigen

Processing digital signals from hazardous areas requires robust galvanic isolation, which the Weidmuller 8965360000 ACT20X-HDI-SDO-S delivers as a high-performance, 2-channel isolating switch amplifier. This device safely transmits switching states from NAMUR sensors or mechanical contacts located in Zone 0, 1, or 2 hazardous areas to the safe area control system, providing complete electrical separation and signal conditioning in a compact form factor.

Key Features

  • Dual-channel intrinsically safe input for NAMUR sensors or dry mechanical contacts.
  • Galvanic 4-way isolation between input, output, power supply, and status output.
  • Integrated line fault detection (LFD) for continuous wire-break and short-circuit monitoring.
  • FDT/DTM software-configurable parameters for custom application tuning and diagnostics.
  • Relay outputs (1 changeover contact per channel) for robust load switching.
  • Compact 22.5 mm DIN-rail housing to optimize cabinet space.

Applications

  • Intrinsically safe signal isolation in chemical and petrochemical processing plants.
  • Oil and gas pipeline monitoring systems requiring Zone 0/1 sensor deployment.
  • Water and wastewater treatment facility telemetry and pump control.
  • Hazardous area valve position feedback and limit switch integration.

Technical Specifications

Parameter Value
Manufacturer Weidmuller
Article Number 8965360000
Model ACT20X-HDI-SDO-S
Number of Channels 2
Input Type NAMUR sensor (DIN EN 60947-5-6) or mechanical switch
Output Type Relay (1 changeover contact per channel)
Nominal Switching Voltage 250 V AC / 30 V DC
Supply Voltage 19.2 to 31.2 V DC
Power Consumption <= 1.1 W
Isolation Voltage 2.6 kV AC (input / output / power)
Connection Technology Screw connection
Clamping Range 0.5 to 2.5 mm2
Flammability Rating UL 94 V-0
Protection Degree IP20
Operating Temperature -20 to +60 degC
Dimensions (H x W x D) 117.2 mm x 22.5 mm x 113.6 mm
Net Weight 0.170 kg

Connections and Interfaces

Terminal Pin Function / Circuit Assignment
11 / 12 Channel 1 Input (NAMUR Sensor / Mechanical Switch)
21 / 22 Channel 2 Input (NAMUR Sensor / Mechanical Switch)
51 / 52 / 53 Channel 1 Relay Output (NC / COM / NO)
61 / 62 / 63 Channel 2 Relay Output (NC / COM / NO)
91 / 92 Power Supply (19.2 to 31.2 V DC: + / -)

Alternative Models & Compatibility

The ACT20X-HDI-SDO-S is part of Weidmuller's premium ACT20X signal converter family. It serves as a direct replacement or upgrade path for legacy ACT20 series modules. When migrating from older systems, verify that your configuration files are updated in the FDT/DTM frame to match the specific firmware revision of the 8965360000 module.

Application Pitfalls & Engineering Notes

When utilizing standard mechanical switches instead of NAMUR sensors, the Line Fault Detection (LFD) circuit must be configured correctly. If LFD is enabled without external resistors, the module will interpret an open switch as a wire break and a closed switch as a short circuit. To prevent false diagnostics, either disable LFD via the DTM software or wire a resistor network (typically 1k Ohm in series and 10k Ohm in parallel) directly at the switch contacts.

Commissioning & Wiring Tips

Configuration is performed using the Weidmuller WI-Manager software via the front-panel service jack. Ensure the CBX200 USB interface cable is used for connection. For field wiring, maintain a minimum physical separation of 50 mm between the intrinsically safe (Ex i) blue terminals on the left side and the non-intrinsically safe terminals on the right side to comply with international hazardous area installation standards.

Installation Guidelines

CRITICAL WARNING

De-energize all power sources before mounting, wiring, or configuring the device. Failure to isolate power can result in electrical shock or spark generation in hazardous areas, compromising explosion protection safety.

1
Snap the module vertically onto a standard TS 35 DIN rail, ensuring the metal grounding spring on the back makes secure contact with the rail.
2
Connect the intrinsically safe field sensors to the blue terminals (11/12 and 21/22), ensuring proper cable routing away from power lines.
3
Wire the relay outputs and the 24 V DC power supply to the black terminals on the opposite side of the module.
4
Connect the configuration interface to set the desired input/output logic and LFD parameters using the FDT/DTM software before commissioning.
Loading product navigation…

How do I configure the Line Fault Detection (LFD) for a standard mechanical switch?

To use LFD with a mechanical switch, you must wire an external resistor network at the switch contacts: a 1k Ohm resistor in series and a 10k Ohm resistor in parallel. Alternatively, you can disable LFD entirely using the Weidmuller FDT/DTM software.

What software is required to configure the ACT20X-HDI-SDO-S?

Configuration requires the Weidmuller WI-Manager software (FDT frame) along with the device-specific ACT20X DTM package and a CBX200 USB interface cable.

Can this isolating amplifier be installed directly in Zone 0?

No, the module itself must be installed in a safe area or Zone 2 (inside a suitable protective enclosure). However, its input circuits are certified intrinsically safe for direct connection to devices located in Zone 0, 1, or 2.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...

Programmierung von Ein-Achsen-Bewegungszyklen auf einem CMZ-Servoantrieb

Dieses Tutorial untersucht, wie die integrierte SPS-Funktionalität in einem CMZ SBD-Servoantrieb eigenständige Bewegungsprogramme ausführen kann, einschließlich Referenzfahrt-Logik,...