1 از 6

ABB CI867K01 3BSE043660R1 System 800xA Modbus TCP Interface

ABB CI867K01 3BSE043660R1 System 800xA Modbus TCP Interface

فقط 5 قلم(های) کالا در انبار باقی مانده است
  • تولیدکننده: ABB

  • شماره محصول: 3BSE043660R1

  • کشور سازنده:سوئد

  • نوع محصول: Modbus TCP Interface Modules

  • بارکد: 85389091

  • پرداخت: حواله بانکی (T/T)، وسترن یونیون

  • وزن: 500g

  • ابعاد: 127.5 x 186 x 59 mm

  • بندر حمل و نقل: شیامن

  • گارانتی: ۱۲ ماه

تعداد
مشاهده جزئیات کامل

Description

Facilitating seamless Ethernet-based industrial communications, the ABB CI867K01 3BSE043660R1 acts as a high-performance Modbus TCP interface kit within the System 800xA and AC 800M controller architecture. This communication package includes the CI867 communication module and the TP867 baseplate, enabling direct connectivity to field instruments, third-party PLCs, and SCADA control networks. Engineered for high-speed industrial telemetry, it functions natively as both a Modbus TCP Master and Slave, ensuring flexible and reliable data exchanges across modern automated systems.

Key Features

  • Dual-channel RJ45 Ethernet interfaces supporting 10/100 Mbps transmission speeds.
  • Includes the rugged TP867 baseplate for stable backplane mounting and reliable shielding.
  • Comprehensive protocol handling for Modbus TCP Master and Slave configurations.
  • Full integration with ABB Control Builder M configuration software.
  • Hot-swappable communication hardware for maximum system availability and reduced downtime.

Industrial Applications

  • Integration of intelligent electronic devices (IEDs) and power meters into central control networks.
  • Inter-controller communications between ABB AC 800M assemblies and third-party PLC architectures.
  • Distributed SCADA telemetry in water treatment, chemical processing, and power generation plants.

Technical Specifications

Manufacturer ABB
Model Number CI867K01
Product ID / SKU 3BSE043660R1
Module Type Modbus TCP Communication Interface
Physical Composition CI867 Module & TP867 Baseplate Assembly
Ethernet Ports 2x RJ45 (Ch1, Ch2)
Transmission Rate 10/100 Mbps (Auto-negotiation)
Connection Limit Up to 120 simultaneous TCP connections
Customs Tariff Number 85176200
Country of Origin Sweden
Net Weight 0.7 kg
Shipping Weight (Calculated) 0.95 kg
Dimensions (D x H x W) 127.5 x 186 x 59 mm

Connections and Interfaces

Interface Terminal Interface Type Functional Assignment
Ch1 RJ45 Connector Primary Ethernet Connection (Modbus TCP Network)
Ch2 RJ45 Connector Secondary Ethernet Connection / Network Redundancy Path
Backplane Connector TP867 Baseplate Interconnect 24 V DC Power Input and Internal System Bus Communication

Empirical Engineering Insights

Alternative Models & Compatibility

The CI867K01 package directly succeeds older Modbus solutions within System 800xA. It requires Control IT firmware version 5.1 or higher loaded onto the PM8xx controller for correct interface addressing. If you are retrofitting older systems using Control Software version 5.0 or earlier, firmware upgrades or compatibility configuration patches are mandatory to ensure that the AC 800M controller recognizes the dual-channel capability of the TP867 baseplate assembly.

Application Pitfalls & Engineering Notes

To prevent communication module lockups, avoid overloading the 120-connection threshold. When configuring master devices, group individual Modbus polling requests into unified, block-read transactions instead of continuous, discrete register queries. This minimizes packet rates and protects the module's microprocessor from thermal overhead inside enclosed unventilated panels.

Commissioning & Wiring Tips

Always use Shielded Twisted Pair (STP) Cat5e or Cat6 cabling to prevent Electromagnetic Interference (EMI) in high-voltage switchgear environments. Ground the cable shields strictly at the industrial patch panel end rather than the TP867 baseplate to suppress potential ground loops. Confirm that the default network routing tables in Control Builder match the physical local network gateway to bypass ARP resolution failure.

Installation Guidelines

CRITICAL WARNING:

De-energize all AC 800M backplane power lines and external communication devices prior to installing or removing the TP867 baseplate. Static discharge and raw voltage spikes can cause irreversible hardware damage to the communication bus components.

1

Mount the TP867 baseplate onto the grounded standard horizontal DIN rail until the plastic locking tab clicks firmly into place.

2

Align the slide connectors of the adjacent communication or CPU modules to bridge the backplane connection path.

3

Carefully insert the CI867 interface module into the slot of the TP867 baseplate, exerting even pressure until it sits flush.

4

Connect the shielded RJ45 cables to Port Ch1 and/or Ch2, route the cabling through the designated panel ducting, and power on the system for commissioning.

Loading product navigation…

Can the CI867K01 be configured as both a Modbus TCP Master and Slave simultaneously?

Yes, the CI867K01 module supports concurrent Modbus TCP Master and Slave operational modes across its independent Ethernet ports, configured via Control Builder M.

What is the maximum number of Ethernet connections supported by the CI867 communication interface?

The module supports up to 120 simultaneous TCP connections, which must be allocated properly between Master and Slave configurations to prevent transaction drops.

Does the CI867K01 communication module support hot-swapping (Hot Configuration in Run)?

Yes, when mounted on the TP867 baseplate within an active AC 800M system, the CI867 interface can be replaced under power without shutting down the controller.

ارسال سریع جهانی

  • تحویل استاندارد: ۴-۶ روز کاری از طریق DHL، FedEx و UPS.
  • ارسال فوری: ارسال همان روز برای سفارش‌های موجود در انبار که قبل از ساعت ۲:۰۰ بعدازظهر (GMT+8) ثبت شده‌اند.
  • پوشش جهانی: خدمات به بیش از ۱۵۰ کشور، شامل تحویل سریع به عربستان سعودی و امارات.

بازگشت کالا و گارانتی

  • ضمانت ۳۰ روزه: بازگشت کالا برای محصولات موجود در انبار با بسته‌بندی اصلی و مهر کارخانه پذیرفته می‌شود.
  • گارانتی ۱۲ ماهه: هر قطعه صنعتی با گارانتی فنی حرفه‌ای ما پشتیبانی می‌شود.

سفارش‌ها از دوشنبه تا جمعه (به جز تعطیلات رسمی) پردازش و تحویل داده می‌شوند.


برای شرایط کامل واجد شرایط بودن، هزینه‌های بازگردانی و جزئیات بازگشت بین‌المللی، لطفاً صفحه رسمی ما را مشاهده کنید سیاست بازپرداخت و بازگشت کالا .

TECHNICAL SPECIFICATIONS

Country of origin
سوئد

محصولات مشاهده‌شده اخیر

دانش فنی

منطق بولی پیشرفته با برنامه‌نویسی FBD PLC: کاربردهای عملی صنعتی فراتر از منطق پایه

این مقاله چندین تابع پیشرفته منطق بولی را که در برنامه‌نویسی PLC فراتر از عملیات پایه AND، OR و NOT استفاده می‌شوند، توضیح می‌دهد. همچنین نحوه استفاده از ابزارهایی مانند جداول صحت، مالتی‌پلکسرها،...

منطق بولی در برنامه‌نویسی PLC: درک گیت‌های منطقی FBD

منطق بولی پایه و اساس هر برنامه PLC است. از کنترل‌های ساده ماشین تا سیستم‌های پیچیده اتوماسیون صنعتی، دروازه‌های منطقی تعیین می‌کنند که کنترل‌کننده‌ها چگونه به ورودی‌ها و شرایط عملیاتی متغیر پاسخ...

راهنمای جامع فایروال‌های صنعتی و تقسیم‌بندی شبکه OT

فایروال‌های صنعتی نقش حیاتی در امنیت سایبری OT ایفا می‌کنند و از شبکه‌های PLC، DCS و SCADA از طریق بخش‌بندی، کنترل ورود/خروج و ادغام IDS/IPS مطابق با اصول IEC 62443 محافظت می‌کنند.

راهنمای گیره‌های رباتیک: از جابجایی ظریف تا اتوماسیون سنگین

گیره‌های رباتیک مدرن فراتر از فک‌های مکانیکی سنتی در حال پیشرفت هستند. از سیستم‌های چسبنده الهام‌گرفته از گکوی، گیره‌های نرم با درجه‌بندی غذایی تا ابزارهای انبار مجهز به هوش مصنوعی، فناوری‌های...

بازگشت به گذشته: چگونه موتورهای الکتریکی اولیه معدن‌کاری زیرزمینی را تغییر دادند

از کمپرسورهای جریان مستقیم با نیروی طناب تا واگن‌های معدنی باتری‌دار، عملیات‌های اولیه معدن‌کاری نقطه عطفی در برق‌رسانی صنعتی بودند. این مقاله بررسی می‌کند که چگونه موتورهای الکتریکی پیش از ورود...

Factory I/O: یک ابزار شبیه‌سازی PLC مدرن برای آموزش اتوماسیون صنعتی

Factory I/O آموزش PLC را با ارائه شبیه‌سازی‌های صنعتی سه‌بعدی فراگیر برای دانشجویان، مهندسان و تیم‌های نگهداری متحول می‌کند. این پلتفرم فاصله بین نظریه و عمل واقعی اتوماسیون را پر می‌کند و در عین حال...