The Beckhoff KM2614 is a high-power, 4-channel relay output terminal from the K-bus series, specifically engineered for direct load switching in building automation and heavy industrial applications. Unlike standard signal relays, the KM2614 features change-over (SPDT) contacts capable of handling 16 A at 250 V AC. A standout feature of this module is the integrated manual/automatic override switch on each relay, allowing maintenance personnel to manually toggle outputs during system testing or commissioning without needing to engage the PLC software.
The KM2614 combines high switching capacity with the flexibility of manual control, making it an essential tool for local machine overrides.
| Feature | Specification |
| Model | KM2614 |
| Channels | 4 x Change-over (SPDT) |
| Max. Current | 16 A AC / 12 A DC |
| Rated Voltage | 250 V AC / 30 V DC |
| Operating Modes | Manual / Automatic |
| Isolation | 1.5 kV (K-bus / field) |
| Dimensions | 99 x 100 x 62 mm |
| Protection Rating | IP20 |
What are the primary applications for the manual/automatic switch?
The manual override is primarily used during system commissioning and maintenance. It allows an operator to manually test a lighting zone or a motor contactor while the PLC is off-line or under service. It is also an essential safety fallback for testing if a communication error is suspected in the fieldbus network.
Can I switch inductive loads like motors with this terminal?
Yes, but you must respect the current de-rating for inductive loads. While the relay handles 16 A for ohmic loads, ensure your inductive load's surge/inrush current does not exceed the relay’s contact capability. For large motors, this terminal should be used to control the coil of an external, larger contactor.
How does the PLC know if the relay is in manual mode?
The KM2614 is a standard output terminal. The PLC will continue to send its commanded state to the module. If an operator switches a relay to "Manual," the relay will ignore the PLC's signal. It is a best practice to monitor the state of the system via feedback sensors if verifying that a manual override has occurred is critical to your safety logic.