Honeywell 05701-A-0327 System 57 Double SPCO Relay Card
The Honeywell 05701-A-0327 is a plug-in interface and control loop module designed for the System 57 / 5701 Series Control System. This hardware module functions primarily as an electrical bridge providing connections between field-mounted industrial gas sensors and their designated Single Channel Control Cards. By decoupling the continuous gas display and processor logic from physical field wiring, the card secures high loop integrity across individual monitoring nodes.
In addition to routing standard sensor signaling paths, the module features single-pole change-over (SPCO) electromechanical relays that provide voltage-free contact outputs to drive external alarm indicators or protective shutdown systems. These integrated relay contacts are permanently or field-configured to monitor specific hazard indices, continuously operating across discrete thresholds for the A1 alarm level, A2 alarm level, and local fault condition paths. The physical layout is optimized for high-density DIN-rail rack assemblies with a dual-chamber separation design providing native attenuation of localized electromagnetic anomalies.
| Parameter | Specifications |
|---|---|
| Manufacturer | Honeywell |
| Model Number | 05701-A-0327 |
| Product Type | Double SPCO Relay Card |
| Product Series | System 57 / 5701 Series Control System |
| Contact Architecture | Single Pole Change-Over (SPCO) |
| Relay Signal Paths | A1 Alarm, A2 Alarm, Fault Condition |
| Max AC Relay Fusing | 5A maximum (when switching mains AC voltages) |
| Height | 112mm |
| Width | 25mm |
| Depth | 102mm |
| Shipping Weight | 2 Kg |
| Connector Pin | Function |
|---|---|
| TB1 - PSU (+) | Main External 24V DC Power Supply Unit Positive Termination Input |
| TB1 - PSU (-) | Main External 24V DC Power Supply Unit Negative Common Reference |
| TB1 - AUX (+) | Standby Backup Battery Storage Power Supply Positive Termination Input |
| TB1 - AUX (-) | Standby Backup Battery Storage Power Supply Negative Common Reference |
| TB1 - GND | Low-Impedance Dedicated Instrumentation Clean Earth Shield Connection |
| User Terminal Reference | Connector Pin / Function |
|---|---|
| Ground | 26 / Shield Ground Path |
| Sensor S Connection | 25 / Sensor Supply line |
| Sensor NS Connection | 27 / Non-Sink / Signal return line |
| Sensor 01 Connection | 28 / Sensor 0V reference line |
| Analogue O/P (+) | 29 / Isolated Current Loop Output Positive |
| Analogue O/P (-) | 32 / Isolated Current Loop Output Negative |
| Remote Inhibit In | 31 / External Channel Inhibit Signal |
| Remote Reset In | 34 / External Alarm Reset Command Line |
| +24V (Out/In) | 33 / System 24V DC auxiliary line |
| 0V (Out/In) | 36 / System 0V DC auxiliary common |
| Fault NC | 1 / Fault Relay Normally Closed Terminal |
| Fault NO | 2 / Fault Relay Normally Open Terminal |
| Fault COM | 3 / Fault Relay Common Path |
| A1(1) NC | 7 / A1 Alarm Normally Closed Contact |
| A1(1) NO | 8 / A1 Alarm Normally Open Contact |
| A1(1) COM | 9 / A1 Alarm Common Path |
| A2(1) NC | 11 / A2 Alarm Normally Closed Contact |
| A2(1) NO | 12 / A2 Alarm Normally Open Contact |
| A2(1) COM | 10 / A2 Alarm Common Path |
| User Terminal Reference | Connector Pin / Function |
|---|---|
| 0V (Out/In) | 36 / System 0V DC auxiliary common |
| +24V (Out/In) | 35 / System 24V DC auxiliary line |
| Remote Reset In | 34 / External Alarm Reset Command Line |
| Remote Inhibit In | 33 / External Channel Inhibit Signal |
| Analogue O/P (-) | 32 / Isolated Current Loop Output Negative |
| Analogue O/P (+) | 31 / Isolated Current Loop Output Positive |
| Sensor 01 Connection | 30 / Sensor 0V reference line |
| Sensor NS Connection | 29 / Non-Sink / Signal return line |
| Ground | 28 / Shield Ground Path |
| Sensor S Connection | 27 / Sensor Supply line |
| Ground | 26 / Alternative Shield Ground Terminal |
| Ground | 25 / Alternative Shield Ground Terminal |
| Fault NC | 1 / Fault Relay Normally Closed Terminal |
| Fault NO | 2 / Fault Relay Normally Open Terminal |
| Fault COM | 3 / Fault Relay Common Path |
| A1(1) NC | 5 / A1 Alarm Normally Closed Contact |
| A1(1) NO | 8 / A1 Alarm Normally Open Contact |
| A1(1) COM | 9 / A1 Alarm Common Path |
| A2(1) NC | 11 / A2 Alarm Normally Closed Contact |
| A2(1) NO | 12 / A2 Alarm Normally Open Contact |
| A2(1) COM | 10 / A2 Alarm Common Path |
How are the contact orientations of the A1 and A2 alarm relays defined?
The documented terminal descriptions for normally closed (NC) and normally open (NO) states match the completely de-energized, unpowered condition of the control module.
What is the default operation mode of the onboard FAULT relay circuit?
The FAULT relay is hardwired for normally energized operation during normal, non-fault plant conditions, ensuring that a total drop in control loop power triggers a fail-safe system alarm state.
Can the alarm relay actuation modes be altered to fit normally energized logic?
Yes, the A1 and A2 alarm relays can be individually reconfigured for normally energized or normally de-energised operation by executing setup updates via the central Engineering Interface Software.
Does this interface module accept thicker high-current industrial wires?
The mechanical compression terminals populated on the interface card assembly are rated to accept single-stranded or multi-stranded instrumentation cables up to a maximum cross-sectional area of 2.5mm2.