The 060L315666 (060L315666) is a heavy-duty KPS 80 series temperature switch designed by Danfoss for demanding industrial and marine applications. Featuring a robust adsorption charge sensing system, this controller operates within a 70 to 120 deg C range, providing reliable thermostat functionality in engine rooms, power plants, and chemical processing facilities. The 060L315666 is engineered to withstand high vibration and harsh environmental conditions, utilizing a 3000 mm armored capillary tube to allow for flexible sensor placement while protecting the internal hydraulic circuit. By employing high-quality SPDT gold-plated contacts, this unit ensures fail-safe switching for both high-power loads and low-voltage PLC signals, significantly enhancing system safety and preventing thermal runaway in critical machinery.

Technical Configuration

The KPS 80 series is distinguished by its mechanical durability and precision adjustment capabilities, specifically configured for industrial endurance:

  • Sensing Element: Utilizes an adsorption charge principle, which offers high resistance to ambient temperature fluctuations and ensures the setpoint remains stable even when the housing is exposed to varying conditions.

  • Armored Capillary: Features a 3000 mm (118 1/8 in) armored capillary tube, providing mechanical protection against abrasion, kinking, and impact in heavy-duty industrial settings.

  • Switching Mechanism: Equipped with an SPDT (Single Pole Double Throw) contact system with gold plating, making it compatible with low-current electronics (1-30 mA) as well as standard AC motor loads up to 440 V.

  • Enclosure and Entry: Housed in a rugged enclosure with a Pg 13.5 metal cable gland and screwed cable entry, ensuring a secure and vibration-proof electrical connection.

  • Differential Control: Features an adjustable differential type, allowing engineers to fine-tune the "cut-in" and "cut-out" points to prevent rapid cycling of connected equipment.

Technical Specifications

Feature Specification
Model 060L315666
Brand Danfoss
Series KPS 80
Temperature Range 70 to 120 deg C
Capillary Length 3000 mm (Armored)
Sensor Connection M 18 x 1.5
Contact Type SPDT Gold
Max Ambient Temp 70 deg C (Short-term 80 deg C for 120 min)
Contact Rating (AC1) 10 A, 440 V
Contact Rating (DC13) 12 W, 220 V
Electrical Entry Pg 13.5 Metal Gland
Net Weight Approx. 1.2 kg
Shipping Weight 2.5 kg

Technical FAQs

What is the advantage of the "Adsorption Charge" in the 060L315666?

The adsorption charge allows the sensor bulb to be placed in environments either warmer or colder than the switch housing without affecting the accuracy of the setpoint. This makes it superior to vapor charge sensors in applications where the ambient temperature near the controller housing varies significantly.

Can I use this temperature control for low-voltage PLC inputs?

Yes. The 060L315666 features gold-plated contacts designed for reliable switching at low voltages (5-30 V) and low currents (1-30 mA). This prevents oxide buildup on the contacts, which is a common cause of signal failure in standard silver contacts used with PLCs.

How do I adjust the temperature differential?

The differential is adjusted via the internal setting disk. By increasing the differential, you increase the gap between the temperature at which the switch activates and the temperature at which it resets, which is essential for protecting motors and compressors from frequent starting and stopping.


Engineering & Installation Guide

  • Capillary Management: When installing the 3000 mm armored capillary, ensure the bend radius never drops below 25 mm. Despite the armoring, sharp bends can cause micro-fractures in the internal tube, leading to a loss of charge and total sensor failure.

  • Mounting and Vibration: The KPS series is highly vibration-resistant; however, for maximum longevity in marine engines or compressors, mount the housing on a vibration-damped surface and use the armored capillary to isolate the switch body from the direct heat and vibration of the medium.

  • Electrical Sealing: Ensure the Pg 13.5 metal cable gland is tightened correctly to maintain the enclosure's integrity. For installations in high-moisture environments, a "drip loop" in the wiring is recommended to prevent water from traveling down the cable and entering the terminal block.

 

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
دانمارک

Recently Viewed Products

Technical knowledge

راهنمای جامع فایروال‌های صنعتی و تقسیم‌بندی شبکه OT

فایروال‌های صنعتی نقش حیاتی در امنیت سایبری OT ایفا می‌کنند و از شبکه‌های PLC، DCS و SCADA از طریق بخش‌بندی، کنترل ورود/خروج و ادغام IDS/IPS مطابق با اصول IEC 62443 محافظت می‌کنند.

راهنمای گیره‌های رباتیک: از جابجایی ظریف تا اتوماسیون سنگین

گیره‌های رباتیک مدرن فراتر از فک‌های مکانیکی سنتی در حال پیشرفت هستند. از سیستم‌های چسبنده الهام‌گرفته از گکوی، گیره‌های نرم با درجه‌بندی غذایی تا ابزارهای انبار مجهز به هوش مصنوعی، فناوری‌های...

بازگشت به گذشته: چگونه موتورهای الکتریکی اولیه معدن‌کاری زیرزمینی را تغییر دادند

از کمپرسورهای جریان مستقیم با نیروی طناب تا واگن‌های معدنی باتری‌دار، عملیات‌های اولیه معدن‌کاری نقطه عطفی در برق‌رسانی صنعتی بودند. این مقاله بررسی می‌کند که چگونه موتورهای الکتریکی پیش از ورود...

Factory I/O: یک ابزار شبیه‌سازی PLC مدرن برای آموزش اتوماسیون صنعتی

Factory I/O آموزش PLC را با ارائه شبیه‌سازی‌های صنعتی سه‌بعدی فراگیر برای دانشجویان، مهندسان و تیم‌های نگهداری متحول می‌کند. این پلتفرم فاصله بین نظریه و عمل واقعی اتوماسیون را پر می‌کند و در عین حال...

برنامه‌نویسی چرخه‌های حرکت تک‌محور روی درایو سروو CMZ

این آموزش بررسی می‌کند که چگونه عملکرد PLC داخلی درایو سروو CMZ SBD می‌تواند برنامه‌های حرکتی مستقل را اجرا کند، از جمله منطق خانه‌یابی، کنترل موقعیت و حرکت دوره‌ای محور بدون نیاز به PLC خارجی.

راه‌اندازی کنترل حرکت تک‌محور با درایوهای سروو CMZ

این آموزش به راه‌اندازی سیستم حرکت سروو تک‌محوره با استفاده از درایو CMZ SBD می‌پردازد و شامل تنظیمات سخت‌افزاری، مقیاس‌بندی محور، پیکربندی موقعیت‌یابی اولیه و تأیید حرکت ایمن برای محیط‌های اتوماسیون...