1 / 1

084G2101 Danfoss EMP 2 Industrial Pressure Transmitter 5 bar

084G2101 Danfoss EMP 2 Industrial Pressure Transmitter 5 bar

Only 10 item(s) left in stock
  • Manufacturer: Danfoss

  • Product No.: 084G2101

  • Country of origin:Egyesült Államok

  • Product Type: Controles Industriales Pressure Transmitter

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Mennyiség
Minden részlet megtekintése

Product Overview

The 084G2101 (084G2101) is a rugged EMP 2 series pressure transmitter from Danfoss, engineered for demanding industrial and marine applications. Designed to measure a pressure range of -1 to 5 bar (-14.5 to 72.52 psi), this transmitter provides highly accurate feedback for both vacuum and low-pressure systems. It converts mechanical pressure into a standardized 4-20 mA current signal, ensuring reliable data transmission even over long distances. Built to withstand harsh environments, the 084G2101 features a sealed gauge pressure reference, an IP65-rated enclosure, and a high overload pressure limit of 35 bar, making it a critical component for monitoring hydraulic, pneumatic, and steam systems where signal stability and durability are paramount.

Technical Configuration

The 084G2101 utilizes a heavy-duty sensor platform optimized for signal integrity:

  • Sealed Gauge Reference: Provides a consistent baseline regardless of local atmospheric pressure changes or altitude, ensuring precision in diverse geographical locations.

  • Precision Current Loop: The 4-20 mA output is resistant to electrical noise and voltage drops, featuring low (3.6 mA) and high (22.4 mA) clipping levels for advanced error detection.

  • Robust Overload Protection: With a 35 bar maximum overload rating, the internal sensor is protected against pressure spikes up to seven times its maximum rated range.

  • Industrial Connection: Equipped with a versatile G 1/4 external and 1/2 inch internal thread per EN 228-1, supported by a Pg 13.5 electrical terminal block for secure field wiring.

Technical Specifications

Feature Specification
Model 084G2101 (EMP 2)
Brand Danfoss
Pressure Range -1 to 5 bar (-14.5 to 72.52 psi)
Output Signal 4 - 20 mA Current
Accuracy (Typical) 0.5% FS
Overload Pressure 35 bar
Response Time 4 ms max.
Supply Voltage 12 - 32 VDC
Electrical Connection Terminal Block (Pg 13.5 Gland)
Enclosure Rating IP65
Medium Temp. Range -10 to 70 deg C
Shipping Weight 2.0 kg

Technical FAQs

How do the clipping levels (3.6 mA and 22.4 mA) assist in troubleshooting?

These levels allow the controller to distinguish between a valid reading and a system fault. If the signal drops to 3.6 mA, it typically indicates a sensor error or extreme under-pressure. If it rises to 22.4 mA, it suggests a short circuit or over-pressure condition. A signal of 0 mA would immediately indicate a broken wire.

Is this transmitter suitable for marine engine rooms?

Yes. The EMP 2 series is specifically designed for marine and heavy industrial use. The IP65 enclosure and the vibration-resistant terminal block make the 084G2101 ideal for monitoring oil, water, or air pressures in the proximity of large engines and pumps.

Can the 084G2101 be used for vacuum applications?

Absolutely. With a minimum pressure range of -1 bar, this transmitter is fully capable of monitoring vacuum levels, making it useful for suction side monitoring in pumping stations or vacuum-assisted process control.


Engineering & Installation Guide

  • Wiring Protocol: The unit uses a 2-wire connection (P = Positive supply, N = Common). To maintain the 0.5% typical accuracy, use shielded twisted-pair cabling. The shield should be grounded only at the PLC or receiver end to prevent ground loops that could introduce signal offsets.

  • Terminal Maintenance: When performing field wiring via the Pg 13.5 gland, ensure the cable diameter matches the gland seal. Tighten the terminal block cover securely to maintain the IP65 rating; moisture ingress is the leading cause of signal drift in industrial transmitters.

  • Mounting for Longevity: For applications with high vibration, mount the transmitter on a rigid support. If the media temperature exceeds 70 deg C, use a siphon or capillary tube to dissipate heat before it reaches the sensor diaphragm to stay within the compensated temperature range of 0 to 70 deg C.

 

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Color pattern
Fehér
Country of origin
Egyesült Államok

Nemrég megtekintett termékek

Műszaki ismeretek

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...