1 / 1

BECKHOFF KL3062 Bus Terminal

BECKHOFF KL3062 Bus Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KL3062

  • Country of origin:Németország

  • Product Type: Analog Input Modules

  • Payment: T/T, Western Union

  • Weight: 60g

  • Shipping port: Xiamen

  • Warranty: 12 months

Mennyiség
Minden részlet megtekintése

Description

Processing analog input signals in the 0 to 10 V range, the BECKHOFF KL3062 Bus Terminal features two single-ended channels designed for direct connection to industrial sensors and transmitters. This compact input module converts analog physical values into digital signals with a 12-bit resolution, ensuring reliable signal transmission to the higher-level automation controller via the K-bus. Utilizing a common internal ground connection for both channels, the terminal minimizes wiring complexity in standard control cabinet installations.

The KL3062 provides comprehensive galvanic isolation up to 500 V between the input circuitry and the internal K-bus. Operating without the need for dedicated power contacts, the terminal derives its required operating power directly from the K-bus interface. The robust IP20 design and standard DIN rail mounting compatibility make it suitable for seamless integration in complex PLC and DCS architectures.

Features

  • Two independent analog input channels.
  • Single-ended measurement technology sharing a common reference ground.
  • Standard 0 to 10 V signal voltage range.
  • 12-bit analog-to-digital resolution.
  • Integrated galvanic electrical isolation up to 500 V (K-bus to signal voltage).
  • Fast conversion time of approximately 2 ms.
  • Low power consumption directly from the K-bus (typically 60 mA).
  • No address or hardware configuration required prior to commissioning.

Applications

  • Industrial process control and monitoring systems.
  • Pneumatic and hydraulic valve position feedback.
  • Integration with pressure transmitters, flow meters, and distance sensors.
  • Factory automation and machine building installations.
  • Hazardous area applications requiring compliant ATEX/IECEx intrinsically safe parameters.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model KL3062
Number of Inputs 2
Power Supply Via the K-bus
Signal Voltage Range 0 to 10 V
Technology Single-ended
Internal Resistance typ. > 200 kOhm
Conversion Time approx. 2 ms
Resolution 12 bit
Measurement Error < +/-0.3% (relative to full scale value)
Electrical Isolation 500 V (K-bus / signal voltage)
Current Consumption K-bus typ. 60 mA
Bit Width in Process Image Input: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration No address or configuration setting
Weight approx. 60 g
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95 %, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Installation Position Variable
Ex Marking ATEX: II 3 G Ex ec IIC T4 Gc, IECEx: Ex ec IIC T4 Gc

Connections and Interfaces

Terminal Point Function Assignment
1 Analog Input 1 (+)
5 Analog Input 2 (+)
3 0 V (Reference ground for Input 1)
7 0 V (Reference ground for Input 2)
4 Shield connection
8 Shield connection

Installation Guidelines

  • Mounting: Snap the module directly onto a standard 35 mm DIN rail (EN 60715). Ensure the locking mechanism engages securely.
  • Wiring: Use appropriate wire sizes with terminal connectors. For solid or stranded wires, ensure the maximum cross-section conforms to the terminal blocks' limit.
  • Shielding: Connect the analog cable shields to terminal points 4 or 8 to prevent electrostatic and electromagnetic interference from disrupting signal integrity.
  • Grounding: Ensure the DIN rail is grounded to a low-impedance earth system in compliance with standard electrical installation codes.

Compliance and Certifications

  • CE
  • UL
  • ATEX (II 3 G Ex ec IIC T4 Gc)
  • IECEx (Ex ec IIC T4 Gc)

What signal range does the Beckhoff KL3062 support?

The Beckhoff KL3062 processes standard analog voltage signals in the 0 to 10 V range.

Does the KL3062 require separate power contacts for operation?

No, the KL3062 is powered directly via the K-bus, drawing typically 60 mA of current. It does not utilize power contacts.

What is the resolution and conversion speed of this bus terminal?

The terminal features a 12-bit resolution with a conversion time of approximately 2 ms.

Are the input channels isolated from the rest of the system?

Yes, there is electrical isolation of 500 V between the signal voltage circuitry and the internal K-bus.

Is the KL3062 suitable for installation in hazardous areas?

Yes, the module is certified under ATEX (II 3 G Ex ec IIC T4 Gc) and IECEx for safe use in classified zone 2 hazardous locations.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Németország

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...