1 / 1

Beckhoff KL4022 Bus Terminal 2-Channel Analog Output Module

Beckhoff KL4022 Bus Terminal 2-Channel Analog Output Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KL4022

  • Country of origin:Németország

  • Product Type: Analog Output Modules

  • Payment: T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Mennyiség
Minden részlet megtekintése

Description

Designed for integration into standard K-bus networks, the Beckhoff KL4022 enables high-precision processing of current loop control signals. This terminal converts 12-bit digital values from the automation controller into isolated analog current outputs within the standard 4 to 20 mA range. Its single-ended topology, compact housing, and low conversion latency make it highly suitable for demanding industrial actuator control, valve positioning, and motor drive setpoint configuration.

Features

  • Dual-channel analog output configuration utilizing single-ended common ground architecture.
  • Robust 12-bit digital-to-analog conversion delivering dependable loop precision.
  • High-integrity electrical isolation of 500 V between the internal K-bus and field signals.
  • Rapid internal conversion sequence with a typical processing time of 1.5 milliseconds.
  • Efficient power distribution leveraging integrated 24 V DC power contacts on the backplane.

Applications

  • Electro-pneumatic and electro-hydraulic proportional valve positioners.
  • Frequency inverter and variable speed drive (VSD) speed references.
  • Distributed SCADA and process control instrumentation interfaces.
  • Industrial boiler and heating element loop controller feedback.

Technical Specifications

Parameter Value / Rating
Manufacturer Beckhoff Automation
Model Number KL4022
Signal Range 4 to 20 mA
Number of Channels 2
Resolution 12-bit
Load Impedance Less than 500 Ohm
Conversion Time approx. 1.5 ms
Output Error Less than +/- 0.1% (relative to full-scale value)
Power Supply 24 V DC via power contacts (or 15 V DC via KL9515 supply terminal)
K-Bus Current Consumption typ. 75 mA
Electrical Isolation 500 V (K-bus / signal voltage)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95%, non-condensing
Country of Origin Germany
Weight approx. 80 g
Shipping Weight (Calculated) 0.25 kg

Connections and Interfaces

Terminal Point Signal Assignment Description
1 OUT 1 Analog Output Channel 1 (+)
5 0V (1) Analog Output Channel 1 ground (-)
2 OUT 2 Analog Output Channel 2 (+)
6 0V (2) Analog Output Channel 2 ground (-)
3 +24 V Power Contact Connection (+24 V DC)
7 0 V Power Contact Connection (0 V DC)
4 Shield Shield contact point (connected to DIN rail)
8 Shield Shield contact point (connected to DIN rail)

Empirical Engineering Insights

Alternative Models & Compatibility

The KL4022 utilizes Beckhoff's legacy K-bus backplane communication system. If transitioning to an EtherCAT infrastructure, the direct equivalent is the EL4022. Note that EL-series terminals utilize the E-bus and cannot reside on standard KL-series couplers (e.g., BK9000, BK3120) without active E-bus/K-bus converter couplers.

Application Pitfalls & Engineering Notes

Since the KL4022 is a single-ended terminal sharing a common internal ground loop, noise injected into the 0 V signal reference on one loop can cause cross-talk or offset drift on the secondary channel. For field installations with significant ground potential differences, isolated signal conditioning barriers must be installed between the KL4022 and the end-actuator to prevent loop degradation.

Commissioning & Wiring Tips

Ensure that shielding is correctly terminated. Terminal points 4 and 8 are connected to the mounting rail. To guarantee sufficient noise rejection, the standard 35 mm DIN rail must be connected to the central control cabinet ground with low-impedance copper braided strap. Ensure K-bus power contacts are adequately populated with 24 V DC; voltage drops below 18 V DC will cause conversion errors or terminal fault signals within TwinCAT.

Installation Guidelines

CRITICAL WARNING: ELECTRICAL HAZARD

Isolate and lock out all power supplies to the system before inserting or removing K-bus components. Modifying the physical configuration or terminal assembly while the power is active can induce voltage spikes, resulting in damage to the internal bus driver circuitry or physical terminal contacts.

1

Mount the terminal onto the 35 mm DIN rail (EN 60715) by sliding the terminal's rear slot onto the rail guide until the locking tab audibly clicks.

2

Align the terminal laterally with the adjacent Bus Terminal block to engage the tongue-and-groove joint and establish continuous electrical contact via the side-mounted gold contacts.

3

Insert field connection cables into the cage-clamp connectors using an appropriate industrial screwdriver. Release the mechanism to secure wire connection.

4

Connect the analog loop shielding directly to contacts 4 or 8 to guarantee direct path grounding through the DIN rail structure.

What is the key difference between the KL4022 and EL4022 modules?

The KL4022 operates on the K-bus backplane protocol for classic bus couplers, whereas the EL4022 communicates via E-bus for EtherCAT networks. They cannot be placed on the same terminal strip without a dedicated converter terminal.

Does this terminal require an external loop power supply for the current signal?

The KL4022 extracts its power from the integrated 24 V DC power contacts. If the power Contacts are not energized, or if isolation is required, you must insert a power supply terminal like the KL9100 or KL9200 immediately to its left.

How is the 12-bit resolution represented inside the controller software?

The 12-bit value is loaded into a 16-bit register as a left-aligned integer. The remaining 4 least-significant bits are ignored by the internal digital-to-analog converter.

Are the two output channels of the KL4022 electrically isolated from each other?

No, both channels share a common internal ground reference (0 V) and are single-ended. However, they are both electrically isolated up to 500 V from the K-bus logic circuitry.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Németország

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...